Title Page

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

  • COMMISSIONING INSPECTION REPORT FOR CARDIAC-PROTECTED ELECTRICAL AREAS

    CVSG ASSET SERVICES PTY LTD
    ABN 62 128 821 698

    Conducted in accordance with:
    AS/NZS 3003:2011 ELECTRICAL INSTALLATIONS - PATIENT AREAS

  • Select date

  • NAME OF PERSON UNDERTAKING TESTS

  • NAME OF FACILITY?

  • ENTER FACILITY ADDRESS
  • LOCATION OF TEST - ROOM NUMBER

  • ASSET BARCODE AVAILABLE?

  • ENTER BARCODE

GENERAL REQUIREMENTS FOR BODY-PROTECTED AND CARDIAC-PROTECTED ELECTRICAL AREAS

  • 2.1 Body-protected or cardiac-protected electrical areas shall not occur in the same room?

CLASSIFICATION OF PATIENT AREAS

  • 2.2.2.1 Compliance: Check by inspection; verify boundaries of <br>protected electrical areas.

  • 2.2.2.2 Compliance: Verify no remote equipment with conductive or <br>applied parts in protected electrical area; verify boundaries <br>of protected electrical areas.

  • 2.2.3 Compliance: Check by inspection; verify boundaries of <br>protected electrical areas.

SUPPLY OF ELECTRICITY TO PATIENT AREAS LOW-VOLTAGE A.C. SUPPLIES

  • 2.4.1 Compliance: Verify that body-protected or cardiac-protected <br>electrical final sub-circuits are unique to respective rooms in <br>body-protected electrical areas and to individual patient <br>locations in cardiac-protected electrical areas.

  • Compliance: Verify that cleaning outlets are on a separate <br>electrical sub-circuit to other socket-outlets in the room.

  • 2.4.2 Compliance: Obtain written statement of compliance with <br>AS/NZS 3000 from the electrical contractor or the electrician <br>who did the work.

  • 2.4.3.2(a) Compliance: Verify by inspection and testing that all socket-outlets<br>are protected by LPD:

  • Socket-outlets in patient areas.

  • Socket-outlets within specified distance of entrance to <br>patient areas.

  • Socket-outlets in another room for medical electrical <br>equipment with conductive parts accessible within patient <br>environment or area.

  • 2.4.3.2(b) Verify all types of sockets in areas protected by LPD.

  • 2.4.3.3 Compliance: For permanently wired medical electrical <br>equipment with Type B applied parts, verify if it is being used <br>or is going to be used in area and test the LPD.

  • Compliance: For other permanently wired medical electrical <br>equipment, obtain written statement of compliance with <br>AS/NZS 3000 from the electrical contractor or the electrician <br>who did the work.

  • 2.4.4 (a) Compliance: Verify by inspection and confirmation of use.

  • 2.4.4 (b) Compliance: Verify by inspection and confirmation of use.

  • 2.4.4 (c) Compliance: Verify by inspection and confirmation of use.

  • 2.4.4 (d) Compliance: Verify by inspection, confirmation of use and <br>marking.

  • 2.4.5.1(a) Compliance: Verify by inspection and testing.

  • 2.4.5.1(b) Compliance: Verify by inspection and testing.

  • 2.4.5.2 Compliance: Verify by inspection and operation.

  • 2.4.5.1(c) Compliance: Verify by inspection and testing.

LOW-VOLTAGE D.C. SUPPLIES

  • 2.5 Compliance: Verify by inspection and current measurement. <br>Include and check the surgical lights battery back-up system.

ACCESS TO CONTROLS AND INDICATORS

  • 2.6(a) Compliance: Verify by inspection.

  • 2.6(b) Compliance: Verify by inspection and measurement.

LOW-VOLTAGE SOCKET-OUTLETS

  • 2.7.1 Compliance: Using the health care facility’s <br>brief/specification/instruction, verify socket-outlet quantity <br>and number on a circuit.

  • 2.7.2 Compliance: Verify by inspection.

  • 2.7.3.1 Compliance: Verify label and exact wording used; verify <br>location and distance measurement.

  • 2.7.3.2 Compliance: Verify by inspection and testing.

  • 2.7.4.1 Compliance: Verify by inspection that labelling is consistent <br>and identifies respective RCD.

  • 2.7.4.2 Verify ‘ON’ indication.

  • 2.7.4.5 Compliance: Verify by inspection and exact wording used.

  • 2.7.4.4 Compliance: Verify indicator colour and operation; verify <br>exact wording used.

  • 2.7.4.3 Compliance: Verify electricity supply source to AS/NZS 3009 <br>and associated socket-outlet colouring.

  • 2.7.5.1 Compliance: Verify by testing—All socket-outlets must be <br>double-poled.

  • 2.7.5.2 Compliance: Verify by inspection and testing.

RESIDUAL CURRENT DEVICES (RCDS)

  • 2.8.1 Compliance: RCDs; Verify Type I RCDs in use.

  • Verify RCD sensitivity using tests in this Standard (and <br>record results).

  • Verify RCD maximum tripping time using tests in this <br>Standard (and record results).

  • 2.8.4(a) Compliance: Verify by inspection and testing (and record <br>results).

  • 2.8.2 Compliance: Verify by inspections and testing of upstream <br>protection and discrimination.

  • 2.8.3 Compliance: Verify by testing that all RCDs double poled.

  • 2.8.4(b) Compliance: Verify by inspection and testing (and record <br>results).

  • 2.8.5 Compliance: Verify indicator colour and operation.

  • 2.8.4(c) Compliance: Verify by inspection and testing (and record <br>results).

  • 2.8.7 Compliance: Verify by inspection and testing.

  • 2.8.6 Compliance: Verify by inspection that labelling is consistent <br>and identifies respective circuit and RCD.

LOW-VOLTAGE ISOLATED SUPPLIES

  • 2.9.1 Compliance: Verify by inspection and testing. Obtain written <br>statement of compliance with AS/NZS 4510 from the <br>electrical contractor or the electrician who did the work.

  • 2.9.2 Compliance: Verify ventilation and line of sight operation.

  • 2.9.7(a) Compliance: Verify by inspection.

  • 2.9.3 Compliance: Verify by inspection and testing using tests in <br>this Standard (and record results).

  • 2.9.4 Compliance: LIMs <br>Verify LIM prospective hazard current display and current <br>alarm using tests in this Standard (and record results).

  • Verify by inspection that labelling is consistent and identifies <br>circuit and LIM.

  • 2.9.5 Compliance: Verify size of MCB by inspection in conjunction <br>with isolating transformer specifications. Confirm MCB rating <br>is less than or equal to the primary current rating of <br>transformer and is not less than the set point of the overload <br>alarm.

  • 2.9.6 Compliance: Verify each transformer-isolated supply is <br>below the prospective hazard current of the supply using <br>tests in this Standard (and record results).

  • 2.9.7(b) Compliance: Verify by inspection.

  • 2.9.8 Compliance: Verify by inspection.

ISOLATION SWITCHES

  • 2.10 Compliance: Verify by inspection for accessibility and testing <br>that isolation switch is double-poled; verify correct labelling.

MARKING

  • 2.11.1 Compliance: Verify by inspection and measurement (where <br>required).

  • 2.11.2 Compliance: Verify patient area signage installed in correct <br>location and appropriate labels attached and signed.

TESTING AND COMMISSIONING OF ELECTRICAL WORK

  • 2.12 Compliance: Obtain written statement of compliance with <br>AS/NZS 3000 from the electrical contractor or the electrician <br>who did the work.

CERTIFICATION

  • 2.13 Certification tests undertaken by a licensed inspector, <br>qualified medical physicist, qualified biomedical engineer or <br>person(s) acceptable to the health care facility.

ADDITIONAL REQUIREMENTS FOR CARDIAC-PROTECTED ELECTRICAL AREAS EXTRA-LOW-VOLTAGE SUPPLIES

  • 4.2.2 Compliance: Obtain written statement of compliance with <br>extra low-voltage Section of AS/NZS 3000 from the electrical <br>contractor or the electrician who did the work.

  • 4.2.3 Compliance: Verify by measurement.

DISPOSITION OF ELECTRICAL POINTS CONTROLLED BY RCDS

  • 4.3 Compliance: Verify by tripping all RCDs in a particular <br>patient location, to confirm that socket-outlets in any other <br>patient location(s) are not protected.

EARTHING AND EQUIPOTENTIAL BONDING

  • 4.4.1 Compliance: Sight written statement of compliance with <br>AS/NZS 3000 from the electrical contractor or the electrician <br>who did the work.

  • Compliance: Verify by measuring the voltage between the <br>EP junction and a representative number of nominated <br>points using a measuring instrument complying with <br>Appendix D.

  • 4.4.2.2 Compliance: Verify by inspection.

  • 4.4.2.3 Compliance: Equipotential earthing system; Verify by inspection that only one EP junction is in use.

  • Where separate nodes in use: Measure resistance to EP <br>junction and verify label wording.

  • Imaging system: Measure resistance to EP junction.

  • 4.4.2.4 Compliance: Verify by inspection and testing that each <br>socket-outlet is connected to the EP Junction:

  • Compliance: Verify resistance of earthing conductor between <br>socket-outlet and EP junction ≤0.1 Ω.Compliance: Verify resistance of earthing conductor between socket-outlet and EP junction ≤0.1 Ω.

  • Socket-outlets within cardiac-protected electrical area.

  • Socket-outlets within specified distance of entrance to <br>cardiac-protected electrical area.

  • Socket-outlets in another room for medical electrical <br>equipment with conductive parts accessible within cardiac-protected<br>electrical area.

  • Compliance: Verify protective earthing conductors are <br>insulated and segregated from other conductive items.

  • 4.4.2.5 Compliance: Verify by inspection and measurement that <br>each item of permanently installed electrical equipment <br>connected to the EP junction has a resistance ≤0.1 Ω.

  • Compliance: Verify protective earthing conductors are <br>insulated and segregated from other conductive items.

  • Compliance: Verify by inspection that each item of <br>permanently installed electrical equipment inaccessible in <br>the patient environment is earthed to the distribution board <br>or to the EP Junction using an earthing conductor.

  • 4.4.2.6 Compliance: Verify by inspection and measurement that <br>each item of permanently installed non-electrical equipment <br>or fittings in contact with structural metal in the patient <br>environment is connected to the EP Junction and has a <br>resistance ≤0.1Ω.

  • Compliance: Measure resistance of each point not connected to the EP junction.

  • Compliance: Verify earthing conductors are insulated and <br>segregated from other conductive items.

  • 4.4.2.7 Compliance: Verify earthing connections by inspection.

  • 4.4.2.9 Compliance: Verify EP test facility location and labelling by <br>inspection.

  • 4.4.2.8 Compliance: Verify EP junction location and labelling by <br>inspection.

  • 4.4.3 Compliance: Sight written statement of compliance with <br>AS/NZS 3000 from the electrical contractor or the electrician <br>who did the work.

SPECIAL PATIENT AREAS - HOME CARE INSTALLATION

  • 5.2.1 Compliance: Verify by inspection and testing.

  • 5.2.2.1 Compliance: Confirm equipment classification.

  • 5.2.2.2 Compliance: Verify by inspection and testing.

INSTALLATION FOR SELF-HARM PATIENTS

  • 5.3.1 Compliance: Exception noted for areas specified.

  • 5.3.2 Compliance: Verify by inspection.

ALTERATIONS, ADDITIONS AND REPAIRS TO ELECTRICAL INSTALLATIONS IN PATIENT AREAS - ALTERATIONS AND ADDITIONS

  • 6.2.2 Compliance: Verify if not existing CPA or BPA, then full <br>compliance with this Standard required.

  • 6.2.5 Compliance: Verify EP wiring system.

  • 6.2.3 Compliance: Verify inspection within last 12 months.

  • 6.2.4 Compliance: Verify % increase in socket-outlets. If 10% or <br>more increase, then all in patient area to comply with colour <br>requirements.

REPAIRS

  • 6.3 Compliance: Verify by inspection.

MAGNETIC FIELDS

  • 7.2 Compliance: Test in nominated areas.

  • 7.3 Compliance: Verify readings below levels nominated in <br>Standard.

MARKING OF PATIENT AREAS

  • 8.1, 8.2, <br>8.3 <br>Compliance: Verify that sign is correct size, affixed in correct <br>location, correctly completed, dated and signed and the <br>tester clearly identified.

  • End of Audit.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.