Title Page
-
Conducted on
-
Store name/Number
-
Auditor
Site audit
Pack HT/DT1
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT/DT2
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT3
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT4
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT5
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT6
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT7
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT8
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT9
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT10
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT11
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack HT12
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT1
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT2
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT3
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT4
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT5
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT6
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT7
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT8
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT9
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT10
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT11
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Pack LT12
-
Gas type/charge with pack label detail recorded
-
Is the extract fan working?
-
Are inverter filters clean and clear?
-
Confirm leak detection in pack is present and in working condition
-
Is the main pack controller in control and working?
-
Are the main pack settings correct?
-
Is the backup controller working?
-
Are the backup control settings correct to Tesco spec?
-
Check condition of oil in compressors,is it clear and have a sight glass?
-
Confirm level in oil separator
-
Are the pressure switches set correctly?
-
Are the PRV's in date and tagged?
-
Is there a refrigerant level in receiver? 20% as a guide.
-
Comperssor functionality, are all compressors in service?
-
Is the vapour/liquid injection system working?
-
Is there any signs of wear on rota locks?
-
Is the condenser/gas cooler clean and in good state of repair?
-
Are all condenser fans working and rotating in correct direction?
Chiller coldrooms
-
Are all evaporator fans working?
-
Are evaporators clear from ice?
-
Are evaporators clean and damage free?
-
Are drains clear from debris?
-
If fitted; are drain pumps clean and functioning?
-
Are all sensors reading?
-
If fitted are heaters working?
-
Confirm fabric of coolroom is in good condition
Frozen coldrooms
-
Are all evaporator fans working?
-
Are evaporators clear from ice?
-
Are evaporators clean and damage free?
-
Are drains clear from debris?
-
If fitted; are drain pumps clean and functioning?
-
Are all sensors reading?
-
Are defrost heaters working?
-
Confirm fabric of coolroom is in good condition
-
Is floor heating working and floor condition good?
Panel services
-
Are cabinet panels working?
-
Are there any cabinets showing offline?
-
Are the cabinet set points to the Tesco spec?
-
Is the leak detection panel online and working?
Design/Build
-
Is there any design or build issues on refrigeration plant?
-
Are condensers/gas coolers located in a shade spot on roof?
-
Do condensers/gas coolers have correct airflow around and obstruction free?
-
Are there any gas bottles on site? if so record bottle numbers