Title Page
-
Conducted on
-
Prepared by
-
Location
-
Asset tag in place?
-
Have you erected warning signage close to work area?
-
Have you manually test ventilation and siren overide?
-
Are all warning labels displayed on control panels?
-
Are all panel keys in place?
-
Are all electrical drawings and manuals are tidy and on side?
-
Is the interlock functioning correctly?
-
Is all metal work and sub circuits earthed?
-
Are all trunking covers on and tidy?
-
Using infrared thermometer are terminal temperatures under 40°?
-
Is mains incoming voltage and ampage correct across all phases?
-
Is the control voltage 24vdc?
-
Is the pack controller operational, staging compressors in/out and set points all fine?
-
Do all compressors run and overloads set 10% above full load amps?
-
Do all crankcase heaters work?
-
Do all housing fans work and are clean?
-
Are all inventors working to manufactures recommendations?
-
Are all compressor mounts and fixings are in place?
-
Have you tested oil using kit?
-
Have you tested for excessive pressure drop across coalescent oil separator and changed if needed?
-
Are all oil management systems working with oil level in them?
-
Is there the correct level of gas in the receiver?
-
Do the transducers work and read correct?
-
Have you changed liquid line filter?
-
Are the PRV's in date and leak free?
-
Have you checked the bursting disc (if fitted)?
-
Are all safety switches fitted and working with no sign of damage?
-
are all pressure vessels clear of corrosion and damage?
-
Is the insulation around pressure vessels and heat exchanger free of damage?
-
Is all pipework free from rubbing and damage?
-
Have you leak tested all components & pipework?
-
Are all temp probes in correct place and secure?
-
Have you carried out a pressure differential test across suction core drier?
-
All components and pipework clear of signs of ice build up?
-
Pack housing is free from damage inside and out?
-
Do all fans operate and set correctly?
-
Have the gas coolers been brushed prior to jet washing?
-
Have you locked off gas cooler fan?
-
Have you washed gas cooler via access point or by removing the fan?
-
Have you washed out all dirt and washed off the under side of coil?
-
Have you refitted all fans using manufactures recommendations for fixings and removed lock off?
-
Are all fins clear from damage and corrosion?
-
Have you removed debris from under gas cooler?
-
Have you closed all electrical panel doors and made sure isolators engaged?
-
Have you left pack bed clean, tidy and pack door shut?
-
Have you checked pipework is free from damage or leaks, pipe brackets and pipe supports are in place?
-
Have you removed warning signage?
-
Are all cases running to set points and communicating?
-
Have you checked battery status on front panel and replaced if needed?
-
Have all defects found been raised as a P3?
-
Confirm all of the above is correct.