Information

  • Mercy Hospital CMS PoC Life Safety

  • Conducted on

  • Prepared by

FIRE RATING AND MODEL

  • Model

  • Rating

  • Size

  • Tag#

REVIEW WALL DAMPER INSTALLED IN

  • Wall Fire Rating

  • Wall Construction

REVIEW DAMPER PRIOR TO INSTALLATION

  • Is Damper Tag # Correct

  • UL Sticker Applied and Correct Rating

  • Electrical Devices Installed and Sealed

REVIEW DAMPER INSTALLATION

  • Damper Blades are Running Horizontally and Installed within Wall/Floor

  • Damper Opening has Proper Clearance for Expansion

  • Mounting Angles Must Overlap the Partition Minimum of 1"

  • Fasteners for Two Angle Installation are Spaced at 8" O.C.

  • Break-away Connections are Installed per the SMACNA standards

  • Round Duct Installed within Screw Limits

  • Duct Sealed Properly with No Leakage

  • Damper has been Installed Square and Free from Racking

REVIEW ELECTRICAL DEVICES INSTALLATION

  • Fire Smoke Damper Interface (FSDI) Installed

  • Actuator is Installed and Wired to FSDI

  • SP-100 Switch Package is Installed and Wired to FSDI

  • Disconnect Switch has been Installed

PHOTOS

  • Add media

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.