1. Walls & Roof Load
[Wall Area (1,000 sq ft)➕Roof Area (1,000 sq ft)]✖️0.4 = Walls & Roof Load (tons) -
Walls & Roof Load (tons)
-
2. Window Load
Window Area (1,000 sq ft)✖️Window Factor (tons / 1,000 sq ft) = Window Load (tons) -
3. Ventilation Air Load
Floor Area (1,000 sq ft)✖️Ventilation Rate (cfm / 1,000 sq ft)✖️2.5 = Ventilation Load (tons) -
Ventilation Load (tons) =
-
4. Lighting Load
Floor Area (1,000 sq ft)✖️Lighting Load (Watts / sq ft)✖️0.28 = Lighting Load (tons) -
Lighting Load (tons)=
-
5. Occupant Load
Floor Area (1,000 sq ft)✖️Load Factor (tons / 1,000 sq ft) = Occupant Load (tons) -
Occupant Load (tons) =
-
6. Equipment Load
Floor Area (1,000 sq ft)✖️Equipment Factor (Watts / sq ft)✖️0.28 = Equipment Load (tons) -
Equipment Load (tons)
-
7. Total Cooling Load
Walls & Roof Load (tons)➕Window Load (tons)➕Ventilation Load (tons)➕Lighting Load (tons)➕Occupant Load (tons)➕Equipment Load (tons) = Cooling Load (tons) -
Cooling Load (tons) =