GENERAL NOC

  • Air conditioning -check air conditioning switch at NOC wall

  • Lighting - report any switch damage and lamp fault

  • BMS (check CER temperature should be within 20-25 degree Celsius)<br>

  • Public address system - test all the button

  • CCTV system- report any signal lost and check time setting for each devices

  • Others- any abnormal not stated above

Corridor

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Meeting Room

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 1

  • FM200 Cylinder - check cylinder condition and pressure gauge

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

CER1

  • Lighting - report any sensor malfunction and lamp fault

  • Housekeeping

  • CRAC Unit conditions - report any alarm

  • PDU conditions - check display status and report any alarm

  • STS conditions - check display status and report any alarm

  • Others- any abnormal not stated above

CER2

  • Lighting - report any sensor malfunction and lamp fault

  • Housekeeping

  • CRAC Unit conditions - report any alarm

  • PDU conditions - check display status and report any alarm

  • STS conditions - check display status and report any alarm

  • Others- any abnormal not stated above

CER3

  • Lighting - report any sensor malfunction and lamp fault

  • Housekeeping

  • MDF - Cage should be locked

  • CRAC Unit conditions - report any alarm

  • PDU conditions - check display status and report any alarm

  • STS conditions - check display status and report any alarm

  • Others- any abnormal not stated above

Gas room 2

  • Fan coil unit - visual inspection on panel and perform function test

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 3

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Water pump room

  • Lighting - report any switch damage and lamp fault

  • ACWP / ACWT Panel status - check panel light and inspect pump condition.

  • FWP / FWT Panel status - check panel light and inspect pump condition

  • PWP / PWT Panel status- check panel light and inspect pump condition

  • Others- any abnormal not stated above

FS Control Room

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Fire Alarm Panel status - read status of panel and indication light<br>

  • Battery charger unit status

  • Others- any abnormal not stated above

UPS Room 1

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 2

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 3

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

PABX

  • Lighting - report any switch damage and lamp fault

  • FM200 system - check system time and function of control panel

  • Air conditioning - report to facility manager if room temperature abnormal

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 4

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 5

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

LV switch room

  • Lighting - report any switch damage and lamp fault

  • Air conditioning - report to facility manager if room temperature abnormal (around 20 to 26 degree Celsius)

  • UPS (70net) - read indicator status about sources, rectifier, battery and inverter

  • switch board - report if any alarm

  • FM200 system - check system time and function of control panel

  • Others- any abnormal not stated above

Gas room 6

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Fire services pump room

  • Lighting - report any switch damage and lamp fault

  • LMCP of EXF - visual inspection on panel and perform function test

  • Alarm module status

  • Others- any abnormal not stated above

Cable store G/F

  • Lighting - report any switch damage and lamp fault

  • Air conditioning - report to facility manager if room temperature abnormal (around 20 to 26 degree Celsius)

  • Housekeeping

G/F E&M Room (next to staircase)

  • Lighting - report any switch damage and lamp fault

  • Power supply status - report if any alarm

Passenger Lift

  • Lighting - report if any light fault

  • Certificate - check certificate should be in place and expiry date

  • Others- any abnormal not stated above

Staging Room

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Air conditioning - report to facility manager if room temperature abnormal (around 20 to 26 degree Celsius)

  • Others- any abnormal not stated above

Pre Action sprinkler control valve room 2

  • Lighting - report any switch damage and lamp fault

  • Pre Action System alarm module- report if any alarm

  • Pressure pump - inspect vibration and noise while pump on

  • Others- any abnormal not stated above

CER4

  • Lighting - report any sensor malfunction and lamp fault

  • Housekeeping

  • MDF - Cage should be locked

  • CRAC Unit conditions - report any alarm

  • PDU conditions - check display status and report any alarm

  • STS conditions - check display status and report any alarm

  • Others- any abnormal not stated above

E&M Room ( inside pre- action sprinkler room)

  • Lighting - report any sensor malfunction and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Battery - inspect battery shape, breakers and connector conditions

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Others- any abnormal not stated above

New E&M Room 1/F

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any sensor malfunction and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 8

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 9

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

UPS Room 6

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 7

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 8

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 9

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

1/F LV switch room A

  • Lighting - report any switch damage and lamp fault

  • Air conditioning - report to facility manager if room temperature abnormal

  • switch board - report if any alarm

  • Housekeeping

  • Others- any abnormal not stated above

1/F LV switch room B

  • Lighting - report any switch damage and lamp fault

  • Air conditioning - report to facility manager if room temperature abnormal

  • switch board - report if any alarm

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 10

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

Gas room 7

  • FM200 Cylinder - inspect pressure gauge and pipe connection

  • Lighting - report any switch damage and lamp fault

  • Housekeeping

  • Others- any abnormal not stated above

UPS Room 4

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

UPS Room 5

  • Lighting - report any switch damage and lamp fault

  • Fan coil unit - visual inspection on panel and perform function test

  • Air conditioning - report to facility manager if room temperature abnormal

  • FM200 system - check system time and function of control panel

  • Battery - inspect battery shape, breakers and connector conditions

  • UPS - read indicator status about sources, rectifier, battery and inverter

  • Water detection system - check system power indicator and alarms

  • UPS switch board - report if any alarm

  • Others- any abnormal not stated above

Outdoor facilities condition

  • Visual check on GEN A1 outdoor enclosure door <br>

  • Visual check on GEN A2 outdoor enclosure door <br>

  • Visual check on GEN A3 outdoor enclosure door <br>

  • Visual check on GEN A4 outdoor enclosure door <br>

  • Visual check on GEN A5 outdoor enclosure door <br>

  • Visual check on GEN B1 outdoor enclosure door <br>

  • Visual check on fuel pump room door<br>

  • Visual check on G/F chiller plant door<br>

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.