Title Page
-
Site conducted
-
Prepared by
-
Conducted on
-
Location
CAUSE
-
BLOCK B - GF GERDA Box - Manual Call Point Activation
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Building B Sounders / Beacons (Ground Floor)
-
Building A Sounders / Beacons (Roof)
-
Building B Sounders / Beacons (Roof)
-
Building C Sounders / Beacons (Roof)
-
Car Park Sounders / Beacons<br>
-
FM Hub Room Sounders / Beacons
-
"FIRE" Indication On all Landlord Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Building C District Heating Plant Room BMS Panel
-
Gas Solenoid Valve Shuts Off
-
Building B Ground Floor Extract Fans Shut Off
EFFECT ON DOORS
Doors
-
Building B Door B.SY.01 Access Control Locks Released<br>
-
Building B Door B.SC.00 Access Control Locks Released<br>
-
Building B Door B.SC.00.1 Access Control Locks Released
-
Building B Door B.CY.01 Access Control Locks Released<br>
-
Building B Door B.SC.01 Access Control Locks Released
-
Building B Door B.SC.02 Access Control Locks Released
-
Building B Door B.SC.03 Access Control Locks Released
-
Building B Door B.SC.04 Access Control Locks Released
-
Building B Door B.SC.05 Access Control Locks Released
-
Building B Door B.SC.06 Access Control Locks Released
-
Building B Door B.SC.07 Access Control Locks Released<br>
-
Building B Door B.SC.08 Access Control Locks Released
-
Building B Door B.SC.09 Access Control Locks Released
EFFECT ON LIFTS
Lifts
-
Lift B1 Primary Floor
-
Lift B2 Primary Floor
OBSERVATIONS
-
Observations