Title Page
-
Project Name
-
Job Number
-
Date
-
Prepared by
-
Position Title
-
Location
-
DB Name
Pre Outage Inspection
Pre-Outage Distribution Board
-
Pre-Outage CB No. where DB is fed from
-
Pre-Outage CB Current Rating
-
Pre-Outage Cable Size
-
Pre-Outage Earth Cable size
-
Photos
Pre-Outage DB Energised
-
Pre-Outage 10 Point Voltage Test: Record any out of the ordinary results. Record Neutral to Earth Voltage. Record one Phase to Neutral, Phase to Earth and Phase to Phase result for reference.
-
VT1 - Phase to Neutral
-
VT2 - Phase to Earth
-
VT3 - Phase to Phase
-
VT1 - Neutral to Earth
-
Further investigation required
-
Pre-Outage Phase Rotation
-
Test Location: Energized Equipment Line side of Main Switch
-
Connection Method: Red, White, Blue leads on meter to match the Circuit Left to right (Not the cable colours)
-
Rotation test
-
Mark Rotation on the switchboard
-
Photo of the results
Pre-Outage DB De-energised
-
Ensure DB is isolated and LOTO procedures are in place
-
Pre-Outage Insulation Resistance
-
Complete a battery test on IR tester
-
Short IR tester leads to confirm working condition.
-
IR1 - A phase to B Phase
-
IR2 - A Phase to C Phase
-
IR3 - B Phase to C Phase
-
IR4 - A Phase to Neutral
-
IR5 - B Phase to Neutral
-
IR6 - C Phase to Neutral
-
IR7 - A Phase to Earth
-
IR8 - B Phase to Earth
-
IR9 - C Phase to Earth
-
IR10 - Neutral to Earth
-
IR Test Results
Comments and Photos
-
Comments
-
Photos
Post Outage Inspection
Post-Outage DB Inspection No.
-
Has DB label been updated
-
Post-Outage CB No. where DB is fed from
-
Post-Outage CB Current Rating
-
Have Submains been upgraded
-
Post-Outage Cable Size
-
Post-Outage Earth Cable size
-
Photos
Post-Outage DB De-energised
-
Earthing System
-
Note: The resistance of the main earthing conductor or any equipotential bonding conductor shall be not more than 0.5 Ohms.
-
Note: On multi board Installation tests are to be completed at the switchboard being Energised.
-
Type of Switchboard
-
EAR1 - MEN Point to Main Earth Stake
-
EAR2 - MEN Point to Earth Bar
-
EAR3 - Earth Bar to Equipotential Bond
-
EAR3 - Earth Bar to Equipotential Bond
-
EAR4 - Earth Bar to Neutral Bar (MEN Check)
-
Post-Outage Insulation Resistance
-
Complete a battery test on IR tester
-
Short IR tester leads to confirm working condition.
-
IR1 - A phase to B Phase
-
IR2 - A Phase to C Phase
-
IR3 - B Phase to C Phase
-
IR4 - A Phase to Neutral
-
IR5 - B Phase to Neutral
-
IR6 - C Phase to Neutral
-
IR7 - A Phase to Earth
-
IR8 - B Phase to Earth
-
IR9 - C Phase to Earth
-
IR10 - Neutral to Earth
-
IR Test Results
-
Post-Outage Polarity
-
Note: The polarity testing shall show that all active, neutral and protective earthing conductors in the electrical installation are correctly connected to the corresponding terminals of electrical equipment.
-
Note: Polarity tests are to be performed at the final connection location.
-
Note: Perform Polarity test by Shorting Phases & Neutral to Earth
-
Note: Disconnection the Neutral from the supply point Neutral bar
-
POL1 - A Phase to Earth
-
POL2 - B Phase to Earth
-
POL3 - C Phase to Earth
-
POL4 - Neutral to Earth
-
Note: Reconnect Neutral
-
Polarity Test Results
-
I am satisfied that the Pre-Energization test have meet the AS3000 requirements
Final Check List
-
SAFETY CHECK - This is HIGH RISK WORKS, Works to be executed carefully, follow the SWMS and safe work procedures and REMEMBER to treat All equipment as energized until proven "DEAD".
-
5.1 Do you have a copy of the Permit to energize.
-
5.3 Has the work areas been made safe with the correct exclusion zones put in place
-
5.7 Confirm Both ends are made safe and ready to energise
-
I have completed all the Final Checks and happy to procedure with Energization
-
Date and Time
Neutral ID
-
Disconnect Neutral at DB Neutral Bar
-
Set up Remote earth and connect Mutli-Meter between the Neutral Conductor and remote earth. Ensure the Connections are Made Safe
-
DO NOT CONNECT THE MULTI METER AFTER ENERGIZATION
-
Complete the Switching of the Equipment
-
Confirm the Voltage between the Remote Earth and the Neutral Conductor is 0V - add photo of results
- Pass
- Fail
-
Reverse the Switching and lock & tag out
-
Reconnect the Neutral - Test back to earth bar to confirm MEN
-
Complete the Switching of the Equipment - Proccedure to Part 7
-
STOP TEST Isolate and Redo Part 4 Test 3: Polarity
Post-Outage DB Energised
-
Switching has been completed and equipment ready for testing
-
Post-Outage 10 Point Voltage Test: Record any out of the ordinary results. Record Neutral to Earth Voltage. Record one Phase to Neutral, Phase to Earth and Phase to Phase result for reference.
-
VT1 - Phase to Neutral
-
VT2 - Phase to Earth
-
VT3 - Phase to Phase
-
VT1 - Neutral to Earth
-
Further investigation required
-
Post-Outage Phase Rotation
-
Test Location: Energized Equipment Line side of Main Switch
-
Connection Method: Red, White, Blue leads on meter to match the Circuit Left to right (Not the cable colours)
-
Rotation test
-
Does this match Pre-Outage Rotation
-
Isolate DB and roll 2 cables then re-test
-
Test Location: Energized Equipment Line side of Main Switch
-
Connection Method: Red, White, Blue leads on meter to match the Circuit Left to right (Not the cable colours)
-
Rotation test
-
Does this match Pre-Outage Rotation
-
Isolate DB and roll 2 cables then re-test
-
Photo of the results
Switchboard Load test
-
Do you have a connected load
-
Is the Connected Load a part of JLE SOW
-
No Further Testing required
-
Follow the ITP to complete the works and commissioning of the connected Load - refer back to check list when load is available for testing.
-
-
Once the connected Load is commissioned simulate a High Load demand for testing
-
Tong A phase
-
Tong B phase
-
Tong C phase
-
Tong Neutral
-
Have you taken photos of the result
-
Are the Phase currents within 10% of each other
-
I am satisfied that the Switchboard load test have meet the AS3000 requirements
-
Select date
-
Confirm the ITC's have been completed for the connected load and commissioning is completed
-
Simulate a High Load demand for testing Switch board loading
-
Tong A phase
-
Tong B phase
-
Tong C phase
-
Tong Neutral
-
Have you taken photos of the result
-
Are the Phase currents within 10% of each other
-
I am satisfied that the Switchboard load test have meet the AS3000 requirements
-
Select date