Title Page
-
Audit Title
-
Asset no. (If applicable):
-
Switchboard location:
-
Switchboard photos
Mains Cable Protection and Information
-
Switchboard is fed from:
-
Rating and classification of protection upstream if accessible:
-
Photo of protective device
-
Rating and classification of Main Circuit Breaker:
-
Mains cable CSA:
-
Current measured (L1/L2/L3/N):
Earthing
-
Main Earth attached and in good condition?
-
Main Earth CSA:
-
Multiple Earthed Neutral (MEN) link present and securely attached?
Surge Diverters
-
Are surge diverters present and in good condition?
Distribution Chassis
-
Does the switchboard have multiple chassis?
Chassis
-
Chassis Designation
-
Rating and classification of chassis protective device:
-
Is there a circuit schedule present/are sub circuits clearly labelled?
-
Are there spare poles/is there capacity for future expansion?
Thermography
-
Thermal image numbers:
-
Priority category/Delta TK:
- Priority 4: SP1 max temp <50°C and/or ΔT <10°
- Priority 3: SP1 max temp 50°C - 75°C and/or ΔT 10°C - 20°C
- Priority 2: SP1 max temp 75°C - 100°C and/or ΔT 20° - 30°C
- Priority 1: SP1 max temp >100°C and/or ΔT >30°C
-
Further action for Priority 1, Priority 2 or Priority 3 items:
Visual Inspection
-
Does the switchboard appear to be in good condition?
- Excellent condition
- Good condition
- Fair condition
- Switchboard in need of attention
-
Switchboard is clean and free of debris
-
Further action required:
-
Photos of visual defects
-
Comments:
Auditor Information
-
Electrical Licence Number
-
Add signature