  • Date Of Inspection

  • Substation Name

  • Location
  • Inspectors Name

General

  • General Condition

  • Substation Access - confirm Dual Locking Arrangement

  • Site Access - 24/7 access available

  • S/S Security - UKPD /DNO locks fitted?

  • S/S Ventilation - Louvers Clear and Unobstructed

  • S/S Nameplate / Property Plate - UKPD / DNO Plates fitted? (Same site Name) + 1 x inside <br>S/S<br>

  • S/S Danger of Death Notices - Notices fitted on all approachable S/S faces?

  • S/S Door Ironmongery - Correctly applied – door stays, drop bolts etc

  • AC Supply Connected - Lighting & Power for indoor S/S & Some GRP’s (depends upon DNO)

  • Housing Watertight - Check for water ingress? GRP housing

  • Site Responsibility Schedule Available - Plan affixed to S/S internal wall - UKPN only

HV Switchgear - (UKPD owned HV Systems only)

  • General Condition

  • SF6 Gas Pressure - Check SF6 Pressure Gauge?

  • Switchgear Locks applied - UKPD padlocks fitted?

  • Engraved Circuit Labels - Photograph required – Photograph of RH SW Label, LH Sw Label and CB Label

HV Switchgear <br>(UKPD owned HV Plant only)

  • Relay setting sheet - on site?

  • Earth connections complete

  • Paint Condition

  • Plant Details - Photograph of rating plate required

  • Earth Fault Indicator Fitted - RH or LH SW? Reset : Man / Elec Photograph Required

Transformer

  • General Condition

  • Oil Level (Sight glass)

  • Off Load Tap changer - Tap Position

  • UKPD Switchgear Gear Locks applied - Applied to Tap changer, Voltage selector (dual Voltage)?

  • Earth Connections Complete - Check for tightness.

  • HV and LV Flange Inspection - Check for Oil Leaks RMU & LV cabinet to Transformer

  • Rating Plate Details - Photograph Required

Substation Earthing

  • Earth Bars & Earth cables

  • Neutral Earth Connection

  • Substation Bonding - Metal Doors, Louvers (Flexibles), cable tray, trunking etc

LV Cabinet, LV Boards

  • General Condition

  • Engraved circuit Destinations labels fitted - LV fuse ways, LV paralleled ways, MCCB’s and ACB’s- Photograph required

  • LV Ways Numbered (L to R) - Fit yellow numbers if no way numbers identified on the engraved labels

  • MDI Ratio & Reading - i.e. 800/1600/5?

  • LV Cabinet Earthing

  • SW Gear Locks Applied - Check UKPD SW Gear locks Applied – LV cabinet door, LV Links, metering Multicore marshalling cabinet.

MCCB / ACB

  • General Condition

  • Engraved Circuit Destinations Fitted

  • Reset Locking Bar Locked - UKPD SW Gear Lock applied

  • MCCB / ACB Protection Setting Sheet - On site

HV Cables (UKPD Owned HV Systems Only)

  • General Condition

  • HV Cable Boxes - Checked secure (all fixings applied (Nuts & Bolts)

  • HV Bending Radii - checked ok

  • HV Trenches - Open?

LV Cables

  • General Condition

  • LV Bending Radii - Checked ok

  • LV Trenches - Open?

MDI Readings

  • CT Ratio

  • L1

  • L2

  • L3

  • General Comments

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.