Title Page

  • Site conducted

  • Conducted on

Untitled Page

  • Check and record operating flow temperatures from water heaters (integral cold-water storage type). (Minimum Control Level = 60C) Take action to raise operating temperature if below 60C, with outlets distributing at a minimum 50C.

  • Check and record flow temperature from small volume unvented<br>water heaters. (Minimum Control Level = 50- 60C) Take action to<br>raise operating temperature if below 50C. - tap closest to tank - check tank gauge

  • Check and record hot water storage vessel operating flow and<br>return temperatures. Take action to raise operating temperature if<br>below 60C and 50C respectively. - Surface probe

  • Check & record hot water temperature at sentinel outlets<br>(Principal loops) or at input to TMVs on a sentinel basis (if fitted).<br>Control Range = 50C. Take action to adjust hot water temperature<br>if outside acceptable range. - Horton Bathroom

  • Check & record mains water temperature at sentinel outlets. (Maximum<br>Control Level = 20C) If temperatures exceed 20C review the risk<br>assessment and consider the need for further control measures.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.