Fire Door Audit
-
Fire door Checklist
Fire Door
Fire door checklist
-
Has the fire door got a BWF-CERTIFIRE Fire Door Scheme label on the top edge?
-
Can you confirm that the door is a certified fire door?
-
Is signage correct and visible
Door Leaf
-
Does the door leaf sit against the door stop, flush with the frame and is free of distortion?
-
If the door is veneered or lipped,is the glue still holding these products firmly in place?
-
Is the door free from damage including dents chips and holes?
Door frame
-
Is the door frame firmly attached to the wall?
-
If a door stop is present is it firmly attached?
-
Is the frame to door leaf gap consistently 3mm
Intumescent/smoke/acoustic Seals
-
Are the intumescent seals in place?
-
Are Seals free from paint or varnish?
-
Are the seals well attached inside the groove in the frame or door leaf?
-
Are the seals free from damage?
-
If you have a brush or fin type seal, is it free from damage or breakage?
-
If fitted, are the smoke and acoustic seals continuous around the frame or door leaf?
Hinges
-
What type of hinge is fitted to the door?
-
Is there a minimum of 3 hinges with all the screws fitted?
-
Are all of the screws the correct size?
-
Are the hinges free of metal fragments and oil leakage, which are signs of wear?
-
Are the hinges marked with stamp or BSEN 1935 grade 11?
-
Are the hinges free from packing?
-
Is intumescent pads present.
-
Are the pivot hinges aligned and in good working order?
-
Are the pivot hinges free from debris and metal fragments?
-
Are there and signs of wear or oil leakage?
-
Are the hinges securely fitted?
Door Closers
-
Open the door to 5 degrees or 75mm. Does it close and engage with the latch?
-
Is the closer correctly attached to the door and frame?
-
Is the closer free from damage and not leaking?
-
If unmatched, does the closer hold the door in line with the frame and instrument seal?
-
If hung in pairs, do they close in line if both opened and released together?
-
Is a "Maglock" type device installed?
-
Does it dis-engage during the fire alarm test
-
Is it secure and locked in place?
-
Does manual release operate when activated with key?
Hold Open Devices- only electronically powered allowed
-
Does the hold open device release the door when required?
Lock and Latch
-
Does the latch hold the door firmly in place without rattling?
Threshold gap
-
Is there a consistent gap under the door that allows it to swing without touching floor covering?
-
Is the door to floor covering gap consistently 5mm or less when the door is closed for smoke control doors in stairwells?
-
Is the door to floor covering gap consistently 10mm or less when the door is closed?
Glazing and Glassware
-
Is the intumescent seal continuous and attached to the glass and the bead?
-
Are the glazing beads well attached to the frame and free from damage?
-
Is the glass free from damage and cracking?
-
Is the glass clear?
-
If the glass has been replaced, is it fire rated glass?
-
If glazing panels are below 1500mm from bottom of door, is the glass safety glass?