Page 1: Initial questions
-
Conducted on
-
Prepared by
-
Location
Checking position
-
Position
Page 3: ELECTRICAL
GENERAL ELECTRICAL CHECK
-
Electrical installation layout/drawings available
-
All components for installation are available/delivered
-
All components for installation are installed and properly secured
-
Conveyors are grounded to PE bar in MP and interconnected (see installation guide for instructions).
-
All groundings connected to metal (not on painting etc.)
-
Earthing: The resistance between the PE terminal (see 5.2 and Figure 4) and relevant points that are part of the protective bonding circuit shall be measured with a current between at least 0,2 A and approximately 10 A derived from an electrically separated supply source
-
All measurement protocols are done (according to IEC and local standards)
-
Belt tracking and tensioning positions are not blocked by containment or support brackets
-
Electrical enclosure is free from any fluid handling systems (i.e. pneumatics, hydraulics)
-
Record serial number of all installed encoders and their positions to Critical material tracking sheet
-
Record serial number of all installed VFDs and their positions to Critical material tracking sheet
Main panel
-
Positioned and fixed as per area layout with no visible external damage
-
Kick plates, corner covers, fan cover and lifting eyes are fitted
-
Signal column and beacon are fitted
-
All required labels are installed (example: 400V Warning label, Isolation Warning label, Traffolyte identification label etc)
-
Equipotential bond from the cabinet earth bar to the area cable containment are installed
-
Equipotential bonds from the cabinet frame to the cabinet doors are fitted
-
No missing components
-
Field cables are terminated, all spare cores have the ends insulated, cable sheath markers are fitted
-
Unused cable glands are removed and replaced with blanking plugs
-
Trunking covers are present and fitted
-
Clean, free of debris and combustible material
-
Provide a safety measurement record of Live Test of AC Branches with certified measurement device (record shall be provided by Authorised person)
-
Provide a safety measurement record of Dead Test of AC branches with certified measurement device (record shall be provided by Authorised person)
-
Provide a safety measurement record of main cable feeding our MP from customers MDP (main distribution panel) (record shall be provided by Authorised person)
-
Provide a callibration certification of the measuring devices (electronicaly)
Cable trays
-
Routes are installed as per specifications; all deviations are approved by the HW EM Site Supervisor
-
All cable trays are securely fixed and lidded throughout
-
Support brackets / threaded rods are filed and painted at cut edges, end caps are fitted
-
Clean, free of debris and combustible material
-
Cable tray is grounded with an earth strap ≧6mm2
-
Edging strip fitted at point of contact with cables, filed and painted at cut edges. The edges of cable tray edges should be protected not to cut the cables
Cables
-
Cables are segregated as per drawings and the installation standard
-
Wraps are trimmed with no sharp edges
-
Cables are undamaged, with no cuts in the cable or core insulation. No exposed conductors.
-
Cables are terminated neatly (spare length kept to the minimum) using the correctly sized ferrules. All spare cores are fitted with sleeves at their bare ends
-
Sheath markers are fitted to both ends of all cables with the text reading away from the gland or terminal
-
Uniform cabling methods are used for similar situations with all cables securely tied to the containment as required, cable bend radius are not tight
-
Field cables are terminated, all spare cores have the ends insulated, cable sheath markers are fitted
-
MDR motor cables are not in contact with belt
Panels installation
-
Positioned and installed as per the mechanical installation layouts, deviations are approved by the HW EM Site Supervisor
-
No visible external damage
-
All required labels are installed
-
Local Cabinets are equipotentially bonded with cable containment by means of an earth-strap ≧6mm2
-
All unused cable glands are removed and replaced with blanking plugs
-
Clean, free of debris and combustible material
Field Kit installation
-
Connectors to field devices are secure (PEC’s/Proximity switches)
-
Legends fitted to all control switches, push buttons and indicators
-
Pen marks and temporary tape labels have been removed
Profinet and communication Installation
-
Cable segregated from all power cables by means of barriers
-
Minimum length of cable between nodes ≥ 1m
-
Segment lengths are within the specification / schematics
-
Cables do not run parallel to power cables inside cabinets
-
All terminators are set as per the schematics
-
Network Report completed