Title Page
-
Site conducted
-
Conducted on
-
Assessor
PPM Inspection
-
Visual inspection should be carried out in a manor where no physical contact is made with any part of equipment, this remains when asset is in serviceable condition or under a CAT failure. Definitions of Categories:- CAT 1- Danger present, risk of injury, immediate remedial action required. CAT 2- Potentially dangerous- urgent remedial action required. CAT 3 - Improvement needed. RECOMENDATION - Asset need improvement but no urgent danger. SERVICABLE - Asset in good condition if Maintenace is continued.
ADD ASSET
-
ASSET TYPE:
- Isolator
- RCD
- Socket
- Motor
- Substation/ switchroom
- LV cable
- HV cable
- E/STOP
- Pull wire
- DB/MCCB
- Metal detector
- Lighting
- Control panels
- Generating plant
- Other
-
Photo of lighting area for REFERANCE:
-
Area of lighting:
-
Lighting ID (circuit number):
-
Internal or external lighting:
-
Number of fixtures:
-
Type of lighting: (LED, etc)
-
Lighting is to be inspected to check that they are in working order, watertight and secure. Condition of lighting junction boxes are to be taken into consideration where applicable. All lighting is to be suitable and adequate for relevant areas
All Operational - Check operation of lighting. Record any defects - Adequate for area- All lighting is to be suitable and adequate for relevant areas. - Watertight - External lighting is to be checked for watertightness / cleanliness - Junction Boxes - Ensure no visible damage to local junction boxes - Secure - Ensure lighting is secure in position and all safety covers are in place -
Fitted with Photocell / motion sensor?
-
Photocell / motion sensor condition?
-
cover photocell with dark cloth to check operation of lights.
-
Operation of Photocell / motion sensor
-
Due to poor condition of Photocell/motion sensor, contact cannot be made to check operation of Appliance. remedial work is needed before full visual test can continue
-
Due to poor condition of Photocell/motion sensor, contact cannot be made to check operation of Appliance. remedial work is needed before full visual test can continue
-
Due to poor condition of Photocell/motion sensor, contact cannot be made to check operation of Appliance. remedial work is needed before full visual test can continue
-
ONLY IF SAFE TO DO SO, cover photocell with dark cloth to check operation of lights.
-
Operation of Photocell / motion sensor
-
Check condition of switch
-
Check operation of lights.
-
Check light and fitting suitable for environment
-
Check light fittings for security/ mounting.
-
Check glanding correct fitting and correct for environment
-
Check cable for abrasions or damage
-
Check cable and cable tray for security and clippings
-
Check all junction boxes for visible damage and suitable for environment
-
PHOTO of isolator for REFERANCE:
-
Isolator ID:
-
Operation of isolator:
-
Isolators are to be inspected for watertightness and cleanliness. Condition of isolator enclosure is to be taken into consideration. All isolation points are to be marked clearly and in a durable manner. - - General condition - Inspect the overall condition of the isolator, including damage and wear - Watertight -External isolators are to be checked for watertightness of enclosures - Identifiable - Ensure isolator is clearly marked in a durable manner and easily identifiable
-
Check Isolator security:
-
Check Isolator can be lock in off position:
-
Check Isolator can NOT be lock in ON position:
-
Check Isolator condition: (fit for environment)
-
Check Isolator watertightness:
-
Check gland entry's:
-
Check gland type connection: (fit for environment)
-
Check identifiable labels:
-
Check cable for abrasions:
-
Check cable clipping:
-
Check cable tray condition and fixings:
-
PHOTO for RCD/RCBO for REFERANCE
-
Location of RCD/RCBO
-
RCD/RCBO circuit ID
-
RCB/RCBO rating (mA)
-
RCD/RCBO type
-
RCD/RCBO CURRENT RATING
-
RCD/RCBO test button fitted
-
Check RCD/RCBO is clearly marked in durable manor
-
Check RCD/RCBO condition
-
Check DB/RCD/RCBO to be clean and no ingress of material/water
-
Is quarterly check label in place
-
PHOTO of socket for REFERENCE:
-
Socket ID:
-
Socket voltage:
-
Check socket for security
-
Check for damage to socket
-
Check (visual) entry into socket
-
Is socket internal or external
-
Check gland entry's:
-
Check socket for suitability to environment
-
Check Isolator can be lock in off position:
-
Check Isolator can NOT be lock in ON position:
-
Check Gland and suitability to environment
-
Check cable for abrasion
-
Check cable clipping
-
Check cable tray.
-
PHOTO of motor for REFERENCE
-
PHOTO of motor plate for REFERENCE
-
Motor ID:
-
visual checks on motors Definitions: General condition:- general state of motor, including earth bonding and safe operation. - Guarding:- Ensure all guards/ cowlings are secure and in good condition - Noise:- NO excessive noise - Vibration:- NO excessive vibration - Terminal box:- Ensure terminal box is secure, free from damage and watertight
-
Check General condition of motor
-
Check Guarding condition
-
Check for noise
-
Check for vibration
-
Check terminal box
-
Check gland and suitable for environment
-
Check cable for abrasion
- CAT 1
- CAT 2
- CAT 3
- RECOMENDATION
- SERVICABLE
-
Check cable clipping
-
Check cable tray and fixings
-
PHOTO of DB/MCCB for REFERENCE
-
DB/MCCB ID number
-
Items feed by DB/MCCB
-
Definitions: Identifiable:- ensure distribution boards are clearly marked in a durable manner and easily identifiable - Condition:- inspect the overall condition, including damage, wear and corrosion. -
-
Condition of DB/MCCB
-
Is lock of kit and arc flash kit available
-
DB/MCCB suitable for environment
-
DB/MCCB watertight/ material resistant
-
DB/MCCB has correct identifiable markings
-
DB/MCCB lockable and in working order
-
DB/MCCB in a clean condition
-
IS DB/MCCB have adequate lighting in area
-
Are blanks fitted
-
Are all MCCB/MCB all the same manufacturer
-
PHOTO of substation/ switchroom for REFERENCE
-
location of substation/ switchroom
-
Photo of relevant warning signs
-
Definition:- Identifiable :- ensure substation is clearly marked in a durable manor and easily identifiable. - Room temperature :- ensure room temperature is adequate to prevent damp or overheating of equipment - Lockable :- ensure the substation/ switchroom is lockable to prevent unauthorized access - Cleanliness :- ensure substation is clean and that walk ways/ exits are clear - Lighting :- Check operation of lights and lighting is adequate
-
Is switch room identifiable
-
Is lock of kit and arc flash kit available
-
Is room temperature adequate
-
Is substation/ switchroom lockable and lock in good condition
-
Is substation/ switchroom clean
-
Is electrical safety matt in place
-
Is electric shock poster, electricity at work act and arc flash assessment
-
Is lighting adequate
-
Fitted with emergency lighting
-
PHOTO of LV cable for REFERENCE
-
Location of LV cable
-
LV cable feed/ circuit ID
-
Definition :- Condition :- ensure cable condition if free from wear and damage - Abrasions :- ensure cable is free from heavy scuff, nicks, cuts to cable protection -
-
LV cable condition and free from abrasions
-
Cable tray and fixings.
-
Cable clipping condition
-
LV cable bonding
-
Cable run (in high risk area, ETC)
-
PHOTO of E/STOP for REFERENCE
-
E/STOP ID
-
E/STOP location
-
Definition :- Adequate for Environment- ensure E/STOP is suitable for the environment that is placed - Watertight - Ensure E/STOP is to be checked for watertightness / cleanliness - Secure - Ensure E/STOP is secure in position and all safety covers are in place
-
Check E/STOP identification
-
Check E/STOP for security
-
Is E/STOP suitable for environment
-
Is E/STOP showing signs of water or material ingress
-
Check condition of E/STOP casing
-
Check condition of E/STOP button
-
Is E/STOP showing discolouration
-
Check condition of glanding
-
Check condition of Cable for abrasion
-
PHOTO of pull wire box for REFERENCE
-
Pull wire ID
-
Pull wire location
-
Pull wire manufacturer
-
Pull wire model number
-
Definition :- Adequate for Environment- ensure PULL WIRE BOX is suitable for the environment that is placed - Watertight - Ensure PULL WIRE BOX is to be checked for watertightness / cleanliness - Secure - Ensure PULL WIRE BOX is secure in position and all safety covers are in place
-
Check pull wire box for security
-
Is pull wire suitable for environment
-
Is pull wire box showing signs of water or material ingress
-
Check condition of pull wire box casing
-
Check condition of glanding
-
Check condition of Cable for abrasion
-
Check condition of cable tray and fixings
-
Check condition of cable clipping
-
Check condition of pull wire (complete length)
-
Is pull wire showing discoloured
-
Check condition of pull wire pig tail and wire mounting
-
Check condition of sprung tensioners and manual tension adjusters
-
PHOTO of generating plant for REFERENCE:
-
Generating plant location
-
Generating plant make
-
Generating plant model
-
Generating plant ID
-
Definition:
Adequate for Environment- ensure all equipment is suitable for the environment that is placed - Watertight - Ensure equipment is to be checked for watertightness / cleanliness - Secure - Ensure equipment is secure in position and all safety covers are in place -
Check identifying marking are in place and durable
-
Visual inspection of generating plant casing
-
Check condition of guarding
-
Check overall generating plant cleanliness
-
Check all inspection hatches and closed and lock in good operating condition
-
Check (visually) earthing arrangement
-
Check control panel for damaged switches, lights and instruments.
-
Check security of switches, lights and instruments
-
Check overall condition of generator E/STOP
-
Check Condition of RCD/RCBO’s
-
Check condition of MCB’S/MCCB’S
-
Visually check for water material ingress in MCB’S/MCCB’S
-
Check outgoing sockets for damage
-
Check outgoing cables for abrasion or damage
-
Check cable clipping
-
Check cable tray and fixings
-
PHOTO of control panel for REFERENCE
-
Control panel ID number
-
Control panel feed from
-
Items feed by control panel
-
Definition:-
Identifiable :- ensure substation is clearly marked in a durable manor and easily identifiable.
-
Lockable :- Control panel is lockable to prevent unauthorized access
-
Cleanliness :- ensure substation is clean and that walk ways/ exits are clear
-
Lighting :- Check operation of lights and lighting is adequate -
Check control panel is suitable for environment
-
Check for signs that control panel watertight/ material resistant
-
Check control panel has correct identifiable markings
-
Check control panel lockable and in working order
-
Check control panel is in a clean condition
-
Check (visually) earthing arrangement
-
Check control panel for damaged switches, lights and instruments.
-
Check security of switches, lights and instruments
-
Check overall condition of control panel E/STOP
-
Is panel fitted with isolator
-
Check Isolator condition:
-
Check isolator identifiable labels:
-
Is panel fitted with interlocking key/castel / fortress key
-
Check Key mount is secure
-
Check key fitment is correct
-
Check Key for damage that will prevent use in future
-
Check incoming cables for abrasion
-
Check incoming cable clipping
-
Check incoming cable tray and fixings
-
Check outgoing cables for abrasion
-
Check outgoing cable clipping
-
Check outgoing cable tray and fixings
-
Check control panel has adequate lighting in area
-
PHOTO of metal detector for REFERENCE
-
Metal detector ID
-
Metal detector location
-
Metal detector manufacturer
-
Metal detector model number
-
Definition: -
Adequate for Environment- ensure all equipment is suitable for the environment that is placed - Watertight - Ensure equipment is to be checked for watertightness / cleanliness - Secure - Ensure equipment is secure in position and all safety covers are in place -
Check mounting of metal detector
-
Check metal detector is suitable for environment
-
Check condition of metal detector
-
Check condition of metal sensor wiring
-
Check condition of Glanding
-
Check condition of Cable for abrasion
-
Check condition of cable clipping
-
Check condition of cable tray and fixings
-
OTHER option only to be used when appliance doesn't match other asset heading.
-
Appliance name
-
Appliance make
-
Appliance model
-
Appliance ID
-
Definition:-
Identifiable :- ensure Appliance is clearly marked in a durable manor and easily identifiable.
-
Lockable :- Appliance is lockable to prevent unauthorized access
-
Cleanliness :- ensure Appliance is clean from material
-
Lighting :- Check operation of lights and lighting is adequate - Adequate for Environment- ensure Appliance is suitable for the environment that is placed - Watertight - Ensure Appliance is to be checked for watertightness / cleanliness -
Check appliance marking is identifiable
- CAT 1
- CAT 2
- CAT 3
- RECOMENDATION
- SERVICABLE
-
Check that appliance if fitted and secure
-
Check appliance is suitable for environment
-
Check appliance is showing no signs of water ingress (visual)
-
Check Appliance door and shut and locked correctly (where applicable)
-
Check Appliance glanding is fitted correctly and for environment
-
Check Appliance cable is free from damage and abrasion
-
Check Appliance cable tray and fixings
-
Check Appliance cable clippings
-
Any further issues with appliance (notes and photos)