Title Page
-
Development Application Number
-
Property Address:
-
Conducted by:
- Alan Stanger
- Chris Ansoul
- Mark Robertson
- Peter Griffith
- Shane Powning
- Shane Sissan
- Wes Bailey
-
Conducted on
WHS Considerations
-
Have you identified any major hazards/no-go areas onsite?
-
Is PPE required before entry?
-
Do you have the correct PPE?
-
Is it safe to proceed onto the site?
Consideration
Drainage
Stormwater
-
Does the Land appear prone to local flooding
-
Are any surface/ subsoil water problems evident
-
Is surface water likely to be diverted to the detriment of adjoining land
-
Can Roof Water drain to the street/reticulated system
-
Stormwater will need to drain to
- Underground
- Interallotment
- Kerb
- Existing system
- Ground (Rural/large acreage)
- Other
-
Describe
-
Can surface water be drained to street/interallotment system
-
Is the existing drainage system adequate for the proposal
-
Is an Onsite Stormwater Detention system (OSD) required
Sewage
-
Will existing sanitary plumbing & drainage be affected
-
Is the existing overflow (relief) gully compliant
-
Will the existing overflow (relief) gully be affected
-
Will the proposal encroach into the influence of an utility main or easement
Effluent Disposal Field
-
Does the Development require an Effluent Disposal Field
-
Is sufficient area available for the initial and reserve disposal fields
-
Does site appear to have limiting disposal criteria present
-
Could the disposal field’s textural classification be determined on inspection
-
Specify
-
Could the appropriate effluent disposal method be determined on inspection
-
Specify
Site Stability
-
Does land appear to have been filled
-
Does land require filling to facilitate the development
-
Does the development necessitate the site being excavated/cut
-
Are retaining walls required to stabilise excavated/cut areas
-
Will the footings be below the influence of any adjoining building
-
Are adjoining building(s) likely to require underpinning
-
Is adjoining footpath/road/public land likely to be undermined
-
Will the structure encroach into the influence of any utility service pipe
-
Will soil erosion control measures be required on site
-
Will slab fill be contained within the allotment
Built Environment
-
Any existing buildings to be demolished
-
Is natural light/ventilation to existing buildings likely to be obstructed
-
Will weep-holes, freeboard of existing dwelling likely to be affected
-
Will any doors/gates open out over public footpath/roadway (Roads Act)
-
Any existing fences on side boundaries
-
Any existing fences forward of the building line
-
Is a swimming pool involved with the development (either existing or proposed)
-
Does existing perimeter fencing comply with Swimming Pools Act
-
Any existing openings from dwelling/outbuildings to be made ‘Child Safe’
Acess
-
Can vehicular access be gained to the site
-
Is a vehicular crossing required
-
Can access be obtained from a Public road
-
Is the ‘Public Road’ maintained
-
Does the existing vehicular access require upgrading
-
Is the existing vehicular crossing on correct side for access
-
Is there adequate line-of-sight at the point of access onto the Public road
-
Any existing damage to kerb and gutter, and footpath
-
Have photos of existing kerb & gutter condition been taken & filed
Utlilities
Electricity
-
Is reticulated electricity available
-
Any overhead power lines in close vicinity that could impact on the building
-
Will the proposed building be too close to the lines<br>
-
Notification to Essential Energy required within 7 days
-
Will the Development: -
-
(a) involve the penetration of the ground within 2m of a power pole or underground electricity power line (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
-
(b) be within or immediately adjacent to an electricity easement (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
-
(c) be immediately adjacent to an electricity substation (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
-
(d) be within 5m of an exposed overhead power line (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
-
(e) if a swimming pool, within 5m vertically of an overhead power line (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
-
(f) if a swimming pool, within 30m horizontally of an overhead electricity transmission line support structure (clause 45 of SEPP (Infrastructure) 2007)
-
Notification to Essential Energy required within 7 days
Water
-
Is Council’s potable reticulated water supply available
-
Is the position of the meter standpipe compatible with vehicular access etc
-
Will access be available/maintained for Council’s meter reader
-
Is the position of the water main consistent with its location on GIS
-
Is the building required to be served by fire hydrants
-
Are Street Hydrants available to serve the building(s)
Sewerage
-
Is a reticulated sewerage system available
-
Is the position of the sewer main consistent with its location on GIS
-
Will access be available & maintained to the lot’s sewer junction
-
Is the sewer junction serving only a single allotment
Stormwater
-
Is a reticulated underground stormwater system evident on lot/in the street
-
Will stormwater pipe outlets have to be cut into the street kerb
-
Is a major overland flow path running through or next to the allotment
-
Is adequate freeboard provided (ie 300mm above Ground Level)
Other
Rail
-
Will the Development:-
-
(a) involve a new level crossing, conversion into a public road or a private road access across a level crossing or a likely significant increase in the number of vehicles using a level crossing in vicinity of site (clauses 84-87 of SEPP (Infrastructure) 2007)
-
Notification to RailCorp/ARTC required within 7 days
-
(b) is likely to have an adverse effect on rail safety (clauses 84-87 of SEPP (Infrastructure) 2007)
-
Notification to RailCorp/ARTC required within 7 days
-
(c) involve the use of a crane in air space above the rail corridor (clauses 84-87 of SEPP (Infrastructure) 2007)
-
Notification to RailCorp/ARTC required within 7 days
-
(e) be likely to be adversely affected by rail noise or vibration (clauses 84-87 of SEPP (Infrastructure) 2007)
-
Notification to RailCorp/ARTC required within 7 days
-
(d) involve the penetration of the ground at least 2m below existing Ground Level: (clauses 84-87 of SEPP (Infrastructure) 2007)<br> i) within or above a rail corridor; or<br> ii) within 25m (measured horizontally) of a rail corridor; or<br> iii) within 25m (measured horizontally) of the ground directly above an underground rail corridor
-
Notification to RailCorp/ARTC required within 7 days
-
If residential development, does it adjoin a railway corridor (ie railway line)
Road
-
Will the Development:-
-
(a) be likely to be adversely affected by road noise or vibration (clauses 100-102 of SEPP (Infrastructure) 2007)
-
(b) be undertaken on land reserved for classified road purposes: (clauses 100-102 of SEPP (Infrastructure) 2007)<br> i) with a value greater than $150,000; or<br> ii) for the purpose of dwellings or other building to be held under strata title
-
Notification to RMS required within 7 days
Amenity
-
Will the adjoining land be adversely affected by overshadowing
-
Is the development likely to adversely affect privacy of adjoining land
-
Is the development likely to adversely obstruct access to light
-
Is the development likely to adversely obstruct access to scenic views
-
Should adjoining owners be notified
-
Is a House No./Rural Property No. required to be erected and displayed
-
Do the submitted plans adequately and accurately depict the condition of the existing building the subject of the inspection
-
Have photos of the site been taken and placed on file
Development
-
Has the building work the subject of this application already commenced
-
List works already commenced
Existing Fire Saftey Measures
-
Existing Fire Safety Measures Present?
-
Smoke Alarms (battery only)
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Smoke Alarms (240v)
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Smoke Detectors
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Fire Hose Reels
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Pillar Hydrants
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Fire Hose Reel Pump
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Sprinklers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
External Wall-wetting Sprinklers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
CO2 Extinguishers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
DCP Extinguishers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Foam Extinguishers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Stored Water Extinguishers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Wet Chemical Extinguishers
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Fire Blankets
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Exit Signs (illuminated)
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Emergency Lighting
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Required Exit Door(s)
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
-
Fire Doors
-
Internal
-
External
-
Tag Date/Number:
-
Number present
-
Comments
-
Photos
Signature
-
Inspecting Officer
- Alan Stanger
- Chris Ansoul
- Mark Robertson
- Peter Griffith
- Shane Powning
- Shane Sissan
- Wes Bailey
-
Senior Building Development Officer
Accreditation Number: BPB 1234 (A1 accreditation) -
Senior Building Development Officer
Accreditation Number: BPB 1664 (A1 accreditation) -
Building Development Officer
Accreditation Number: BPB 0970 (A2 accreditation) -
Building Services Supervisor
Accreditation Number: BPB 1236 (A1 accreditation) -
Building Development Officer
Accreditation Number: BPB 1339 (A1 accreditation) -
Building Development Officer
Accreditation Number: BPB 1739 (A3 accreditation) -
Senior Building Development Officer
Accreditation Number: BPB 1496 (A1 accreditation) -
Signature of Officer
-
Select date