Information

  • Job Number and Name

  • Location
  • Building's Name and Level

  • System(s) Inspected

  • Conducted on

  • Inspected by

  • 210500.1 Common Work Result for Fire Suppression

  • 210513 Common Motor Requirements for Fire Suppression

  • 211313 Wet Pipe Sprinkler System

  • 211316 Dry Pipe Sprinkler System

  • 211316.A Pre-Action Sprinkler System

  • Document No.

Execution of Work

Hangers

  • Are hangers straight and plumb

  • Are hangers installed to manufacturer's guidelines

  • Proper spacing of hangers and supports for piping and independently supported?

  • Are hangers supporting pendent sprinkler heads within 12" of the end of the line

Pipe, Fittings and Valves

  • Is proper schedule of pipe being used?

  • Has all pipe been pressure/water tested?

  • Are joints and fittings properly installed

  • All valves and devices are accessible

  • All floor control valves are installed properly

  • Verify that indicating valve is working and in the correct position for system condition?

  • Drain line installed

  • Is pipe and fittings installed are free of foreign debris or corrision

  • No piping, wiring or duct is touching sprinkler pipe

  • Are all outlet capped and plugged at the end of shift?

  • Are all bolts torqued to manufacturer's guidelines?

Sprinkler Heads and Flexible Connections

  • Are the proper temperature rating sprinkler heads installed?

  • Are brackets attached to ceiling grid as per manufacturer's guidelines

  • Are sprinkler head guards installed properly

Design Installation

  • No sprinkler heads are further than 7'-6" or closer than 6" from walls

  • Sprinkler heads are spaced appropriately for the hazard

  • Sprinkler heads are installed under ductwork 4'-0" or greater

  • Mechanical rooms with ceilings lower than 8' above FF have sprinkler heads with guards?

Miscellaneous

  • Work area is clean and free debris (cut off rods, plastic plugs and caps)

  • Material and equipment have been cleaned (wipe off dust and dirt)

  • Is sprinkler system(s) installed as per drawings?

Comments

Material Deficiency

Installation Deficiency

Damaged Material

Additional Comments

  • Additional Pictures

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.