Title Page
-
Date
-
Completed by
-
Location
-
To view our Loss Prevention Standard that supports this checklist, please view the following link : https://broker.aviva.co.uk/documents/view/aviva_fire_doors_fire__shutters_and_fire_dampers_lps.pdf
Fire Doors, Fire Shutters and Fire Dampers Checklist
-
1. Are there accurate fire compartmentation wall/floor drawings for the site?
-
2. Is the fire compartmentation and use of fire doors consistent with the needs of the site?<br>• Life safety?<br>• Property values?<br>• Business impact/interruption?<br>• Smoke sensitivity?
-
3. Are all fire doors, shutters, dampers, etc. identified on the fire compartmentation documentation?<br>Including within ventilations systems, ducting systems, etc.?
-
4. Are only third party accredited/certified:<br>• Organisations used for any design/installation/maintenance activities, etc. ?<br>• Manufacturers/products used for all equipment, etc.?
-
5. Is each fire door, shutter, damper, etc., frame and all fixtures and fittings rated consistently with the fire resistance rating of the fire compartment wall?<br>• Integrity?<br>• Insulation?<br>• Including glazed elements?
-
6. Are all fire doors, shutters, dampers, etc. listed with:<br>• Own unique identifier?<br>• Fire resistance rating?<br>• Any smoke protection enhancement?<br>• Method of automatic actuation?
-
7. For each fire door, shutter or damper, etc. should enhanced smoke leakage resistance be provided?
-
8. Are fire doors, shutters, dampers, etc. included in regular site self-inspections by a competent person, e.g. daily or weekly housekeeping checks?
-
9. Are more formal and documented fire door inspections completed by a competent person:<br>• Monthly?<br>• Quarterly?<br>Does this include closing doors, rolling shutters down, checking door frames, runners, tracks, etc.?
-
10. Are any doors actuated by fusible element or frangible bulbs?<br>Are the bulbs/fusible elements:<br>• Located close to the roof/ceiling deck on both sides of the compartment wall?<br>• Checked for damage, painting, etc.?
-
11. Can any fusible link or frangible bulb actuation be replaced with faster acting automatic fire detection with devices located on both sides of the fire compartment wall?<br>If the occupancy of the building is sensitive to smoke damage/smoke contamination, then this should be considered a high priority.
-
12. Are formal fire door, shutter and damper audits and maintenance schedules completed annually?<br>Does this include formal trip test, drop test, actuation with the automatic means?
-
13. Is the automatic closing operation of fire doors overridden or delayed for evacuation purposes?
-
Could alternative routes or additional means of escape doors be fitted and this door closure delay removed?
-
14. Is there any damage, deterioration, wear and tear or alterations to any of the doors?
-
15. Are intumescent strips or smoke seals in good condition, not painted and not damaged?
-
16. Can all fire doors and shutters close freely as intended without any obstructions?
-
17. Are any fire doors propped or wedged open at any time?
-
Consider automatic door closures linked to the fire alarm.
-
18. Are any doors that close automatically upon automatic fire alarm actuation verified during routine fire alarm tests?
-
19. Are any doors that can be manually released with a push-button verified on a quarterly basis?
-
20. Are any fire doors prone to damage or wear and tear?
-
Are these appropriately protected?
-
21. Is a clear space/sterile area of at least 2m in all directions maintained on either side of every fire door?<br>• Kept clear of stock, contents and other combustible materials?
-
22. Is there the potential for combustible or flammable liquids to be released and pass under a closed fire door?<br>• Including on the surface of any fire water involved in a fire event?<br>• Is this clearly identified in the fire risk assessment?<br>• Are liquid retention/flow prevention measures in place at the plane of the fire compartment wall/door enclosure to prevent this from happening?
-
23. Are conveyors, production lines passing through a fire compartment wall opening interlocked to shut down/clear of materials before the fire door closes? <br>• So contents on the conveyor do not block fire door operation?<br>• Is the conveyor/production line segmented to enable fire door closure?
-
24. Are all normally open fire doors, shutters and dampers closed when the premises are vacated/at the end of the working day?
Sign Off
-
Additional Comments
-
Completed by (Name and Signature)