Title Page
-
Site conducted
-
Conducted on
-
Conducted by
Water Storage Tank
-
Check water level indicator (s) is operational.
-
Check ball valve operation and verify tank water level.
-
Check ladder and access platform in good condition and secure from unauthorised access.
-
Check for damage to the tank or its roof and if there are any leaks
-
Observations
Pump House
-
Check pump house is not being used for storage
Check minimum temperature has not dipped below 10°c
Check also that temperature does not rise by more than 10°c during the test.
-
Observations
Jockey Pump
-
After isolating any other pumps, simulate pressure reduction on the small-bore hydraulic pump start connection (closing stop valve and very slowly opening drain valve).
-
Record cut-in pressure of the jockey pump.
-
Return these valves to normal position.
Electric Pump
-
Check mains power indicator on pump controller panel is lit.
-
After isolating any other pumps, simulate pressure reduction on the small-bore hydraulic pump start connection (closing stop valve and very slowly opening drain valve).
-
Record cut-in pressure of the electric pump.
-
Return these valves to normal position.
-
Run pump for 5 minutes.
-
Whilst the pump is running, check visual and audible alarms at the remote indicator panel.
-
Close main test valve and shut off the pump.
-
Start pump manually from the controller (if fitted).
-
Stop the pump and return the system to normal.
Diesel Pump
-
Note: Diesel pump should not be left unattended
-
After isolating all other pumps, simulate pressure reduction using the small-bore hydraulic pump start connection (by closing the stop valve and very slowly opening the drain valve).
-
Record cut-in pressure of diesel pump.
-
Return these valves to normal position.
-
Run for at least 5 minutes.
-
Whilst the pump is running, check visual and audible alarms at the remote indicator panel.
-
Stop the pump and return the system to normal.
Completed by
-
Signature
-
Date