Switch Board Inspection & Test
Visual Inspection prior to energisation. Please add photos to each question where practicable.
-
Inspect switchboard for damage. Is switchboard in good condition?
-
Please describe issue. Add photos
-
Are all escutcheons/covers present and in good condition?
-
Please describe issue. Add photos.
-
Is there adequete protection to ensure live parts cannot be accessed through covers/escutcheons
-
Please describe issue. Add photos.
-
Has there been any changes to the switch board since last tested?
-
Please describe issue. Add photos.
-
Are all cable connections correct? Right locations? Correct phasing?
-
Please describe issue. Add photos.
-
Is the switch board fit for energisation?
-
Please describe issue. Add photos.
Testing
-
Meter used in tests. Add photo of meter and calibration cert/sticker
Measure voltage at SPD. Ensure all CBs, Main Switch and outgoing circuits are in the Off position before testing. Please investigate any abnormal readings.
-
Neutral -Earth
-
Red - Earth
-
Red - Neutral
-
Red - White
-
Red - Blue
-
White - Earth
-
White - Neutral
-
White - Blue
-
Blue - Earth
-
Blue - Neutral
Phase Rotation tests measured at SPD
-
Phase rotation correct?
-
Please describe issue
Turn on SPD, conduct visual inspection
-
Does WP meter come on?
-
Please describe issue
Turn on Consumer Main Switch, conduct visual inspection
-
Does REM Live Indicator come on? All lights working?
-
Please describe issue
Measure voltage at line side of Main CBs. Ensure SPD and Main Switch are on, all other CBs off. Test
-
Please identify the CB under test
-
Neutral - Earth
-
Red - Earth
-
Red - Neutral
-
Red - White
-
Red - Blue
-
White - Earth
-
White - Neutral
-
White - Blue
-
Blue - Earth
-
Blue - Neutral
-
Phase rotation correct?
-
Please describe issue
Measure voltage at line side of RCDs & Small CBs. Turn on Light & Small Power Main CB. Ensure all RCDs and small CBs are turned off. Please investigate any abnormal readings. Test
-
Please identify the CB under test
-
Neutral-Earth
-
Active -Earth
-
Active - Neutral
RCD tests. Verify that all external devices are either switched off or plugged out as appropriate. Turn on Light & Small Power Main CB. Turn on all RCDs. Please investigate any abnormal readings. Test
-
Please identify the CB under test.
-
Record make, and model of RCD. Add a photo.
-
Overcurrent rating and type of RCD (e.g.: C16, B10, D20, etc)
-
Residual trip current in mA
-
Fault rating in kA
-
Does the RCD operate when the manual trip button is pressed?
-
Please describe issue
-
RCD trip time at 0 deg in milli seconds
-
RCD trip time at 180 deg in milli seconds
-
Verify isolation of all poles after RCD operates
Circuit Breaker Settings. Verify settings with client engineer.
-
Red Phase - Test fault loop impedence at SPD. Add photo of test result
-
Red Phase - Record Prospective Short Circuit current from last test. Add photo of test result
-
White Phase - Test fault loop impedence at SPD. Add photo of test result
-
White Phase - Record Prospective Short Circuit current from last test. Add photo of test result
-
Blue Phase - Test fault loop impedence at SPD. Add photo of test result
-
Blue Phase - Record Prospective Short Circuit current from last test. Add photo of test result
-
Q1 current setting
-
Does Customer SPD grade with Western Power's upstream protection as noted on Western Power's SLD?
-
Verify that Short circuit/Instantaneous setting of Q1 is set lower than value of Prospective Short Circuit value as per our test results
-
Seal settings window of Q1 using copper strand and a bootlace. Set phone to datestamp and add photo of sealed settings
-
Q2 current setting
-
Q3 current setting
-
Q4 current setting (if applicable)
Close out. Leave all outgoing CBs in off position until ready to energise final circuits
-
Comments (tagged, locked out, etc). Please note any works that are incomplete out in the field and ensure relevant CBs are locked/tagged out.
-
Electrical Licence Number
-
Sign off