  • These plant checks were carried out on

  • Prepared by

Roof Plant

  • AHU1 &AHU2<br>Running ok (green lights)<br>There are no alarms(red lights)

  • Extract fans <br>Running ok (green lights)<br>There are no alarms(red lights)

2nd floor

PDU room 2

  • PDU/SF2. <br>Phases healthy <br>On preferred supply <br>Free from visible problems

  • CRAC unit set to 21 and achieving temperature between 20/21.5

PDU room 1

  • PDU/SF1<br>Phases healthy <br>On preferred supply <br>Free from visible problems

  • CRAC unit set to 21 and achieving temperature between 20/21.5

PDU room 3

  • PDU/SF 3&4<br>Phases healthy <br>On preferred supply <br>Free from visible problems

  • CRAC unit set to 21 and achieving temperature between 20/21.5

Comma 2a

  • CRAC unit set to 21 and achieving temperature between 20/21.5

Comma 2b

  • CRAC unit set to 21 and achieving temperature between 20/21.5

1st Floor

Comma room 1b

  • CRAC unit set to 21 and achieving temperature between 20/21.5

  • CRAC unit set to 21 and achieving temperature between 20/21.5

Comma room 1a

  • CRAC unit set to 21 and achieving temperature between 20/21.5

  • CRAC unit set to 21 and achieving temperature between 20/21.5

PDU Room 1

  • PDU/FF1<br>Phase healthy<br>On preferred supply <br>

  • CRAC unit set to 21 and achieving temperature between 20/21.5

PDU Room 2

  • PDU/FF2<br>Phase healthy<br>On preferred supply <br>

  • CRAC unit set to 21 and achieving temperature between 20/21.5

Ground floor

  • Bulk tank <br>in auto <br>No alarms

Stand by generator

  • Set to auto <br>Hot water heater working <br>No alarms

  • Bulk tank fuel levels LTRS

  • Day tank fuel levels LTRS

Plant room

  • Primary pump unit is set to 1.1 Record pressure

  • Secondary pump unit is set to 2.7 Record pressure

  • BMS panel has no alarms <br>All green lights no red

  • Gas solenoid shut off normal running position

  • Water leak detection system all ok

  • Water solenoid shut off normal running position

Battery room A

  • CRAC unit set to 21. and achieving temperature >21.5<br>Battery backup system fault free<br>No visible signs of damage

Battery room B

  • CRAC unit set to 21. and achieving temperature >21.5<br>Battery backup system fault free<br>No visible signs of damage

UPS ROOM A

  • UPS A1&2 <br>No alarms <br>Not in bypass <br>CRAC unit reporting >21.5<br>Split A/C reporting >21.5<br>

UPS ROOM B

  • UPS B1&2<br>No alarms <br>Not in bypass <br>CRAC unit reporting >21.5<br>Split A/C reporting >21.5<br>

Electric switch room

  • System fault free<br>System alarm free <br>No visible signs of damage <br>Sign in and record time

Equipment Hall

  • PDU/GF3<br>phases healthy <br>On preferred supply <br> <br>

  • PDU/GF2<br>phases healthy <br>On preferred supply <br> <br>

  • CRAC unit 15A. set to 18 and achieving temperature >18.3

  • CRAC unit 15D. set to 18 and achieving temperature >18.3

  • PDU/GF8<br>phases healthy <br>On preferred supply <br> <br>

  • PDU/GF1<br>phases healthy <br>On preferred supply <br> <br>

  • PDU/GF4<br>phases healthy <br>On preferred supply <br> <br>

  • CRAC unit 15C. set to 18 and achieving temperature >18.3

  • PDU/GF7<br>phases healthy <br>On preferred supply <br> <br>

  • CRAC unit 15B. set to 18 and achieving temperature >18.3

SER

  • PDU/GF5<br>phases healthy <br>On preferred supply <br> <br>

  • CRAC unit set to 18 and achieving temperature >18.3

  • CRAC unit set to 18 and achieving temperature >18.3

CER

  • PDU/GF6<br>phases healthy <br>On preferred supply <br> <br>

  • CRAC unit set to 18 and achieving temperature >18.3

  • CRAC unit set to 18 and achieving temperature >18.3

Risers

  • Checked to make sure all risers are ok

BMS Checks in the security room

  • The BMS alarm system is healthy <br>Green light no red lights

LTHW Heating system

  • Note A or B pump Running

  • Note flow temperature

  • Note return temperature

  • Note storage temperature

Air cooled chiller

  • Note A or B pump Running

  • Note flow temperature

  • Note return temperature

Internal chilled plant

  • Note A or B pump Running on primary

  • Note A or B pump Running on secondary

  • Note flow temperature primary

  • Note return temperature secondary

Cold water storage tanks

  • Cold water storage tank 1 temperature

  • Cold water storage tank 2 temperature

Sign check sheet as completed

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.