Title Page
-
Conducted on
-
Prepared by
-
Location
-
Asset tag in place?
-
Have you erected warning signage close to work area?
-
Is there warning label displayed on control panel door?
-
Is isolator interlock working?
-
Are mains isolator terminal shields in place?
-
Using infrared thermometer are termal temperatures under 40°?
-
Confirm panel wiring has no signs of over heat damage
-
Are all panel fans, housing fans working and clear of debris?
-
Are all overloads and trips operational ?
-
Do all compressors run?
-
Are all run currents on compressors satisfactory?
-
Are all overloads set 10% above full load amps?
-
Is the crankcase heater operational?
-
(LT only)Have you changed battery on Emerson vapour injection module?
-
Are all compressors secure?
-
Are all rota locks tight and corrosion free?
-
(LT Pack) Is the liquid Injection operational with compressor running?
-
Is the pressure drop between suction core inlet/outlet fine? If not has it been changed?
-
Have you carried out oil test and changed oil if required?
-
Is pressure between inlet/outlet of oil separator less than 20psi if not P3 raised to replace?
-
Is oil level in trax and separator fine? If not have you replaced temprite?
-
Are all safety switches working And set correctly?
-
Are all pressure transducers reading correctly?
-
Have you tripped backup controller in and does it run? Reset after tested
-
Have you replaced drier cores,dated and are leak tight?
-
Have you checked liquid receiver for damage and corrosion and repaired if needed?
-
Are all PRVs in date and tagged? (5 years)
-
Is there liquid in receiver?
-
Are all condenser fans operational and secure?
-
Have you cleaned condenser and daylight visible through it?
-
Have you leak tested all components and pipework?
-
Have you cleaned rack, shut all doors and made sure canopy locks are secure?
-
Have you removed all warning signs from area?
-
Are all cases communicating and running to set point ?
-
Is battery on front end panel fine and has been replaced if not?
-
Are all integral condenser clean and fans working?
-
Have you cleaned click and collect/dot com condensers?
-
Have all defects been raised as P3's ?
-
Confirm all of above is correct.