Information

Bi-Monthly inspection form

  • Substation

  • Checked by

  • Date

Battery System

Battery charger

  • Current

  • Voltage

  • If below 124 V or above 135 V report to system operator

Battery

  • Water level between the high and low lines (if not, identify the cell number and water level)

Transformers

Is transformer oil level visible

  • AT-1

  • AT-2

  • T-2

Is transformer bushing oil level visible

  • AT-1

  • AT-2

  • T-2

Does transformer main tank have pressure

  • T-2

Are all fans working properly

  • AT-1

  • AT-2

  • T-2

Run tap charger 4 steps above and below present position, return too automatic. Does TC operate properly? (if TC is not found in auto, check with sys. Op. Before operating)

  • T-2

Circuit Breaker

Are circuit breaker tank oil levels visible

  • 8680

  • 130

  • 7510

  • 7530

  • 7540

  • 7550

  • 7560

  • 7570

  • 7518

  • 3220

  • 2248-40

Is circuit breaker bushing oil levels visible

  • 8680

  • 130

  • 7510

  • 7530

  • 7540

  • 7550

  • 7560

  • 7570

  • 7518

  • 3220

A are circuit breaker air compressors working properly (open draincock, drain moisture, insure draincock is closed and comp. stops)?

  • 7518

  • 130

  • CAP. Banks 7518 & 70 contain PCB's. Check for leaks an initial here.

Circuit Switchers

Are circuit switcher needles in upper yellow are of gauge

  • M-CS3

  • M-CS4

Miscellaneous

Miscellaneous

  • Has fire extinguisher been checked and card initialed

  • Have breaker operations and targets been checked

  • Is a good switch stick and can on hand

  • Is a complete set of fuses on hand

  • Has annunciator Ben tested

  • Has control house thermostat been set to 60 degrees

  • Is telephone operating properly

  • Is operating diagram properly posted in house or bkr. Cabinet?

  • Is site plan and asbestos guideline posted in control house

Items condition

General condition of the following items (paint, rust, leaks, breaks, etc.)

  • Transformers

  • Circuit breakers

  • Circuit switches

  • Lighting arresters

  • Insulators

  • PT's and CT's

  • Station service pots

  • Switches

  • Switch numbers

  • Structures

  • Flood lights

  • Fences, gates, locks

  • Yard

Concluding questions

  • Remarks

  • SUPV of resources

  • Date

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.