Check and record operating flow temperatures from water heaters (integral cold-water storage type). (Minimum Control Level = 60C) Take action to raise operating temperature if below 60C, with outlets distributing at a minimum 50C.
-
Check and record flow temperature from small volume unvented<br>water heaters. (Minimum Control Level = 50- 60C) Take action to<br>raise operating temperature if below 50C. - tap closest to tank - check tank gauge
-
Check and record hot water storage vessel operating flow and<br>return temperatures. Take action to raise operating temperature if<br>below 60C and 50C respectively. - Surface probe
-
Check & record hot water temperature at sentinel outlets<br>(Principal loops) or at input to TMVs on a sentinel basis (if fitted).<br>Control Range = 50C. Take action to adjust hot water temperature<br>if outside acceptable range. - Horton Bathroom
-
Check & record mains water temperature at sentinel outlets. (Maximum<br>Control Level = 20C) If temperatures exceed 20C review the risk<br>assessment and consider the need for further control measures.