  • INSPECTION REPORT FOR SWITCHBOARDS
    CVSG ASSET SERVICES PTY LTD
    ABN 62 128 821 698

    Conducted in accordance with:
    AS/NZS 3003:2011 ELECTRICAL INSTALLATIONS - PATIENT AREAS

INSPECTION DETAILS

  • Select date

  • NAME OF PERSON UNDERTAKING TESTS

  • NAME OF FACILITY?

  • Add location
  • LOCATION OF TEST - ROOM NO.?

  • SWITCHBOARD NUMBER

  • SWITCHBOARD TYPE

  • Type of Inspection?

  • ASSET NO. BAR CODE AVAILABLE?

INSPECTION

  • All electrical equipment & fittings in good condition?

  • Wiring and switches - Check general condition of conduits, connectors, switches and wiring especially in damp and outdoor areas.

  • Operation - Check to ensure all items of equipment are capable of satisfactory operation.

  • Contacts and relays - Check and clean contacts or relays. Notify the Principal’s Representative of any faulty contacts or relays that need replacement.

  • Overload ratings - Check overload ratings against motor nameplate ratings.

  • Fuses Check all fuses for correct rating. Check fuse connections are tight. Inspect fuse-links for signs of deterioration.

  • Electrical connections - Check connections at motors, switchboards and equipment subject to vibration. Re-tighten cable terminations as necessary

  • Interpole barriers - Inspect interpole barriers and shrouds where fitted.

  • Cable insulation - Check cable insulation. Notify the Principal’s Representative of any damaged or faulty exposed cable insulation.

  • Switchboard - Vacuum clean the switchboard interior and remove an rubbish.

  • Door / panel seals - Check door / panel seals. Notify the Principal’s Representative of any damaged or faulty seals.

  • Wiring diagrams Check and report where wiring diagram(s) are considered to be incorrect. This diagram should preferably be laminated and wall mounted.

  • Earthing Check continuity to earth.

  • Neutral current Check and record neutral current.

  • General Perform service items listed in Clause 5.1. 5.1 Switchboards Supplying Fire Safety Installations Perform all of the service requirements as detailed under for the following switchboards: • Main fire and essential services switchboard supplying fire safety installations • Air conditioning switchboards / stair pressurisation switchboards / motor control centres supplying fire safety installations where fans operate under fire alarm mode

  • Indicating lights Check operation and replace lamps as required.

  • Meters Record all meter readings including instantaneous and maximum demand values and the date. Reset maximum demand meters.

  • Combined Fuse Switches (CFS Units): • Open switch and door and check operation of indicator • Withdraw moving fuse contact carrier and arc chamber • Check fuse-links for signs of deterioration and connection tightness • Verify fuse ratings are correct • Inspect contact surfaces, and clean, treat and/or adjust contacts in accordance with manufacturer's instruction • Clean and lubricate switch mechanism • Re-assemble unit and test operation.

  • Switchgear including ACBs, contactors, isolators, busties, controls, etc • Inspect indicating devices such as mechanical 'ON' and 'OFF' indicators, etc to ensure that they are in good order and operating correctly • Verify that interlocks and padlocking devices operate correctly and make adjustments where required eg castel key interlocks for main isolators and bus-tie switches, automatic transfer switches.

  • Insulation resistance Check and record insulation resistance levels of the main switchboard for each transformer fed section for the following: • Each phase to phase • Each phase to neutral • Each phase to earth. NOTE: Test voltages shall be 1 kV for main circuits and shall not exceed 500 V for small wiring and ancillary components.

SWITCHBOARD ROOM / CUPBOARD

  • Check clearance around switchboard. Ensure rubbish, spare parts, stock etc does not infringe on mandatory clearances around switchboard.

  • Check clear access to and from exit doors for switch rooms

  • Check all exit doors are clearly labelled and are properly secured to prevent the entrance of an unauthorised person from outside whilst at all times allowing free escape from inside.

  • Check effectiveness of ventilation of switch room

  • Vacuum clean floor space.

SWITCHBOARD

  • Check effectiveness of ventilation of switchboard cubicles (if applicable). Clean and/or replace filter(s) if fitted.

  • Open and/or remove all doors, access panels, cable covers, escutcheon panels etc and carry out the following work: • Inspect for any evidence of dampness or condensation • Check operation of any heater and inspect any anticondensation finishes for signs of deterioration • Check for smells that might indicate overloading or deterioration of equipment/components. • Check for noises that might indicate electrical discharge, tracking or looseness of components or equipment that requires servicing eg contactors • Inspect insulation for signs of deterioration or tracking • Inspect switchgear, controls, cabling, busbars etc for dust build-up, signs of overheating/loose connections and general condition of equipment • Check any penetrations in the switchboard are sealed • Check for rodent/pest infestation. Treat and clean as required Close and/or reinstall doors, access panels, cable covers, escutcheon panels etc after the thermoscan and all other items have been completed. Ensure all fixings for panels etc are installed and securely tightened.

  • Check labels are legible and suitably attached. Refix any labels that have been dislodged.

  • Check circuit schedules are available and legible.

  • Check for signs of corrosion and/or condition of : • Paint • Door locking handles and levers • Hinges • Cable access points.

  • Clean all external surfaces of the switchboard to remove any dust.

SURGE DIVERTERS

  • • Inspect condition of surge diverters, where fitted, in accordance with manufacturer's instructions and report if less then 50% of life remaining • Inspect existing surge diverters to determine if they visually indicate the integrity of the surge diverter protection • Inspect all main switchboards to determine if surge diverters are fitted Report to Principal’s Representative your findings above.

INSPECTION COMPLETE

  • INSTALLATION COMPLIANT WITH AS/NZS 3003:2011?

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.