Title Page
-
Building being audited:
-
Building Address:
-
Date of Audit:
-
Auditee:
-
Auditor:
Section 1 - Opening Meeting
Introductions and format of the audit
-
Introductions:
H&S Team
Site Team -
The purpose of this audit is to ensure that the Building Custodian and Corporate Landlord are meeting their statutory requirements with regards to statutory inspections and building maintenance.
-
Who has got overall responsibility for the building.
-
The audit is split into specific sections as follows:
Building Custodian
Corporate Landlord
The Building Custodian will be required to facilitate a site inspection and to answer questions and provide documentary evidence on areas of compliance.
A thorough inspection of Weblog will be used to check that Corporate Landlord responsibilities are being met.
General Information
-
Name of Building Custodian?
-
Name of Site Manager/Caretaker?
-
Building function?
-
Total number of staff working in the building?
-
Approximate age of the building?
General Notes
Section 2 - Building Custodian
Section 1 - Regulatory Reform (Fire Safety) Order
-
1.1 - Is there evidence that Fire Evacuation Drills are carried out every 6 months?
-
1.2 - Is there evidence that annual briefing sessions are held with Fire Marshals?
-
1.3 - Is there evidence that Fire Safety records are being kept on a weekly basis?
Section 2 - Means of Escape
-
2.1 - Is there evidence that Means of Escape are being checked on a daily basis?
Section 3 - Asbestos
-
3 - Is there any Asbestos on site?
-
3.1 - Is there evidence that Asbestos Containing Materials are checked monthly?
-
3.2 - Are all contractors informed of the location of asbestos containing materials prior to starting work?
Section 4 - Management of Health & Safety at Work Regulations
-
4.1 - Is there evidence that an annual audit of significant building related risks is carried out?
-
4.2 - Is there evidence that daily checks of significant building related risks are carried out?
Section 5 - Construction Design & Management Regulations
-
5.1 - Is there evidence that Corporate Landlord is notified in advance of all building maintenance work being carried out?
-
5.2 - Is there evidence that purchase orders for building maintenance work are checked before work is allowed to commence?
-
5.3 - Is there evidence that risk assessments and method statements for all building maintenance work are approved before work commences?
Section 6 - Health & Safety (First Aid) Regulations
-
6.1 - Is there evidence that an annual review of First Aid provision is carried out?
-
6.2 - Is there evidence that regular checks of First Aid Equipment is carried out?
Section 7 - Portable electrical equipment testing (PAT)
-
7.1 - Is there evidence that a complete inventory of all Portable Electrical Equipment carried out annually?
-
7.2 - Is there any evidence that Personal Electrical Equipment is in use within the building?
Section 8 - Emergency Lighting
-
8.1 - Is there evidence that monthly testing of Emergency Lighting is being carried out?
Section 9 - Fire Alarm System
-
9.1 - Is there evidence that weekly testing of the Fire Alarm system is being carried out?
Section 10 - Fire Fighting Equipment
-
10.1 - Is there evidence that weekly visual inspections of the Fire Fighting Equipment is being carried out?
-
10.2 - Is there evidence that monthly visual inspections of Evac Chairs is being carried out?
Section 11 - Legionella
-
11.1 - Is there evidence that monthly Thermal Disinfection tests are being carried out?
-
11.2 - Is there evidence that weekly flushing of Infrequently used outlets is being carried out?
Section 12 - Oil Storage Tanks
-
12 - Are there any Oil Storage Tanks on site?
-
12.1 - Is there evidence that weekly inspections of Oil Storage Tanks, Bunds, Pipework an surrounding areas is being carried out?
Section 13 - Responsible Person
-
13.1 - Is there evidence that a 6 monthly review of Responsible Named Persons is carried out?
Section 14 - External Areas
-
14.1 - Is there evidence that daily inspections of External Areas are being carried out?
Section 15 - Alarm Systems
-
15.1 - Is there evidence that regular testing of the Disabled Toilet Alarm system is being carried out?
-
15.2 - Is there evidence that regular testing of the Emergency Call system is being carried out?
-
15.3 - Is there evidence that regular testing of the Emergency Panic Alarm system is being carried out?
-
15.4 - Is there evidence that daily testing of the Intruder Alarm system is being carried out?
Section 16 - External Lighting
-
16.1 - Is there evidence that monthly inspections of the External Lighting is being carried out?
Section 17 - Sprinkler System
-
17 - Is a Sprinkler System fitted within the building?
-
17.1 - Is there evidence that weekly testing of the Sprinkler System is being carried out?
Section 18 - Ladders
-
18.1 - Is there evidence that monthly inspections of the Ladders is being carried out?
Section 19 - Meter Readings
-
19.1 - Is there evidence that monthly Electricity Meter Readings are being taken?
-
19.2 - Is there evidence that monthly Gas Meter Readings are being taken?
-
19.3 - Is there evidence that monthly Water Meter Readings are being taken?
Section 20 - Serious health and safety issues identified during physical site visit
-
20.1 - Have any other serious health & safety issues been identified during the physical site inspection?
Section 3 - Corporate Landlord
Section 21 - Regulatory Reform (Fire Safety) Order
-
21.1 - Is there a copy of the current Fire Risk Assessment?
-
21.2 - Is there evidence that an annual review of the Fire Risk Assessment has been carried out?
Section 22 - Asbestos
-
22 - Is there any Asbestos on site?
-
22.1 - Does the building have an Asbestos Risk Assessment?
-
22.2 - Is there evidence that an annual review of the Asbestos Risk Assessment has been carried out?
-
22.3 - Does the building have an Asbestos Management plan?
-
22.4 - Is there evidence that an annual review of the Asbestos Management plan has been carried out?
-
22.5 - Have all actions identified in the Asbestos Management Plan review been completed?
Section 23 - Air Conditioning
-
23 - Are there any Air Conditioning units on site?
-
23.1 - Is there evidence that Servicing and F Gas checks of Air Conditioning equipment is carried out every 6 months?
Section 24 - Mixing Valves
-
24.1 - Is there evidence that annual servicing of Mixing Valves is carried out?
Section 25 - Automatic Door/Gates/Barriers
-
25 - Are there any Automatic Doors/Gates/Barriers on site?
-
25.1 - Is there evidence that servicing of Automatic Doors/Gates/Barriers is carried out every 6 months?
Section 26 - Gas
-
26.1 - Is there evidence that servicing of Gas Fired Boilers/Equipment is carried out every 6/12 months?
-
26.2 - Is there evidence that 5 yearly testing (annual testing for Catering/Residential) of Gas systems is carried out?
Section 27 - Catering Equipment
-
27 - Is there any catering equipment on site?
-
27.1 - Is there evidence that servicing of Gas Catering Equipment is carried out annually?
-
27.2 - Is there evidence that servicing of Electrical Catering Equipment is carried out annually?
-
27.3 - Is there evidence that cleaning, sterilising and testing of Extraction Fan/Canopy is carried out every 6/12 months?
Section 28 - Lightning Conductors
-
28 - Does the building have a Lightning Conductor?
-
28.1 - Is there evidence that annual visual inspection of Lightning Conductors is carried out?
-
28.2 - Is there evidence that 5 yearly testing of Lightning Conductors (as part of the Fixed Electrical Wiring) is carried out?
Section 29 - Fixed Electrical Wiring Installation
-
29.1 - Is there evidence that Periodic Inspection of Fixed Electrical Wiring Installations are carried out every 5 years (3 Years for Residential Premises)?
Section 30 - Portable electrical equipment testing (PAT)
-
30.1 - Is there evidence that annual testing of portable electrical equipment is carried out?
Section 31 - Emergency Lighting
-
31.1 - Is there evidence that an annual full discharge test of emergency lighting is being carried out?
Section 32 - Fire Alarm System
-
32.1 - Is there evidence that a 6 monthly inspection of the fire alarm system is being carried out?
Section 33 - Fire Fighting Equipment (Extinguishers/Sprinkler Systems/Dry & Wet Risers and Hose Reels)
-
33.1 - Is there evidence that an annual equipment certificate is issued for all fire fighting equipment?
-
33.2 - Is there evidence that a 5 yearly full discharge test of fire fighting equipment is carried out?
Section 34 - Hazardous Waste
-
34.1 - Is there evidence that an annual permit check is carried out?
-
34.2 - Is there evidence that consignment notes are received and recorded for each waste transfer?
Section 35 - Emergency Drills for High Risk sites
-
35 - Is this site deemed High Risk?
-
35.1 - Is there evidence that regular Emergency Drills are carried out for High Risk sites?
Section 36 - Lifts
-
36 - Are there any type of lifts on site?
-
36.1 - Is there evidence that monthly maintenance inspections of Passenger Lifts are being carried out?
-
36.2 - Is there evidence that 6 monthly insurance inspections of Passenger Lifts are being carried out?
-
36.3 - Is there evidence that 3 monthly maintenance inspections of Non-Passenger Lifts are being carried out?
-
36.4 - Is there evidence that annual insurance inspections of Non-Passenger Lifts are being carried out?
-
36.5 - Is there evidence that 5 yearly tests of safety gear on Non-Passenger Lifts is being carried out?
-
36.6 - Is there evidence that 6 monthly insurance inspections of Person Hoists (inc. slings) are being carried out?
-
36.4 - Is there evidence that annual insurance inspections of Non-Passenger Lifts are being carried out?
-
36.7 - Is there evidence that annual insurance inspections of Powered Stair Lifts are being carried out?
-
36.9 - Is there evidence that annual maintenance inspections of Powered Stair Lifts are being carried out?
Section 37 - Sewage/Water Treatment/Septic Tank and Oil Interceptors
-
37 - Are there any Sewage/Water Treatement/Septic Tanks on site?
-
37.1 - Is there evidence that tanks are being pumped out every 6 months?
-
37.2 - Is there evidence that annual servicing of lift pumps is being carried out?
Section 38 - Legionella
-
38.1 - Is there evidence that annual sampling of water supplies is being carried out?
-
38.2 - Is there evidence that annual chlorination of water supplies is being carried out?
-
38.3 - Is there evidence that 6 monthly water tank inspections are being carried out?
-
38.4 - Is there a water risk assessment available?
-
38.5 - Is there evidence that the water risk assessment is reviewed every 2 years?
Section 39 - Oil Storage Tanks
-
39 - Are there any Oil Storage Tanks on site?
-
39.1 - Is there evidence that annual inspections of oils storage tanks, bunds, pipework an surrounding areas are being carried out?
Section 40 - Permitting/Exemptions for Waste/Effluent/Air Emmisions
-
40 - Does the site hold permits/exemptions for Emmisions?
-
40.1 - Is the permit/exemption valid?
Section 41 - Petrol/Diesel Storage Tanks
-
41 - Are there any Petrol/Diesel storage tanks on site?
-
41.1 - Test??????
Section 42 - Energy Performance of Buildings
-
42.1 - Is there evidence that the annual Energy Performance of Building inspection has been carried out?
Section 4 - Physical Site Inspection
Carry out a physical site inspection to identify any serious Health & Safety issues, not identified elsewhere in the audit
-
Issue No.
-
Location:
-
Health & Safety Issue:
-
Photo of H&S Issue
-
Action required:
-
Responsible:
Section 5 - Closing Meeting
Summary of findings of audit
General Notes
Signatures
-
Building Representatives Signature
-
Auditors Signature