Title Page
-
Audit Title
-
INSPECTION REPORT FOR MSSBs
CVSG ASSET SERVICES PTY LTD
ABN 62 128 821 698
INSPECTION DETAILS
-
Select date
-
NAME OF PERSON UNDERTAKING TESTS
-
NAME OF FACILITY?
-
SWITCHBOARD NUMBER
-
SWITCHBOARD TYPE
-
ASSET NO. BAR CODE AVAILABLE?
-
Enter barcode
INSPECTION
-
All electrical equipment & fittings in good condition?
-
Remove front panel, dust and clean components, remove accumulated rubbish and redundant wiring.
-
Check that all indicator lights are working.
-
Check fuse sizes correspond with those in the drawings.
-
Visually check all wiring and tidy up where necessary, check all connections including earthing.
-
Check chiller contactors thoroughly for signs of excessive arcing on contacts.
-
Check fire isolation relays, vibration switches, reverse phase relays, phase failure relays etc. check all contacts for signs of excessive pitting.
-
Check set point and operation of all motor running amps.
-
Provide details of follow up if required.
SWITCHBOARD ROOM / CUPBOARD
-
Check clearance around switchboard. Ensure rubbish, spare parts, stock etc does not infringe on mandatory clearances around switchboard.
-
Check effectiveness of ventilation of switch room
-
Vacuum clean floor space.
-
Provide detail of follow up if required.
SWITCHBOARD
-
Check effectiveness of ventilation of switchboard cubicles (if applicable). Clean and/or replace filter(s) if fitted.
-
Open and/or remove all doors, access panels, cable covers, escutcheon panels etc and carry out the following work: • Inspect for any evidence of dampness or condensation • Check operation of any heater and inspect any anticondensation finishes for signs of deterioration • Check for smells that might indicate overloading or deterioration of equipment/components. • Check for noises that might indicate electrical discharge, tracking or looseness of components or equipment that requires servicing eg contactors • Inspect insulation for signs of deterioration or tracking • Inspect switchgear, controls, cabling, busbars etc for dust build-up, signs of overheating/loose connections and general condition of equipment • Check any penetrations in the switchboard are sealed • Check for rodent/pest infestation. Treat and clean as required Close and/or reinstall doors, access panels, cable covers, escutcheon panels etc after the thermoscan and all other items have been completed. Ensure all fixings for panels etc are installed and securely tightened.
-
Check labels are legible and suitably attached. Refix any labels that have been dislodged.
-
Check circuit schedules are available and legible.
-
Clean all external surfaces of the switchboard to remove any dust.
-
Take tong ammeter readings of incoming supply and distribution cables.
-
A phase current.
-
B phase current
-
C Phase current
-
Provide detail of follow up if required.
SURGE DIVERTERS
-
• Inspect condition of surge diverters, where fitted, in accordance with manufacturer's instructions and report if less then 50% of life remaining • Inspect existing surge diverters to determine if they visually indicate the integrity of the surge diverter protection • Inspect all main switchboards to determine if surge diverters are fitted Report to Principal’s Representative your findings above.
-
Provide detail of follow up if required.
INSPECTION COMPLETE
-
Add signature