  • GENERAL

  • 1 Deep cleaning in all areas

  • 2501 EXTERIOR & Parking

  • 1 Guardrail will be added to the terrace at the fire exit- Staircase to be built. To be confirmed with fire consultant about assembly points

  • 2 All exterior windows to be cleaned before opening

  • 3 Mechanical rooftop terrace must have guardrails. Please confirm with fire consultant

  • 4 Rooftop access door: add a magnetic switch, add a security measure to avoid guest entry.Please confirm with fire consultant All rooftop exits must be equipped with a panic bar or other releasing device, latching hardware and an alarm that is monitored in the security dispatch office or PBX. These doors must have a sign on the inside face indicating the door is alarmed and to be used in emergency situations only, if accessible to the public.

  • 5 Separate trash and smoker’s post receptacles near the guest entrance

  • 6 Planters to be potted

  • 7 Exterior surface parking - painted markings on paved floors must be washable and antiskid

  • 8 Pls. confirm carpark scenario of operation for parking garage. Min. 1 parking area for every 4 guestrooms. (27) Please confirm total available number.Take necessary security and access control measures if there is guest use. Parking control- entry exit barriers are optional.

  • 9 Parking lot striping must be white or yellow, except where other colors are required by local codes for fire lanes, accessible parking, no parking zones, etc

  • 10 Basement levels -3 -4 elevator halls fire zoning to be confirmed with fire consultant

  • 11 Guest hall door needs door handle. To be confirmed with fire consultant

  • 12 Pls. confirm with the operator the staff entrance scenario to determine security needs

  • 13 Garage elevators Must terminate at the lobby level, within view of the front desk. Direct guest access from parking garage level to guestroom floors must be by card key/room key access. Please confirm the scenario with the operator

  • 2502 LOBBY

  • 1 Metal dedector to be installed at entry

  • 2 Floor:2 Inset carpets to be installed

  • 3 Ventilation grills to be in place

  • 4 Min. one outlet for a house telephone in the lobby area

  • 5 Televisions must be mounted where indicated in the prototypical drawings.

  • 6 Artwork and accessories to be placed

  • 7 Workstation equipments to be installed

  • 8 BOH corridor door to be installed

  • 9 Luggage room keycard to be installed

  • 10 Luggage room hanging racks (25%) and storage shelving (weight allowance 159kg) units (75%).

  • 11 Liquor storege and back office ffe not procured

  • 12 Liquor storeage and back office ceiling access panels are missing

  • 2503 PUBLIC RESTROOMS

  • 1 5 doors are missing: Toilet hall, men-women wc, janitor,accessible WC

  • 2 Window treatment to be placed

  • 3 Women wc wall sconces to be installed

  • 4 Accessble wc accessories to be installed

  • 5 Paper towel dispensers to be mounted.

  • 6 Baby changing station at accessible wc

  • 7 Mirror above all vanities: casegood to be finalised

  • 2504 FOOD AND BEVERAGE

  • SHOW KITCHEN

  • 1 All equipment to be installed and finalised, to be ready for test cookings

  • 2 Basin mixers are missing

  • 3 House telephone missing

  • 4 Eyewash station missing

  • FOOD PREP/KITCHEN

  • 1 Chef office ffe not procured

  • 2 Finalize and commision all kitchen equipment ready for test cookings

  • 3 "Telephone:

  • A telephone outlet for a wall mounted house telephone in the kitchen area.

  • A telephone outlet for a minimum two-line telephone with calling number display in-room service.

  • 4 telephone outlets and data ports at all cash register/point of sale terminals requiring credit card verification"

  • 4 Eyewash station missing

  • BAR

  • 1 BOH door to be installed

  • 2 Decorative panels at continuous hanging glassware to be installed

  • 3 Bar footrests and purse hooks. LED to be finished

  • 4 Equipments to be finalised

  • 5 TV to be installed

  • 6 Barstools to be placed

  • DINING SPACE

  • 1 All furniture to be placed

  • 2 Buffet equipment to be finalised

  • 3 Central buffet is missing

  • 4 Ventilation grills to be in place

  • 5 Accent pendant lighting.

  • 2506 COMMERCIAL FACILITIES

  • THE SHOP

  • 1 Shop trolley is missing. Shop to be finalised

  • 2 Refrigerato and equipments to be installed

  • GUEST LAUNDRY

  • 1 Entry door to be installed

  • 2 Keycard to be installed

  • 3 washer and dryer machines to be installed

  • 4 One side chair with upholstered seat is required.

  • 2507 MEETING FACILITIES

  • MEETING ROOMS

  • 1 All meeting room doors are yet to be installed

  • 2 One outlet for a house telephone per subdivision.

  • 3 Touch panels to be installed

  • 4 Decorative panels are to be installed

  • 5 Projection screen - if permanently installed, it must be ceiling recessed.

  • 6 Artwork-

  • PRE-FUNCTION AREA

  • 1 TVs to be placed

  • 2 All loose furniture to be placed

  • 3 Wall claddings to be installed

  • 4 Artwork-accessories

  • MEETING-FITNESS FLOOR RESTROOMS

  • 1 All doors yet to be installed

  • 2 accesible wc accessories to be installed

  • 3 Paper towel dispensers to be mounted.

  • 4 Please correct all the trap-openings in drywall below the basin counters

  • 5 Mirror above all vanities: casegood to be finalised

  • 6 Men wc wallpapers need to be finished

  • 2508 RECREATIONAL FACILITIES- Fitness Center

  • 1 Door to be installed

  • 2 Finish the floor rubber tiles

  • 3 Wall claddings to be installed

  • 4 TV to be installed

  • 5 Towel station is missing

  • 6 Three wall-mounted towel/coat hooks near the towel station.

  • 7 Wall mirrors, installed flush–mount.

  • 8 Water cooler.

  • 9 Key card to be installed

  • 2509 CIRCULATION

  • ELEVATORS/LIFTS

  • 1 Number 2 to be replaced with L sign on operating panels. -3 and -4 floors will not be accessible from guest elevator. Remove numbering

  • 2 Keycards to be installed

  • SERVICE ELEVATORS/LIFTS

  • 1 Number 2 to be replaced with L sign on operating panel. O meeting floor has the green highlight, it is confusing

  • 2 Can kitchen service elevator obtain green label?

  • GUESTROOM CORRIDORS

  • 1 Carpets to be installed

  • 2 Decorative window treatment.- missing at corridors

  • 3 Console table- house telephone to be placed in elevator halls

  • 4 artworks

  • EXIT STAIRS

  • 1 Treads non-skid nosings of contrasting color missing.

  • 2510 GUESTROOM/SUITES

  • 1 Door Closer - all doors to be calibrated as no hold open

  • 2 Accessible guestrooms keycards to be installed

  • 3 Emergency escape sign on guestroom side below door viewer.

  • 4 Safes to be installed

  • 5 Wall - claddings to be installed in some rooms

  • 6 LED lux levels for bedside pendant lamps are not enough. LED to be replaced

  • 7 Mattresses sofa seats to be placed

  • 8 Rugs to be placed

  • 9 TV to be installed and programmed

  • 10 Tea and coffee making facilities to be placed, all collaterals to be placed

  • 11 Brand approved 40L Refrigerator- needs to be fixed in place.

  • 12 Artworks to be installed

  • 13 Blackouts and sheers to be placed

  • 14 Telephones to be installed

  • 15 All collaterals must be in place. All coffee-tea amenities must be in place.

  • 16 Freestanding TV furniture to be installed

  • 2512 GUEST BATHROOM

  • 1 Crabtree bulk amenities to be placed

  • 2 Shelf LEDs to be installed

  • 3 Accessible room bathroom sliding doors to be intalled

  • 4 Accessible room bathroom accessories, shower curtains, mirrors to be installed

  • 5 accessible bathroom shower seat structure was not built- ID to find solution

  • 2513 BACK-OF-HOUSE

  • 1 All BOH corridors to have full height corner guards.Corner guards must be a resilient, throughcolored vinyl to coordinate with the wall color and must be adhesive mount. The flanges must be a maximum width of 1”/25 mm.

  • OFFICE

  • 1 Skirtings to be installed

  • 2 Pantry-printer room ffe to be finished

  • LAUNDRY VALET

  • 1 Outlet for a wall-mounted house telephone.

  • 2 FFE to be procured. Table for folding laundry with adjustable heights.

  • HOUSEKEEPING

  • 1 HSK office ffe to be procured

  • 2 HR office ffe to be procured- skirtings to be finished

  • ENGINEERING

  • 1 ffe to be procured

  • 2 Workbench.

  • 3 skirting at chief engineer office to be done

  • DINING/BREAK ROOM

  • 1 skirtings

  • 2 "Tables and chairs not procured

  • "

  • 3 "TV to be installed

  • "

  • 4 Min. 1 outlet for a house telephone if not adjacent to laundry.

  • LOCKER ROOM

  • 1 Paper towel dispensers to be mounted.

  • 2 Electric hand dryers to be installed

  • 3 Benches to be placed

  • 4 Toilet accessories to be placed

  • ELECTRICAL ROOMS

  • to be checked

  • MECHANICAL ROOMS

  • to be checked

  • COMPUTER/TELECOM ROOM

  • to be checked

  • TRASH COLLECTION AREA

  • 1 Thrash collection doors need stoppers to avoid hitting the fire piping

  • RECEIVING AREA

  • 1 CCTV and receiving offices ffe to be procured

  • 2514 Technical Criteria

  • 1 Provide doorstops for all doors

  • 2 Minimum of three commercial-grade hinges for all doors

  • 3 "Electronic locksets are required in the following locations (deadbolt must be removed with the exception of the guestroom entry):

  • Main entry door to the property

  • Each guestroom entry

  • Fitness Center

  • Indoor swimming pool entry and secondary entries (exception: entry from secure outdoor patio)

  • Guest Laundry

  • Meeting rooms

  • Boardroom

  • Computer/Telecom Room

  • Secondary guest entrances to the public corridors"

  • 4 "Areas that must be provided access-control devices include, but are not limited to: Entrance to front office area

  • Back office areas accessible from public corridors

  • Team member entrance, if not monitored

  • Connecting door when provided to the office area from the business center

  • Back-of-house access from meeting rooms

  • Luggage storage room(s)"

  • 5 Full height corner guards at outside wall corners in all public areas susceptible to damage - must be a resilient vinyl to coordinate with the wall color and must be adhesive mount. The flanges must be a maximum width of 25 mm.

  • 6 "Internet access must be provided in the following areas:

  • Guestroom - wireless required; wired optional

  • Lobby - wireless

  • Meeting rooms - wireless

  • Boardroom - wireless

  • Business center - wired for business center equipment; wireless for guests

  • Restaurant - wireless

  • Bar - wireless (includes Lounge)

  • Team Member Back of House Areas"

  • 7 "Sound System (background music) is required in the following areas:

  • Patio

  • Lobby

  • Public restrooms

  • Dining area/restaurant/bar

  • Lounge

  • Meeting room/boardroom

  • Pre-function

  • Elevator lobbies

  • Team Member Back of House Area"

  • 2519 SIGNAGE AND GRAPHICS

  • INTERIOR SIGNAGE

  • to be checked

  • PARKING SIGNAGE

  • to be checked

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.