Title Page
-
Site conducted
-
Prepared by
-
Conducted on
-
Location
CAUSE
-
1st Floor Far Side (East) - Optical Detector Activation
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Building D Sounders / Beacons (Ground, 1st Floor & Roof)
-
FM Hub Room Sounders / Beacons
-
"FIRE" Indication On all Landlord Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Building D Ground Floor Extract Fans Shut Off
EFFECT ON DOORS
Doors
-
Building D Door D.ME.01 Access Control Locks Released
-
Building D Door D.ME.02 Access Control Locks Released
-
Building D Door D.MG.04 Access Control Locks Released
-
Building D Door D.SY.01 Access Control Locks Released
-
Building D Door D.PD.01 Access Control Locks Released
-
Building A Door A.PD.01 Access Control Locks Released
-
Building B Door B.PD.01 Access Control Locks Released
-
Building C Door C.PD.01 Access Control Locks Released
-
Building E Door E.PD.01 Access Control Locks Released
-
Building F Door F.PD.01 Access Control Locks Released
EFFECT ON MSFD
-
Building D 1st Floor MSFD Closes
EFFECT ON AOV
AOV
-
Building D 1st Floor Far Side Smoke Extract Vent Opens
-
Building D Head of Stair Extract Vent Opens
EFFECT ON LIFTS
Lifts
-
Lift D1 Primary Floor<br>
-
Lift D2 Primary Floor<br>
-
Lift D3 Primary Floor
OBSERVATIONS
-
Observations