CAUSE
-
BLOCK E - Terrace- Manual Call Point Activation (8th Floor MCP)
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Building E Sounders / Beacons (Ground Floor & Roof)
-
FM Hub Room Sounders / Beacons
-
"FIRE" Indication On all Landlord Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Building E Ground Floor Extract Fans Shut Off
EFFECT ON DOORS
Doors
-
Building E Door E.ME.01 Access Control Locks Released
-
Building A Door A.PD.01 Access Control Locks Released
-
Building B Door B.PD.01 Access Control Locks Released
-
Building C Door C.PD.01 Access Control Locks Released
-
Building E Door E.PD.01 Access Control Locks Released
-
Building F Door F.PD.01 Access Control Locks Released
EFFECT ON MSFD
Damper Control Panel (D Locker Room)
-
Ref 8 Block E Cleaner Store - Closes
EFFECT ON LIFTS
Lifts
-
Lift E1 Primary Floor<br>
-
Lift E2 Primary Floor<br>
OBSERVATIONS
-
Observations