Information
-
Job Number:
-
Property Address:
-
Conducted on
-
Prepared by
-
Electrical Licence:
Switchboard
-
Cleanliness - Switchboard is clean & free from debris?
-
Please clean switchboard.
-
Why could this not be completed?
-
Damage - Switchboard is free from damage?
-
What is wrong with the Switchboard?
-
Does Switchboard need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Main Earth - Main earth cable is the correct size, connected properly and undamaged?
-
What is wrong with the Main Earthing cable?
-
Main Earthing MUST be rectified immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Main Earth Electrode - Main electrode is damage free, correctly installed, connection is solid and galvanised, MEC tag installed?
-
What is wrong with the Main Earth Electrode?
-
Main Earth Electrode MUST be rectified immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
M.E.N Link - M.E.N link is installed, the correct size (fused or unfused mains), Damage free?
-
What is wrong with the M.E.N link?
-
M.E.N link MUST be rectified Immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Equipotential bonding - All extraneous metal parts have an Equipotential bond with the correct size Earth cable?
-
What is wrong with Equipotential Bonding?
-
Equipotential Bond MUST be rectified Immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Metering Service Link - Is Service Link Installed.
-
Meters - Are meters installed correctly as per QEMM?
-
What is wrong with the metering?
-
Main Neutral - Main Neutral is the correct size, installed correctly and free from damage?
-
What is wrong with the Main Neutral?
-
Main Neutral MUST be rectified Immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Neutral Bar - Neutral Bar is installed in accordance with AS3000:2018 and free from damage?
-
What is wrong with the Neutral Bar?
-
Neutral Bar MUST be rectified Immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Protective devices - Protective devices are installed as per AS3000:2018, design is correct, in safe condition, and RCBO's installed where mandatory?
-
What is wrong with the protection devices?
-
Do any protective devices need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Cables - Are all cables installed in compliance with Ib<In<Iz, free from damage and protected?
-
What is wrong with the cabling?
-
Does the cabling need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Circuit Segregation - Are circuits correctly segregated? Kitchen and Laundry on separate ccts? No shared neutrals?
-
What is wrong with the segregation of the circuits?
-
Do the circuits need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Schematic - Does the switchboard have an up-to-date Schematic?
-
Legend - Does the switchboard have an up-to-date Legend?
-
Labels - Is the switchboard labelled correctly?
-
Please label board correctly.
External
-
All metal parts are equipotential bonded in compliance with AS3000:2018?
-
What is wrong with the Equipotential bonding?
-
Equipotential Bonding MUST be rectified Immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
External Power Outlets - All external outlets are operational and free from damage?
-
What is wrong with the External Power Outlets?
-
Do the External Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
External Lighting - All external lighting is operational and free from damage?
-
What is wrong with the External Lighting?
-
Does the External Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Swimming Pool - Is the swimming pool area electrically safe?
-
What is unsafe about the DAMP area?
-
Does the area need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Solar - Is the Solar Installation safe?
-
What is unsafe about the Solar Installation?
-
Does the area need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Entrance
-
Power Outlets - All outlets are operational and free from damage?
-
What is wrong with the Power Outlets?
-
Do the Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Lighting - All lighting and switches are operational and free from damage?
-
What is wrong with the Lighting?
-
Does the Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Living room area
-
Power Outlets - All outlets are operational and free from damage?
-
What is wrong with the Power Outlets?
-
Do the Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Lighting - All lighting and switches are operational and free from damage?
-
What is wrong with the Lighting?
-
Does the Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Fans - All fans are operational and free from damage?
-
What is wrong with the Fans?
-
Do the Fans need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Air Conditioner - A/C is operational and free from damage?
-
What is wrong with the A/C?
-
Does the A/C need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Kitchen
-
Power Outlets - All outlets are operational and free from damage?
-
What is wrong with the Power Outlets?
-
Do the Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Lighting - All lighting and switches are operational and free from damage?
-
What is wrong with the Lighting?
-
Does the Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Isolator - Is Isolator for HOB correctly installed in compliance with AS3000:2018, operational and free from damage?
-
What is wrong with the Isolation for the HOB cct?
-
Does the HOB cct need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Laundry
-
Power Outlets - All outlets are operational and free from damage?
-
What is wrong with the Power Outlets?
-
Do the Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Lighting - All lighting and switches are operational and free from damage?
-
What is wrong with the Lighting?
-
Does the Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Bedroom
-
Power Outlets - All outlets are operational and free from damage?
-
What is wrong with the Power Outlets?
-
Do the Power Outlets need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Lighting - All lighting and switches are operational and free from damage?
-
What is wrong with the Lighting?
-
Does the Lighting need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Fans - All fans are operational and free from damage?
-
What is wrong with the Fans?
-
Do the Fans need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Air Conditioner - A/C is operational and free from damage?
-
What is wrong with the A/C?
-
Does the A/C need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Bathroom
-
Are all power outlets installed in the correct locations away from wet areas?
-
Is exhaust fan and lighting installed in the correct location away from wet areas?
-
Are there any other electrical non-conformities noticed?
-
Does any immediate rectification works need to be undertaken?
-
Undertake rectification works as necessary
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
Other
-
Other Areas - Garages, Sheds etc. - Are other areas Electrically Safe and in compliance with AS3000:2018?
-
What is the area and what is wrong?
-
Does problem need immediate rectification?
-
Undertake rectification works as necessary.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified and power isolated until rectified. Is it safe to leave site?
-
Audit to be paused until safe.
-
Smoke Alarms - Are smoke alarms installed and compliant with the current Fire Regulations?
-
What is wrong with the Smoke Alarms?
-
Smoke Alarms MUST be rectified immediately.
-
Why could this not be completed?
-
Electrical Manager & Client MUST be notified. Is it safe to leave site?
-
Audit to be paused until safe.
-
All Electrical Installations are safe and installed as per AS3000:2018
-
Follow up jobs to be created and followed up.
-
Signature