Information

  • Fire Cert Inspection -

  • Conducted on

  • Prepared by

  • Location
  • Personnel Involved

AIR CONDITIONING SYSTEM - CED FC ACS

  • Name of Building:

1a. AHU

  • Smoke cut-off system provided within return air stream of AHU

  • Activation of smoke-cut-off system shuts down AHU

  • Manual reset provision for AHU

  • No storage in AHU room

  • Smoke detector provided and tested in order

1b. FIRE DAMPERS

  • Fire Dampers are properly installed

  • Motorised Fire dampers operate upon activation of auto fire alarm detectors

  • No obstruction to dampers louver (blades) movement

  • Access door for inspection of Fire dampers provided

  • Fire dampers of approved rating and with PSB label

Inspection details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

ATRIUM SMOKE CONTROL SYSTEM - CED FC ASCS

  • Name of Building:

  • Smoke detectors provided at the perimeter of the Atrium

  • Separate manual reset switch provided

  • Functions under Secondary supply provided

  • Auto supply mode activated by fire alarm system (where applicable) under Secondary power supply

  • Manual activation provision installed

  • System extraction air fan operate upon activation of fire alarm

  • Smoke curtains operate upon activation of fire alarm

  • Ventilation louvers operation by fire alarm and under secondary power supply are in order

  • All fire scenarios where is / are designed under the engineered smoke control system has / have been tested

  • Air-condition cut-off upon activation of fire alarm

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

AUTOMATIC FIRE ALARM SYSTEM - CED FC AFAS

  • Name of building:

  • Name of monitoring company:

  • Building code no:

Heat/ Smoke Detector Test

  • Sufficient coverage

  • Detector points not painted

  • Detector points unobstructed

  • System connected to monitoring company / 995

  • Alarm signal transmission received by monitoring company

  • Zone tested is indicated correctly on main-alarm panel

  • Audible fault alarm & fault indication light provide at main-alarm panel

  • Zoning diagram provided next to the main-alarm panel

  • Zone tested is indicated correctly on sub-alarm panel

  • Audible fault alarm & fault indication light provide at sub-alarm panel

  • Zoning diagram / mimic panel provided next to the sub-alarm panel

  • Alarm bells in operational condition

  • Alarm general sounding throughout the building

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

AUTOMATIC FIRE SUPPRESSION SYSTEM FOR COOKING HOOD - CED FC AFSS

  • Name of building:

1. General

2. Cylinder for Extinguishing Agent

3. Nozzle and Pipe Works

4. Heat Activating Device

DRY RISER SYSTEM - CED FC DRS

  • Name of building:

  • Dry Riser Type?

1. Breeching Inlet

  • Inlet housed in glass fronted protective enclosure

  • Properly installed / secured

  • Clear of Obstruction

  • About 0.76m above finished floor level

  • Labelled “DRY RISER INLET” and differentiated

  • Inlet painted in yellow colour

2. Riser

  • Not passing through unprotected area / Fire rated

  • Air release valve provided

  • Earthing provided

3. Landing Valve

  • 0.76m to 1m above finished floor level

  • Condition of hand wheel satisfactory

  • Blank Cap provided

  • Strapped and padlocked in closed position

  • Labelled / Numbered

  • Clear of Obstruction

  • Landing valve painted in yellow colour

4. Testing of Hydrostatic Pressure

  • Pressure constant at 200 PSI for 2 hrs

  • Air release valve functioning

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

ENGINEERED SMOKE CONTROL SYSTEM - CED FC ESCS

  • Name of building:

  • Separate manual reset switch provided

  • Functions under secondary supply provided

  • Auto supply mode activated by fire alarm system under normal power supply

  • Auto supply mode activated by fire alarm system under secondary power supply

  • Manual activation provision installed

  • Air exhaust fan operate upon operation of fire alarm

  • Air condition system cut-off upon activation of system

  • Smoke curtain operate upon activation of system

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

HOSE REEL SYSTEM (WITH PUMP) - CED FC HRS

  • Name of building:

1. Hose

2. Testing

  • No Leakage detected

  • 6m throw achievable or flow rate of 0.4 litre / sec

3. Pump

  • Pump can be manually tested

  • Auto changeover from normal to secondary power supply

  • Auto changeover from duty to standby pump operation in order

  • Differentiated

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

LIFT - CED FC LIFT

  • Name of building:

  • No of Passenger Lift:

  • No of Cargo Lift:

  • No of Fire Lift:

1. Passenger and Fire Lift

  • Lift homing under fire alarm activation in order (Clause 13.1.3)

  • Lift homing under secondary power supply (Clause 13.1.2)

  • Warning notice for fire situation provided (Clause 13.1.8)

  • PSB (SISIR) approved EBOPS provided (Clause 12.3)

  • EBOPS supply to lift car bell, lighting and fan in order

  • Lift differentiated with numbers

  • Storey Numbering for lift lobbies provided

  • Lifts home at designated floor

2. Fire Lift (Size and Capacity)

  • State capacity:

  • Lift travel from ground to top level within 1 minute

  • Fire lift operated under fire switch in order

  • Labelled “FIRE LIFT”

  • Fire switch properly enclosed in labelled glass fronted cover

  • No combustible furnishing

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

OTHER SYSTEMS AND FIXTURES - CED FC OSF

1a. Hosereels (w/o Pump)

  • Is the nozzle condition satisfactory?

  • Non kinking reinforced rubber?

  • Length of hose 30m?

  • No locking device provided?

  • Condition of stop cock satisfactory?

  • Clear of obstruction?

  • Labelling provided for cabinet?

  • Labelling provided for instructional signage?

1b. Hosreel (w/o Pump) - Testing

  • No leakage detected?

  • 6m throw achievable with 0.4L/sec?

2. Portable Fire Extinguisher

  • Properly hung on bracket

  • Clear of obstruction

  • Service by licensed contractor

  • PSB label

  • Date of service

3. Manual Call System (Call Point)

  • The colour for all fire alarm panels, bell ,conduit <br>and trunking are painted red<br>

  • Clear of obstruction

  • Fire alarm zoning diagrams provided near fire <br>alarm panel<br>

  • General sounding throughout the building

  • Located about 1.4m from floor level

  • Alarm bell in operational condition

  • The fire alarm sounding distinguishable from any other alarm system

  • Audible fault alarm & fault indication light <br>provided at sub / main panel<br>

  • Zone tested is indicated correctly on the fire<br>alarm main / sub panel<br>

  • “IN CASE OF FIRE CALL 995” signage provided

4a. Exit signs

  • Exit signs adequately provided along: 1. Staircase, 2. Escape Routes, 3. Public Area

  • Exit sign visible?

  • Directional Exit Sign connected to secondary power supply tested in order?

  • Exit sign complied with CP19 colour code (green and white combination)

4b. Emergency Lighting

  • Emergency lighting adequately provided along: 1. Staircase, 2. Escape Routes, 3. Public Area, 4. Essential Plant Rooms

  • Automatic operation tested in order?

  • Emergency lighting provided is sufficient?

  • Identification (CI 7.8 CP 19)

  • Emergency lighting connected to secondary power supply?

5a. Fire Doors

  • Fire door installed at the following location are in order: 1. Staircases, 2. Escape Routes, 3. Public Area

  • Fire doors provided with PSB label?

  • Swing of door in direction of escape?

  • No stopper detected?

  • Is the fire rated door fitted with door closer?

  • Is the fire rated exit door in closed fitting?

  • Clear from obstruction?

  • Panel above the door same rating as the wall?

  • No locking device for doors passing to the firefighting staircase?

  • Viewing glass panel at fire rated door does not exceed 650mm2

5b. Exit Doors

  • Doors unlocked during operating hours?

  • Clear of obstruction?

6. Duct Riser

  • Fire stopped accordingly

  • Protected by fire-resisting enclosure

  • No Storage

7. Staircases

  • Open type -

  • Enclosed type -

  • Clear from any obstruction and combustible material?

  • No combustible furnishing?

  • Fully compartmented?

  • Service pipe (gas, oil and vent) other that water pipes passing through protected staircase, lobby area

8. External Fire Fighting Access Opening

  • Clear of obstruction internal and external?

  • (Red or Orange) external marking provided?

  • Signage "Fire Fighting Access - Do Not Obstruct" provided?

  • Readily open from inside and outside?

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

PRESSURISATION SYSTEM - CED FC PS

  • Name of building:

  • Location of fans:

  • Separate manual reset switch provided

  • Fan operation at high speed under fire alarm (if single)

  • Both fans operating under fire alarm (if double)

  • Fan operating upon secondary power supply (Fire mode)

  • Fan in operation can only be stopped manually

  • Average air velocity not less than 1 m/s

  • Force require to open any door is not more than 110 N

  • Independent system for smoke lobby / protected corridor connected to secondary power supply

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

PRIVATE HYDRANT SYSTEM - CED FC PHS

  • Name of building:

  • Hydrant No:

1. Hydrant

  • Rigidly mounted on ground

  • Cover for spindle chamber visible

  • Spindle depth not more than 1 metre

  • Blank cap provided

  • Spindle chamber and Hydrant clear of obstruction

  • Hydrant painted with yellow colour band

Testing of Static Pressure and Flow Rate

    Hydrant Details
  • Hydrant No:

  • Static Pressure:

  • Flowrate in L/sec

  • Remarks:

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

STANDBY GENERATOR SET - CED FC SGS

  • Name of building:

  • Location of Standby Gen Set:

1. Generator Operation

  • Automatically changeover within 15 sec.

  • Smoke exhaust in-order

  • No storage

2. Generator Set tested on full load - Supply to the following systems simultaneously

a) Emergency Lighting

b) Fire Pump System

c) Lift System

d) Mechanical Vent System

e) Public Addressing System

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

VOICE COMMUNICATION SYSTEM - CED FC VCS

  • Name of Building:

One Way Communication

  • Operational test in order

  • Standby battery provided

  • Secondary power supply provided

  • Over riding switch provided at Fire Command Center (FCC)

Two Way Communication

  • Operation tested in order

  • Standby battery provided

  • Secondary power supply provided

  • Provided at Strategic Location

  • To label & colour in red

  • 1.5m above the floor

  • Operational test is indicated correctly at panel in FCC

Inspection Details

  • Select date

  • Facilities Management Rep

  • WSH Personnel

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.