Title Page

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

  • 1. Bare Pipe Heat Loss

  • 18.4 ➕ 0.66 ✖️ Pipe Diameter (inches) ✖️ [Water Temp. (Degrees F) ➖ Space Temp. (Degrees F)] = __________ Bare Pipe Heat Loss (Btu / ft)

  • 2. Heat Loss Factor

  • Insulation U - Value ✖️ [Pipe Diameter (inches) ➕ 2 ✖️ Insulation Thickness (in.)] = __________ Heat Loss Factor

  • 3. Insulated Pipe Heat Loss

  • Heat Loss Factor ✖️ 0.179 ✖️ [Water Temp. (Degrees F) ➖ Space Temp (Degrees F)] ➖ 3.01 = __________ Insulated Pipe Heat Loss (Btu / ft)

  • 4. Energy Savings

  • [Bare Pipe Heat Loss (Btu / ft) ➖ Insulated Pipe Heat Loss (Btu / ft)] ✖️ Pipe Length (ft) ✖️ 0.000001 = __________ Energy Savings (Millions of Btu)

  • 5. Cost Savings

  • Energy Savings (Millions of Btu) ✖️ Energy Cost ($ / million Btu) = __________ Cost Savings ($)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.