Title Page
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
-
INSPECTION REPORT FOR CARDIAC-PROTECTED ELECTRICAL AREAS
CVSG ASSET SERVICES PTY LTD
ABN 62 128 821 698
Conducted in accordance with:
AS/NZS 3003:2011 ELECTRICAL INSTALLATIONS - PATIENT AREAS
INSPECTION DETAILS
-
Select date
-
NAME OF PERSON UNDERTAKING TESTS
-
NAME OF FACILITY?
-
Add location
-
LOCATION OF TEST - ROOM NO.?
-
ASSET BARCODE AVAILABLE?
UNINTERRUPTIBLE POWER SUPPLIES (UPS)
-
Confirm that UPS status indicator performance is routinely verified.
INSPECTION
-
All electrical equipment & fittings in good condition?
LABELLING
-
Circuit identification visible and intact on each?
-
Relevant electrical points labelled to identify associated RCDs?
-
Circuit identification visible and intact on each LIM?
-
Relevant electrical points labelled to identify associated LIMs?
-
Overload monitors labelled with alarm setting?
-
Socket-outlets protected by RCD labelled ‘RCD PROTECTED’?
-
Socket-outlets protected by Isolating transformers labelled ‘ISOLATING TRANSFORMER PROTECTED’?
-
Socket-outlets intended for cleaning purposes labelled ‘CLEANING PURPOSES ONLY’?
-
Body-protected electrical area sign:<br>Still visible.<br>Labelled with current inspection date.<br>Labelled with identity of authorized person.<br>Labelled with next test date.
SOCKET OUTLETS
-
Socket-outlets coloured according to type of supply
-
If RCD protected, power-available indicator operational?
-
Number of socket-outlets and permanently wired electrical equipment protected by RCD does not exceed 12?
-
On/off luminous indicators operational, if applicable?
-
Socket-outlets double-poled if protected by a transformer-isolated supply?
-
All socket-outlets below 2.3 m protected by LPD?
-
Confirm each socket-outlet trips the RCD when fault applied?
-
Confirm each socket-outlet causes a response on LIM when a fault is applied?
-
Confirm that RCDs do not protect socket-outlets in another patient location?
EARTHING
-
Confirm that the earth pin of all socket-outlets below 2.3 m are earthed to less that 0.1 Ω?
-
Confirm that all permanently wired appliances with conductive parts below 2.3 m are earthed to less that 0.1 Ω with respect to EP junction node or other appliances.
POTENTIAL DIFFERENCE BETWEEN ACCESSIBLE METAL EQUIPMENT
-
Confirm that the potential difference does not exceed 50 mV between EP junction and—
-
Earthing pins of at least 2 socket-outlets in each patient location.
-
Reticulated plumbing pipework services<br>
-
Accessible conductive parts of permanently wired electrical equipment that are accessible in patient environment:<br>Surgical luminaires and patient examination lights.<br>Pendants.<br>Imaging systems.<br>Equipment mounting rails.
RCD SENSITIVITY (AUS)
-
Confirm that the RCD trips at a value greater than 4.5 mA and less than 10.5mA
RCD TRIPPING TIMES (AUS)
-
Confirm this by repeating the test at least 2 times.
-
Record the worst case (mA)
RCD SUPPLY AVAILABLE INDICATOR LIGHTS
-
If applicable, confirm that they are operational.
AUDIO VISUAL RCD TRIP INDICATORS
-
If applicable, confirm that they are operational.
PROSPECTIVE HAZARD CURRENT OF INSUALTION
-
Ensure PHC is less than 2 mA when no appliance is plugged in.
-
Record hazard current (mA)
LIM PROSPECTIVE HAZARD CURRENT ALARM
-
Confirm that the LIM alarms between 17 and 19 mA. Record alarm current (mA)
OVERLOAD MONITORS
-
Confirm that a load of 110–120% of transformer rated current causes the alarm to activate in 3–5 s
INSPECTION COMPLETE
-
INSTALLATION COMPLIANT WITH AS/NZS 3003:2011?
-
Add signature