Title Page
-
Audit Title
-
Switchboard Designation
-
Asset no. (If applicable)
-
Switchboard photos
-
Is there a circuit schedule present/are sub circuits clearly labelled?
Chassis
-
Does the switchboard have multiple chassis?
Chassis
-
Chassis Designation
RCDs
-
Are there RCDs present?
-
Type of RCD test being performed?
- Test Button only
- Timed Test and Test Button
RCD
-
Circuit Designation
-
Trip time @ 0° (milliseconds)
-
Trip time @ 180° (milliseconds)
-
Does this comply with AS/NZS 3000 and AS/NZS 3760?
RCD
-
Circuit Designation
-
Does this comply with AS/NZS 3000 and AS/NZS 3760?
Thermography
-
Thermal image numbers:
-
Priority category/Delta TK
- Priority 4: SP1 max temp <50°C and/or ΔT <10°
- Priority 3: SP1 max temp 50°C - 75°C and/or ΔT 10°C - 20°C
- Priority 2: SP1 max temp 75°C - 100°C and/or ΔT 20° - 30°C
- Priority 1: SP1 max temp >100°C and/or ΔT >30°C
-
Further action for Priority 1, Priority 2 or Priority 3 items:
Visual Inspection
-
Does the switchboard appear to be in good condition?
- Excellent condition
- Good condition
- Fair condition
- Switchboard in need of attention
-
Switchboard is clean and free of debris
-
Further action required:
-
Photos of visual defects
-
Comments:
Auditor Information
-
Add signature
-
Electrical Licence Number