  • Daily Tasks

  • Log condenser and oil pressure readings.

  • Check general condition.

  • Check for excessive noise or vibration.

  • Inspect for water leaks.

  • Check oil level in sump.

  • Weekly Tasks

  • Check motor for overheating.

  • Check refrigerant level.

  • Check refrigerant system for leaks.

  • Inspect operation of purge system.

  • Log purge cycle counter reading.

  • Inspect water treatment system operation.

  • Monthly Tasks

  • Inspect all valves for leaks.

  • Check control system settings and operation.

  • Check filters and strainers.

  • Annual Tasks

  • Inspect all wiring, starters, and disconnects.

  • Test operation of all safety controls.

  • Meg motor windings.

  • Calibrate chiller controls.

  • Change purge unit dehydrators.

  • Change compressor oil and filter.

  • Check operation of purge system.

  • Inspect condenser tubes for scale and fouling.

  • Inspect chiller case for rust.

  • Inspect chiller and piping insulation.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.