Title Page
-
Installation and Commissioning Checklist
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
Installation Details
-
PV Array Tilt degrees
-
PV Array Orientation Degrees
PV Module Details
-
PV Module Manufacturer
-
PV Module Model Number
-
Number of Panels in total
Inverter details
-
Type of system
-
Number of Inverters
- 1
- 2
- 3
- 4
- 5
- 6
Inverter #1 Details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of modules in series in a string for MPPT 2
-
Number of Strings in Parallel on MPPT 2
Inverter #2 Details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of modules in series in a string for MPPT 2
-
Number of Strings in Parallel on MPPT 2
Inverter #3 Details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of modules in series in a string for MPPT 2
-
Number of Strings in Parallel on MPPT 2
Inverter #4 details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of Modules in Series on MPPT 2
-
Number of Strings in Parallel on MPPT 2
Inverter #5 details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of Modules in Series on MPPT 2
-
Number of Strings in Parallel on MPPT 2
Inverter #6 details
-
Inverter Manufacturer
-
Inverter Model Number
-
Number of MPPT's
-
Number of modules in series in a string for MPPT 1
-
Number of Strings in Parallel on MPPT 1
-
Number of Modules in Series on MPPT 2
-
Number of Strings in Parallel on MPPT 2
System Checks
-
Irradiance at the time of testing? A clear sunny day measures 1000W/m2
PV Array
-
Array Frame is certified to AS1170.2 for installation location
-
No galvanically similar metals are in contact with the array frame or supports
-
Array Frame is installed to manufacturer's instructions
-
Roof penetrations are suitably sealed and weatherproofed
-
PV wiring losses are less than 3% at the maximum current output of the array
-
When PV array comprises multiple strings- string protection has been provided
-
Wiring is protected from mechanical damage and is appropriately supported
-
Weatherproof DC isolator mounted adjacent to the array
-
DC isolator Voltage rating
-
DC isolator Current rating
LV DC & AC Installation
-
All low voltage wiring has been installed by a licensed electrical tradesperson
-
All wiring has been tested and approved by a qualified electrical tradesperson
Inverter
-
PV array isolator is mounted adjacent to the invertor
-
DC isolator Voltage rating
-
DC isolator Current rating
-
Isolator is mounted on the output of the inverter if required
-
Lockable AC circuit breaker mounted within the switchboard to act as the inverter main switch for the PV/Inverter system
-
Circuit breaker rating
- 10 Amp
- 16 Amp
- 20 Amp
- 25 Amp
- 32 Amp
- 40 Amp
- 50 Amp
-
Circuit breaker number of phases
-
If multiple inverters please list circuit protection provided
-
Inverter is installed as per manufacturer's specification
-
Inverter ceases supplying power within two seconds of a loss of AC mains
-
Inverter does not resume supplying power until mains have been present for more than 60 seconds