Title Page
-
Document No:
-
Board ID and General location (e.g. DBWH3-6, Warehouse):
-
Client / Site:
-
Conducted on:
-
Prepared by:
-
Does the enclosure have a 3 phase main incomer (or multiple 3 phase incomers)? Only boards with 3 phases will be assessed.
-
Take Photos of Escutcheon, photo should provide a general overview of the arrangement of incomer and sub circuits:
Incoming Cable Details:
-
Where is the DB fed from - not including secondary (generator) supplies? (Include DB-enclosure#/TXF#/Generator unique ID)
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
-
How long is the cable route? (Easiest method is to pace out distance looking for any obvious cable penetrations or pits along the route, allow additional meters for any rises or falls of cable.)
-
Any other notes?
-
Is the enclosure supplied from two sources - as in, are there two incoming feeder connections at this particular DB enclosure?
-
Record the generator or other alternative supply details. (Details to include kVA/kW ratings, rated current, make and model, unique identifier)
Secondary Supply Incoming Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
-
How long is the cable route? (Easiest method is to pace out distance looking for any obvious cable penetrations or pits along the route, allow additional meters for any rises or falls of cable.)
-
Any other notes?
Are there any downstream DB Enclosures fed from this location that require assessment?
-
Does the DB Enclosure have any outgoing 3 phase feeders to DB's or enclosures? (3ph supplies to motors, A/C units, UPS’s, and outlets are ignored for the purposes of this assessment)
Main Isolator / Incoming Circuit Breakers.
-
Make / Model of breaker/isolator (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
Is there a DB Enclosure secondary incomer?
-
Is the enclosure supplied from two sources - as in, are there two incoming feeder connections at this particular DB enclosure?
Secondary Supply Isolator / Incoming Circuit Breaker Details:
-
Make / Model of breaker/isolator (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
Outgoing 3 phase Feeder Details:
Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#6 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#6 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#6 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#6 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#7 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#7 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#6 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#6 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#7 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#7 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#8 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#8 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#6 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#6 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#7 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#7 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#8 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#8 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#9 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#9 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#1 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#1 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#2 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#2 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#3 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#3 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#4 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#4 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#5 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#5 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#6 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#6 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#7 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#7 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#8 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#8 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#9 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#9 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
#10 Outgoing feeder Circuit Breaker Details:
-
Make / Model of breaker (e.g. Terasaki Tembreak 2 - XS630NE)
-
What's the "In" rating of the breaker? Usually detailed on the breaker or trip unit e.g. "In = 250A"
-
Photo(s) required with escutcheon closed, labels visible in relation to circuit breaker protusion
-
Photo(s) required with escutcheon open, breaker model and trip unit visible clearly
-
Photo(s) required with escutcheon open, trip unit settings clearly visible
-
Photo(s) required with escutcheon open, Earth Leakage unit and settings clearly visible (only if applicable to this device)
#10 Outgoing feeder Cable Details:
-
How Is the cable installed along its route? (Buried in conduit, in cable ladder or tray, in ceiling space, direct buried etc)
-
How many other cables share this route. (Only write down what can be easily observed, otherwise declare any assumptions)
-
What is the cable type and is it parallel? (I.E. 2x 75sqmm, PVC/SWA/PVC). If unsure of size declare so.
-
End of assessment, ensure all questions have been responded to where possible.
-
Sign name once completed all sections.