Title Page

  • Conducted on

  • Prepared by

  • Location

Site audit

Pack HT/DT1

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT/DT2

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT/DT3

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT/DT4

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT5

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT6

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT7

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT8

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT9

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT10

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT11

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack HT12

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT1

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT2

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT3

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT4

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT5

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT6

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT7

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT8

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT9

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT10

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT11

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Pack LT12

  • Gas type/charge with pack label detail recorded

  • Is the pack label PD compliant?

  • Is the isolator fully functional and interlocking?

  • Check isolator terminal shields are present

  • Pack housing condition

  • Is the extract fan working?

  • Are inverter filters clean and clear?

  • Confirm leak detection in pack is present and in working condition

  • Is the main pack controller in control and working?

  • Are the main pack settings correct?

  • Is the backup controller working?

  • Are the backup control settings correct to Tesco spec?

  • Are all sensors working on pack controls?

  • Check condition of oil in compressors,is it clear and have a sight glass?

  • Confirm level in oil separator

  • Are the pressure switches set correctly?

  • Have the liquid driers been changed,with proof?

  • Is the pressure vessel/receiver in good repair with no signs of rust?

  • Are the PRV's in date and tagged?

  • Is the PRV attached to a vent line?

  • Is there a refrigerant level in receiver? 20% as a guide.

  • Comperssor functionality, are all compressors in service?

  • Is the vapour/liquid injection system working?

  • Is there any low level alarms? are level sensors in place?

  • Are all compressor overloads/contactors in good state of repair?

  • Is the vapour/liquid injection system working?

  • Is there any obvious vibration issues with pipework?

  • Is there any signs of wear on rota locks?

  • Is the condenser/gas cooler clean and in good state of repair?

  • Are all condenser fans working and rotating in correct direction?

Chiller coldrooms

  • Are all evaporator fans working?

  • Are evaporators clear from ice?

  • Are evaporators clean and damage free?

  • Are drains clear from debris?

  • If fitted; are drain pumps clean and functioning?

  • Are all sensors reading?

  • If fitted are heaters working?

  • Confirm fabric of coolroom is in good condition

Frozen coldrooms

  • Are all evaporator fans working?

  • Are evaporators clear from ice?

  • Are evaporators clean and damage free?

  • Are drains clear from debris?

  • If fitted; are drain pumps clean and functioning?

  • Are all sensors reading?

  • Are defrost heaters working?

  • Confirm fabric of coolroom is in good condition

  • Is floor heating working and floor condition good?

Panel services

  • Are cabinet panels working?

  • Are there any cabinets showing offline?

  • Are the cabinet set points to the Tesco spec?

  • Is the leak detection panel online and working?

Shop floor Produce

  • Are dividers present between mods?

  • Have night blinds been fitted?

  • If fitted, are night blinds functional?

  • Are honeycombs present and clean?

  • Are drains clear from water and flowing as should?

  • If fitted; Are doors/hinges in good repair?

  • Are back panels damage free and in place?

Shop floor Fresh

  • Are dividers present between mods?

  • Have night blinds been fitted?

  • If fitted, are night blinds functional?

  • Are honeycombs present and clean?

  • Are drains clear from water and flowing as should?

  • If fitted; Are doors/hinges in good repair?

  • Are back panels damage free and in place?

Shop floor Frozen

  • Are dividers present between mods?

  • Are honeycombs present and clean?

  • Are drains clear from water and flowing as should?

  • If fitted; Are doors/hinges in good repair?

  • Check trim heaters are not exposed and are working correctly

HVAC

  • Is the stores HVAC equipment (AHU,AC) working?

  • Record level of humidity and temperature of shop floor

Design/Build

  • Is there any design or build issues on refrigeration plant?

  • Is there any design or build issues with shop floor cabinets?

  • Are condensers/gas coolers located in a shade spot on roof?

  • Do condensers/gas coolers have correct airflow around and obstruction free?

  • Are there any gas bottles on site? if so record bottle numbers

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.