Information
-
Mercy Hospital CMS PoC Life Safety
-
Conducted on
-
Prepared by
FIRE RATING AND MODEL
-
Model
-
Rating
- 1.5 hour
- 3 hour
-
Size
-
Tag#
REVIEW WALL DAMPER INSTALLED IN
-
Wall Fire Rating
- 1 HR
- 2 HR
- 3 HR
- 4 HR
-
Wall Construction
REVIEW DAMPER PRIOR TO INSTALLATION
-
Is Damper Tag # Correct
-
UL Sticker Applied and Correct Rating
-
Electrical Devices Installed and Sealed
REVIEW DAMPER INSTALLATION
-
Damper Blades are Running Horizontally and Installed within Wall/Floor
-
Damper Opening has Proper Clearance for Expansion
-
Mounting Angles Must Overlap the Partition Minimum of 1"
-
Fasteners for Two Angle Installation are Spaced at 8" O.C.
-
Break-away Connections are Installed per the SMACNA standards
-
Round Duct Installed within Screw Limits
-
Duct Sealed Properly with No Leakage
-
Damper has been Installed Square and Free from Racking
REVIEW ELECTRICAL DEVICES INSTALLATION
-
Fire Smoke Damper Interface (FSDI) Installed
-
Actuator is Installed and Wired to FSDI
-
SP-100 Switch Package is Installed and Wired to FSDI
-
Disconnect Switch has been Installed