Draws and documents relied on for inspection

  • Drawings:

  • Specification/Technical Submission:

PRE-INSULATION

  • Layout, matches contract drawings?

  • Have all inspection and acceptance testing of the piping/ducting as required by the specification been completed and that the system is ready for installation of insulation (e.g., leak/pressure tests)?

  • Test points on ductwork and pipework provided with extension pieces?

  • Valve stems on pipework provided with extension pieces?

  • Where external have valve handles been positioned between 4 to 8 o'clock to minimise water entry?

  • Where external have access doors/test holes been positioned on side or bottom of duct to prevent water entry?

  • Have all pipe/duct hangers, supports and anchors installed in accordance with the project specification?

  • Bracket supports provided as BS5422?

  • Vapour barrier continous over insulation blocks at support points (i.e. foil facing maintain on insulation block under bracket)?

  • Where insulation is external weatherproofing is continous at support points (i.e. weatherproof membrane is taken over insulation block under bracket)?

  • Pipe sleeve of sufficient size to allow the insulation to go through walls except fire barriers?

  • Firewalls – fire sleeves installed?

  • Surfaces to be insulated clean and any necessary surface preparation or coatings completed?

  • All materials (insulation, coverings, tapes, etc.) delivered to the jobsite in factory containers with manufacturer’s label showing manufacturer, product name and product fire hazard information

  • Has the insulation materials been manufactured at facilities with an acceptable quality control program?

  • Any insulation materials that are damaged, wet, or contaminated?

  • Is there adequate clearance to install the insulation in accordance with project drawings, operation performance parameters of the specification, such as access to controls, valves and for maintenance and repair

  • Where insulation is installed external are all building entry points weather sealed to allow insulation to be abutted to complete weather membrane?

  • Has all fire stopping been completed?

  • Any required trace heating installed?

  • Photos

GENERAL

  • Does the installed insulation product satisfy the specification?

  • Has the insulation been protected from dirt, water, chemical attack, and mechanical damage before and during installation?

  • Has the installation been performed by qualified engineers?

  • Damage to insulation?

  • Unused materials returned to stores?

  • Waste materials removed and disposed, and area left clean?

  • Plant and equipment demobilised and returned?

  • Facilities inspected for damage or neglect?

  • Works Area inspected for damage or neglect?

  • General Photos

INSULATION INSTALL

  • Does the installed insulation product satisfy the specification?

  • Has the correct thickness been applied in accordance with the specification?

  • Has the product been cut to size accurately?

  • Has the insulation been pulled tight and fitted in close contact to the surface?

  • Close fit of adjacent edges?

  • Has the total surface been covered?

  • Have all the fibres been encapsulated within the insulation finish?

  • Are all joints sealed?

  • Type and position of fixings are as per specification?

  • Terminations neatness, flange bolt clearance etc. in line with specification?

  • Has the correct tape been used?

  • Does the installed vapour barrier product satisfy the specification?

  • Vapour barrier unbroken or damaged?

  • Vapour barrier continuous through walls etc.?

  • Vapour barrier sealed at brackets, fittings, terminations, supports etc.?

  • Vapour barrier overlaps are adequate and sealed?

  • General Photos

FINISHES

  • Does the installed insulation product satisfy the specification?

  • Formation of cladding as specification and/or BS5970?

  • Fixings to specification and/or BS5970?

  • Fittings will be checked for joint overlaps and installation as specification and/or BS5970?

  • Terminations neatness, flange bolt clearance etc. in line with specification?

  • Where cladding is applied lap joints are positioned "out of view"?

  • Damage to finishes?

  • No dangerous edges or corners?

  • General Photos

WHERE EXTERNAL

  • Where insulation is external "water-stops" are positioned at support blocks ?

  • Weather-proof membranes installed with Water-shedding?

  • Where ductwork has side > 800mm has a fall been formed on top to shed water?

  • Damage to weather-proof membrane?

  • General Photos

VALVE & FLANGE INSULATION

  • Does the installed product satisfy the specification?

  • Has the insulation been fitted tightly and aligned to the fitting?

  • Where jackets or boxes installed do they land on adjacent insulation by minimum 50mm?

  • Where jackets or boxes installed insulant contained and fitted without gaps?

Outstanding items:

  • Notes:

SIGN OFF

  • INSPECTION COMPLETED

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.