  • INSPECTION REPORT FOR BODY-PROTECTED ELECTRICAL AREAS

    CVSG ASSET SERVICES PTY LTD
    ABN 62 128 821 698

    Conducted in accordance with:
    AS/NZS 3003:2011 ELECTRICAL INSTALLATIONS - PATIENT AREAS

INSPECTION DETAILS

  • Select date

  • NAME OF PERSON UNDERTAKING TESTS

  • NAME OF FACILITY?

  • Add location
  • LOCATION OF TEST - ROOM NO.?

  • ASSET BARCODE AVAILABLE?

INSPECTION

  • All electrical equipment & fittings in good condition?

LABELLING

  • Circuit identification visible and intact on each?

  • Protected points labelled as to which RCD protects them?

  • Circuit identification visible and intact on each LIM?

  • Protected points labelled as to which LIM monitors them?

  • Overload monitors labelled with alarm setting?

  • Socket-outlets protected by RCD labelled ‘RCD PROTECTED’?

  • Socket-outlets protected by Isolating transformers labelled ‘ISOLATING TRANSFORMER PROTECTED’?

  • Socket-outlets intended for cleaning purposes labelled ‘CLEANING PURPOSES ONLY’?

  • Body-protected electrical area sign:<br>Still visible.<br>Labelled with current inspection date.<br>Labelled with identity of authorized person.<br>Labelled with next test date.

SOCKET OUTLETS

  • Socket-outlets coloured according to type of supply

  • If RCD protected, power-available indicator operational?

  • Number of socket-outlets and permanently wired electrical equipment protected by RCD does not exceed 12?

  • On/off luminous indicators operational, if applicable?

  • Socket-outlets double-poled if protected by a transformer-isolated supply?

  • All socket-outlets below 2.3 m protected by LPD?

  • Confirm each socket-outlet trips the RCD when fault applied?

  • Confirm each socket-outlet causes a response on LIM when a fault is applied?

EARTHING

  • Confirm that the earth pin of all socket-outlets below 2.3 m are earthed to less that 1 Ω?

  • Confirm that all socket-outlets used by electrical appliances accessible below 2.3 m are earthed to less that 1 Ω?

  • Confirm that all permanently wired appliances with conductive parts below 2.3 m are earthed to less than 1 Ω?

RCD SENSITIVITY (AUS)

  • Confirm that the RCD trips at a value greater than 4.5 mA.

  • Record the RCD sensitivity (mA)

RCD TRIPPING TIMES (AUS)

  • Confirm this by repeating the test at least 2 times.

  • Record the worst case (mA)

RCD SUPPLY AVAILABLE INDICATOR LIGHTS

  • If applicable, confirm that they are operational.

AUDIO VISUAL RCD TRIP INDICATORS

  • If applicable, confirm that they are operational.

PROSPECTIVE HAZARD CURRENT

  • Confirm that the hazard current is below 2 mA.<br>

  • Record hazard current (mA)

OVERLOAD MONITORS

  • Confirm that a load of 110–120% of transformer rated current causes the alarm to activate in 3–5 s

UNINTERRUPTIBLE POWER SUPPLIES (UPS)

  • Confirm that UPS status indicator performance is routinely verified.

INSPECTION COMPLETE

  • INSTALLATION COMPLIANT WITH AS/NZS 3003:2011?

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.