Information
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
-
PLEASE NOTE :- TRANSPORT RANDOM CHECKLIST MUST ALSO BE COMPLETED. SPEED GUN AVAILABLE FROM THE EHS&Q OFFICER.CPR118/A TESTING OF EMERGENCY PROCEDURES CHECKLIST MUST ALSO BE COMPLETED
-
Enter Date of Inspection
-
Please sign:
Main Office
-
Fire extinguishers in position and within test expiry date?<br>
-
Are Fire Exit Doors are operating correctly? <br>
-
Are Emergency Exits and Walkways clear of obstructions?<br>
-
Are Amenities are all in good condition and working properly?
-
Is Housekeeping is in good order?
-
Are appropriate notices displayed and in good condition?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Are operators wearing the correct P.P.E?
-
Is Fire exit door is operating correctly?
-
Is Housekeeping in good order?
-
Any further comments?
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Toilets (2 off) housekeeping
-
Are Boiler House fire extinguishers in position and within test expiry date?
-
Toilets (2 off) housekeeping
-
Any further comments?
Fixing Materials Stores
-
Fire extinguishers in position and within test expiry date?<br>
-
Are Fire Exit Doors are operating correctly? <br>
-
Washroom housekeeping in good order?
-
Shower housekeeping in good order?
-
Toilets (2 off) housekeeping
-
All appropriate notices are displayed and in good condition?
-
Amenities are all in good condition and working properly?<br>
-
Oil Heater, supply tank and pipework in good order?
-
Racking in good condition?
-
Are SWL signs in position?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
M.C.S. Workshop in good working condition?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Are Emergency Exits and Walkways clear of obstructions?
-
Is a 6S system in place in the Fixing Materials Stores?
-
Sub Station fire extinguishers in position and within test expiry date (padlock combination 5588)
-
Sub Station housekeeping is in good order?
-
Any further comments?
Yard Area
-
Main entrance gate and fence line in good order?
-
Yard area at MCS compound in good order?
-
Yard area at transport Wagon Wash in good order?
-
Is the Yard area where old Transport Diesel Tank used to be in good order?
-
Is wooden boarding around hill areas in good condition?
-
Is oil level on hydraulic unit at Netting Station okay? ( report to maintenance if low )
-
Any further comments?
Sand Delivery Hopper Area
-
House keeping on and around ramp and inside guarded compound around belt in good order?
-
Are Guards in good condition?
-
Are Spill Kit covers and sand container in position?
-
Any further comments?
Sand Silo Building
-
Fire extinguishers in position and within test expiry date?<br>
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Are Walkways around Dragout Conveyors free of any trip hazards?
-
Is Housekeeping on both levels in good order?
-
Any further comments?
Screen House Building 3 Levels
-
Fire extinguishers in position and within test expiry date?<br>
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Is Housekeeping on all levels in good order?
-
Any further comments?
Forklift Workshop
-
Fire extinguishers in position and within test expiry date?<br>
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is Fire Exit Door operating correctly when locked?
-
Is Housekeeping in good order?
-
Is Extraction unit in working order?
-
Is there a 6S system in place in the Forklift Workshop?
-
Any further comments?
Packaging Area (Rotary Drier and OMS)
-
Fire extinguishers in position and within test expiry date?<br>
-
Check Fire Exit Door at OMS is operating correctly when locked.
-
Is Housekeeping in good order?
-
Are all guards around Rotary Drier and OMS in good repair?
-
Are Power Packs free from oil leaks?
-
Are Spill Kits in position?
-
Is Control Room housekeeping in good order?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Are operators wearing the correct P.P.E?
-
Is a 6S system in place in the Packaging Area?
-
Is a 6S system in place in the factory Dryside Area?
-
Any further comments?
Paint Unit
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Fire Exit Door working correctly when locked?
-
Is Housekeeping in good order?
-
Are all guards in good repair?
-
Is Racking in a good condition?
-
Are SWL signs in position?
-
Are all Vehicle sheets filled in correctly?
-
Is Paint Tote Bunded Stand area clean & tidy?
-
Are operators wearing the correct P.P.E?
-
Is there a 6S system in place for the Paint Unit Quality Area?
-
Any further comments?
First Aid Room
-
Are all appropriate notices on Notice Board outside Lab are displayed and in good condition?
-
Is the Accident Book available?
-
Are Accident Reporting forms available?
-
Are Near Miss forms are available?
-
Is First Aid Equipment in order and forms signed?
-
Is Housekeeping in good order?
-
Any further comments?
Q.A. Lab
-
Is Housekeeping in good order?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is there a 6S system in place for the QA Lab?
-
Any further comments?
Locker / Toilets (2off) & Shower Room
-
Is Housekeeping in good order?
-
Any further comments?
Mess Room & Kitchen
-
Fire extinguishers in position and within test expiry date?<br>
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is Housekeeping in good order?
-
Any further comments?
Switch Room
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Any further comments?
Compressor Room
-
Is Housekeeping in good order?
-
Is there a 6S system in place for the Compressor Room
-
Any further comments?
Racking Plant and Curing Cambers
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Fire Exit Door at roller shutter door at side of curing chambers operating correctly when locked?
-
Are Fire Exit Doors at rear end of building operating correctly when locked?
-
Is Housekeeping in good order?
-
Are all guards around Racker in good repair?
-
Are Power Packs and pipes free from oil leaks?
-
Are Spill Kits in position?
-
Is Control Room housekeeping in good order?
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Are walk ways around curing chambers clear?
-
Is there a 6S system in place for the Area?
-
Is the Floor Sweeper charging station in a good condition?
-
Are operators wearing the correct P.P.E?
-
Any further comments?
Electricians Workshop
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Are Work Benches tidy?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is there a 6S system in place for the Electricians Workshop?
-
Any further comments?
Maintenance Workshop
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Fire Exit Door operating correctly when locked?
-
Is Housekeeping in good order?
-
Are Work Benches tidy?
-
Is Radial Arm Drilling machine in good order?
-
Is Pedestal Grinder in good order?
-
Is The welding bay in good order?
-
Is the Clarke Strong Arm Press in good order?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is there a 6S system in place for the Pump Testing Station?
-
Is there a 6S system in place for the Maintenance Workshop?
-
Are operators wearing the correct P.P.E?
-
Any further comments?
Machine Room
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Is Milling Machine in good order?
-
Is Lathe in good order?
-
Is there a 6S system in place for the Machine Room?
-
Any further comments?
Mixer Control Room
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Are Electrical Panel doors locked and panels checked for IP2X?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is the working area clean & tidy?
-
Any further comments?
Raw Material Store (FACTORY)
-
Is Housekeeping in good order?
-
Is Racking in good Condition?
-
Are SWL signs in position?
-
Is the working area clean & tidy?
-
Does Sodium Lamp box need emptying?
-
Does WEEE box need emptying?
-
Any further comments?
Raw Material Store (YARD)
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Is Racking in good Condition?
-
Are SWL signs in position?
-
Is the working area clean & tidy?
-
Is Fire exit door is operating correctly?
-
Any further comments?
Machine Area
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Are Maintenance Work Benches tidy?
-
Is Fire Exit Door between Shift Managers office and Raw Material Stores is operating correctly when locked?
-
Are operators wearing the correct P.P.E?
-
Are Ladders secure?
-
Are Ladders signed in and out?
-
Is there a 6S system in place for the Factory Wetside Area?
-
Is there a 6S system in place for the Machine Area Cleaning Equipment?
-
Is there a 6S system in place for the Maintenance Workbench?
-
Any further comments?
Engineering Stores
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Fire exit door is operating correctly?
-
Is Housekeeping in good order?
-
Is Racking in good Condition?
-
Are SWL signs in position?
-
Is electrical equipment being used P.A.T. and up to date? Please note Asset numbers of items checked.
-
Is there a 6S system in place for the Engineering Stores?
-
Is there a 6S system in place for the Lifting Equipment?
-
Any further comments?
Body Colour Mixing Area
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Is the Pressure wash in good order and cabinet locked?
-
Is Bund under tanks in order?
-
Is the Platform around tanks in good order?
-
Any further comments?
Mixing Platform (4 Levels)
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Is Mixer platform in good order?
-
Is 2nd level platform in good order?
-
Is 3rd level platform (Hogan Feeders) in good order?
-
Is 4th Level (Over day bin) in good order?
-
Any further comments?
Boiler House
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Are Oil tanks and supply pipes free from oil leaks?
-
Is there a 6S system in place for the boiler house?
-
Any further comments?
Old MSK Shed
-
Fire extinguishers in position and within test expiry date?<br>
-
Is Housekeeping in good order?
-
Test bund alarm on rape seed oil tank.
-
Any further comments?