Title Page

  • Site conducted

  • Conducted on

  • Prepared by

  • Location

Substation

  • Is there a Substation on site

MSB

  • Photos of External and internal of board.

  • Can the MSB be isolated externally.

  • Is there a site Single Line Diagram (SLD)

  • Can the board be isolated during hours or does it need to be done after hours?

  • Condition & Rough age of MSB (are parts still readily available or are boards end of life?

  • Are the boards labelled and have switchboard schedules

  • Provide Thermograph Photos and Report

  • Supply Type

  • Meter Type

  • Photo of meter

SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

  • Are there more SB

  • Switchboard Name

  • Photos of External and internal of boards

  • Breaker name and model

  • Circuit Breaker details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • RCBO details - Total amount per amps (eg. 4x 20a 1P, 7x32a 3P)

  • Is the board labelled and have switchboard schedules

  • Condition & Rough age (are parts still readily available or are boards end of life?)

  • Provide Thermograph report

Exit and Emergency

  • Do they have EEL Test switches/ Log Books and site plans

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.