Title Page

  • Summer PPM Checks - multiclient - Arcus

  • Store number

  • Store name

  • Conducted on

  • Prepared by

  • Location

Compressor Checks

  • Check the tightness of the Rota lock/service valve connections on the compressor body

  • Check the crankcase heater is operational when the compressor is not running

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Oil system checks

  • Check the compressor and reservoir oil levels are sufficient.

  • Check all oil management device functionality

  • Take an oil sample (one shot test) and send for analysis

  • Image of oil sample

  • Using a differential or calibrated gauge, check the pressure differential between the suction and reservoir. For coalescent separators, check pressure drop across internal filter

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

System & Pack Control Switches, controllers, controlls

  • Check & test all pressure switches (high pressure, low pressure & oil differential)

  • Trip the main plant hp switch circuit and record pressure plant tripped

  • Using a calibrated gauge, check suction and pressure transducers are reading correctly, calibrate as required. Record current offset and alterations if required

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Filters & driers checks

  • Check for pressure drops across filter

  • Supply details of any faults/defects found

  • Supply images of any faults/defects identified

Pressure Vessel/Reciever checks

  • Visually inspect pressure vessel/Reciever

  • Ensure there are no signs of corrosion

  • Supply details of any faults/defects found

  • Supply images of any faults/defects identified

PRV checks

  • Check PRV's are in date

  • List expiry dates for all PRVs

  • Supply images of PRV's

  • Are PRV's on dual port manifold

Pipe work and inline components

  • Check for visual damage, evidence of oil seepage

  • Check pipe insulation is fitted and confirm condition

  • Check all flexible lines & capillaries for evidence of oil seepage

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Electrical Panels and Switch gear, control panels

  • Check the condition and functionality of all external illuminated indicators

  • Check all internal cable management including conduit, trunking and tray work

  • Check all bonding straps to all doors

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Electrical panels and switch gear, control panels

  • Check that electrical panel door isolator / interlock is functional

  • Check panel keys are present

  • Are electrical wiring diagrams present

  • Ensure panel fans are operational and clean internal panel filter

  • Check for signs of overheating or arcing on all internal panel components

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Condenser checks

  • Check the condition of the condenser fins for signs of corrosion (inclusive of support structures)

  • Remove all loose debris

  • Is a deep clean with pressure washer required to clean condensers?

  • If deep clean required please provide pre clean images

  • Prior to deep clean provide anemometer reading from face of coil

  • Apply appropriate chemical cleaner & flush with water

  • Ensure all condenser control circuits and contactors are functioning and fans are freely spinning including directional/rotation checks.

  • Visually inspect to ensure all condenser fan fixings are in place and secure

  • If using EC fan motors, ensure the fan speed is varying as required

  • Where multiple non EC fan motors are being used, ensure the motors are staging as required

  • Please provide images of condenser coil post clean

  • Please provide anemometer reading post clean from face of coil

  • Please grade condenser coil condition after works completed

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Display Cases, defrost heaters

  • Where fitted and if accessible check the operation of the defrost heaters

  • Check the control set points please refer to up to date compendium

  • Check all joints between cabinets where multiplexed check all end walls are sealed to the cabinet

  • Check all condensate drain components for leaks or blockages inside and underneath the cabinets

  • Ensure that all fixtures are visible on the store remote network

  • Ensure all earth bonding and straps are in place and secure.

  • Condition of electrical control box and components, including all cable management, conduit, trunking and tray work.

  • Check all doors functioning correctly, seals intact and self closing mechanisms functioning

  • Night blind functionality

  • Fixture lights functional

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Cold store

  • Where fitted, check the operation of the defrost heaters

  • Trace/drain line heaters, where fitted, check operation

  • Check the control set points match up to date compendium

  • Ensure that fixture alarms are visible and available on the stores remote networks

  • Check the condition of the electrical control box, components, cable management, trunking, tray work & conduit

  • Check doors and curtain condition and functionality

  • Check walls and ceiling panels and floors for any signs of wear or damage

  • Check the evaporator fins for any signs of damage/debris, ensure inspection end plates are fitted

  • Check evaporator fans are functioning check correct rotation

  • Ensure that all entrapment alarms are functional.

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Temperature alarm panels

  • Check temp alarm panels can see all connected fixtures

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Store heating (freeheat packs)

  • Indoor unit air filter, check & clean

  • Check the condensate away system for blockage or dirt

  • Indoor unit - heat exchanger and refrigeration connections, check for contamination. Clean as necessary

  • Controllers - check operation

  • Indoor unit fan & motor. Running noise, check for abnormal noise. Clean fan

  • Electrical - check tightness of terminals, tighten as necessary. Check correct operation of all switches and interlocks

  • Supply details of any faults/defects found

  • Supply images of faults/defects identified

Additional information

  • Please list any additional information supporting these PPM checks, any restrictions preventing a full completion & any H&S issues requiring urgent attention

  • Are remedial works required

  • Please list remedial work order numbers

Sign off

  • Managers full name

  • Managers signature

  • Date

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.