Compressor Checks
-
Check the tightness of the Rota lock/service valve connections on the compressor body
-
Check the crankcase heater is operational when the compressor is not running
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Oil system checks
-
Check the compressor and reservoir oil levels are sufficient.
-
Check all oil management device functionality
-
Take an oil sample (one shot test) and send for analysis
-
Image of oil sample
-
Using a differential or calibrated gauge, check the pressure differential between the suction and reservoir. For coalescent separators, check pressure drop across internal filter
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
System & Pack Control Switches, controllers, controlls
-
Check & test all pressure switches (high pressure, low pressure & oil differential)
-
Trip the main plant hp switch circuit and record pressure plant tripped
-
Using a calibrated gauge, check suction and pressure transducers are reading correctly, calibrate as required. Record current offset and alterations if required
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Filters & driers checks
-
Check for pressure drops across filter
-
Supply details of any faults/defects found
-
Supply images of any faults/defects identified
Pressure Vessel/Reciever checks
-
Visually inspect pressure vessel/Reciever
-
Ensure there are no signs of corrosion
-
Supply details of any faults/defects found
-
Supply images of any faults/defects identified
PRV checks
-
Check PRV's are in date
-
List expiry dates for all PRVs
-
Supply images of PRV's
-
Are PRV's on dual port manifold
Pipe work and inline components
-
Check for visual damage, evidence of oil seepage
-
Check pipe insulation is fitted and confirm condition
-
Check all flexible lines & capillaries for evidence of oil seepage
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Electrical Panels and Switch gear, control panels
-
Check the condition and functionality of all external illuminated indicators
-
Check all internal cable management including conduit, trunking and tray work
-
Check all bonding straps to all doors
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Electrical panels and switch gear, control panels
-
Check that electrical panel door isolator / interlock is functional
-
Check panel keys are present
-
Are electrical wiring diagrams present
-
Ensure panel fans are operational and clean internal panel filter
-
Check for signs of overheating or arcing on all internal panel components
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Condenser checks
-
Check the condition of the condenser fins for signs of corrosion (inclusive of support structures)
-
Remove all loose debris
-
Is a deep clean with pressure washer required to clean condensers?
-
If deep clean required please provide pre clean images
-
Prior to deep clean provide anemometer reading from face of coil
-
Apply appropriate chemical cleaner & flush with water
-
Ensure all condenser control circuits and contactors are functioning and fans are freely spinning including directional/rotation checks.
-
Visually inspect to ensure all condenser fan fixings are in place and secure
-
If using EC fan motors, ensure the fan speed is varying as required
-
Where multiple non EC fan motors are being used, ensure the motors are staging as required
-
Please provide images of condenser coil post clean
-
Please provide anemometer reading post clean from face of coil
-
Please grade condenser coil condition after works completed
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Display Cases, defrost heaters
-
Where fitted and if accessible check the operation of the defrost heaters
-
Check the control set points please refer to up to date compendium
-
Check all joints between cabinets where multiplexed check all end walls are sealed to the cabinet
-
Check all condensate drain components for leaks or blockages inside and underneath the cabinets
-
Ensure that all fixtures are visible on the store remote network
-
Ensure all earth bonding and straps are in place and secure.
-
Condition of electrical control box and components, including all cable management, conduit, trunking and tray work.
-
Check all doors functioning correctly, seals intact and self closing mechanisms functioning
-
Night blind functionality
-
Fixture lights functional
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Cold store
-
Where fitted, check the operation of the defrost heaters
-
Trace/drain line heaters, where fitted, check operation
-
Check the control set points match up to date compendium
-
Ensure that fixture alarms are visible and available on the stores remote networks
-
Check the condition of the electrical control box, components, cable management, trunking, tray work & conduit
-
Check doors and curtain condition and functionality
-
Check walls and ceiling panels and floors for any signs of wear or damage
-
Check the evaporator fins for any signs of damage/debris, ensure inspection end plates are fitted
-
Check evaporator fans are functioning check correct rotation
-
Ensure that all entrapment alarms are functional.
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Temperature alarm panels
-
Check temp alarm panels can see all connected fixtures
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Store heating (freeheat packs)
-
Indoor unit air filter, check & clean
-
Check the condensate away system for blockage or dirt
-
Indoor unit - heat exchanger and refrigeration connections, check for contamination. Clean as necessary
-
Controllers - check operation
-
Indoor unit fan & motor. Running noise, check for abnormal noise. Clean fan
-
Electrical - check tightness of terminals, tighten as necessary. Check correct operation of all switches and interlocks
-
Supply details of any faults/defects found
-
Supply images of faults/defects identified
Additional information
-
Please list any additional information supporting these PPM checks, any restrictions preventing a full completion & any H&S issues requiring urgent attention
-
Are remedial works required
-
Please list remedial work order numbers