BARRIER INFORMATION
-
Entered Barrier Model number?
-
Entered Barrier Serial Number?
-
Enter Type of barrier:
-
Enter software version? (if ANY)
Prior to concrete pour, perform ONLY the Visual Inspection and Insulation Resistance Tests. After the pour perform ALL tests.
1. Perform Visual Inspection.
-
1.1. Confirm 30-mA ground-fault device marked for proper rating. Is device marked per drawing?
-
Enter description/explanation of device markings.
-
If possible, take a picture of the device markings.
-
1.2. Visually inspect inside connection boxes for overheating, corrosion, moisture, loose connections, or other problems. Are there any problems?
-
Enter description/explanation of problem or problems.
-
If possible, take a picture or pictures showing problems.
-
1.4. Barrier goes to the UNSECURED/OPEN/DOWN position in standard operating time?
-
1.5. SECURED/CLOSED/UP position initiated via the push button on Remote panel(s)?
-
1.6.UNSECURED/OPEN/DOWN position initiated via the push button on Remote panel(s)?
-
1.7.Verified Indicating lights for status of barrier position on master panel?
-
1.8. Verified Indicating lights for status of barrier position on remote panel?
-
1.9. Verified all ILLUMINATED SWITCHES or LIGHTS are functional on both Master control panel(s) and Remote panel(s), If applicable.
-
1.10. Verified AUDIBLE ALRAM to indicate barrier left in the UNSECURED/OPEN/DOWN <br>position for operator determined time period, If applicable.
-
1.11. Verified all TRAFFIC LIGHTS - RED ON SECURED/CLOSED/UP Position are functional, If applicable.
-
1.12. Verified all TRAFFIC LIGHTS - AMBER ON UNSECURED/OPEN/DOWN Position are functional, If applicable.
-
1.13. Verified all TRAFFIC ARMS - ARM in the DOWN POSITION when Barrier is in the SECURED/CLOSED/UP Position are functional, If applicable.
-
1.14. Verified all TRAFFIC ARMS - ARM in the UP POSITION when Barrier is in the UNSECURED/OPEN/DOWN Position are functional, If applicable.
-
1.15.Verified all SAFETY Control Loops are functional, If applicable.
-
1.16.Verified all EXIT Control Loops are functional, If applicable.
-
1.17.Verified all CARD ACCESS Control Loops are functional, If applicable.
-
1.18.Verified all SPEED DETECTION Loops are functional, If applicable.
-
1.19.Verified all WRONG WAY DETECTION Loops are functional, If applicable.
-
Enter any corrective actions that WILL NEED to be undertaken.
-
Perform a Visual Inspection of Barrier for any damages.
2. Sequence of Operations - EMERGENCY MODE
-
2.1. ALL Barriers in SECURED/CLOSED/UP Position initiated via the EFO/E-UP Push Button on Master Panel?
-
2.2. ALL Barriers in SECURED/CLOSED/UP Position initiated via the EFO/E-UP Push Button on REMOTE Panel?
-
2.3. ALARM sounds continuously , until MANUAL (KEY) RESET of the system.
-
2.4. Barrier goes to SECURED/CLOSED/UP position in Approx. one (1) second. ALARM sounds continuously , until MANUAL (KEY) RESET of the system.
-
2.5. Verified all ILLUMINATED SWITCHES or LIGHTS are functional on both Master control panel(s) and Remote panel(s) during EFO/E-UP, If applicable.
-
2.6.. Verified all TRAFFIC LIGHTS - RED ON SECURED/CLOSED/UP Position are functional during EFO/E-UP, If applicable.
-
2.7. Verified all TRAFFIC ARMS - ARM in the DOWN POSITION when Barrier is in the SECURED/CLOSED/UP Position are functional during EFO/E-UP, If applicable.
-
Enter any corrective actions that WILL NEED to be undertaken
3. Sequence of Operations - SPECIAL MODE
-
Fill in any Special Sequence of Operations requirements and Authorized END-User MUST SIGN.
-
AUTHORIZED END-USER APPROVAL AND ACCEPTANCE FOR SPECIAL SEQUENCE
APPROVAL and ACCEPTANCE AUTHORIZED SIGNATURES (must be signed and date for Warranty)
-
On Site Representative (GC/Customer)
-
End-User Representative
-
NASATKA Representative
Signature Acknowledgement
-
ELECTRONIC SIGNATURE ACKNOWLEDGE, I AGREE THAT MY ELECTRONIC SIGNATURE <br>IS A LEGALLY BINDING EQUIVALENT TO MY HANDWRITTEN SIGNATURE. WHENEVER I <br>EXECUTE AN ELECTRONIC SIGNATURE, IT HAS THE SAME VALIDITY AND MEANING AS <br>MY HANDWRITTEN SIGNATURE. I WILL NOT AT ANY TIME IN THE FUTURE, REPUDIATE <br>THE MEANING OF MY ELECTRONIC SIGNATURE OR CLAIM THAT MY ELECTRONIC SIGNATURE <br>IS NOT LEGALLY BINDING.