Information
-
Document No.
-
Company's Name
-
Company's Address (Street/Suite#/City/State/Zip)
-
Conducted on
-
Prepared by
-
Personnel
Information
Information
-
GFS Texas Order Number:
-
Date and Time
-
Report To:
-
Site Inspection's Address (Street/Suite/City/State/Zip)
-
Is the building occupied?
-
Has the Building Owner been notified?
-
Has the Fire Marshall been Notified? (If "No" does the FM need to notified to perform inspection)
-
Has the building's Security/Maintenance been notified of fire suppression system testing?
General Section (A) - To only be answered by the Owner or Owner's Representative
-
Is the Owner or Owner's Representative Present during inspection?
-
Name, Title and Signature
-
Have there been any changes in the occupancy classification or operation since last inspection?
-
Have there been any changes or repairs to the fire protection system since last inspection?
-
Has a fire occurred since last inspection?
-
Have damaged sprinkler components been replaced?
-
Are gravity, surface or pressure tanks protected from freezing?
-
Are the buildings areas protected by a wet system, heated, including the blind attic and perimeter areas, where accessible?
-
Have there been any irregularities in pump operation during weekly/monthly test? (If applicable)
-
Are any of the sprinkler heads 50 years old or older?
General Section (B)- to only be answered by Inspector
-
Does there appear to be proper clearance between the top of all storage and the sprinklers' deflectors?
-
Have the sprinkler systems been extended to all visible areas of the building?
-
Are all visible exterior opening protected against the entrance of cold air?
-
Have all fire pumps been tested to their full capacity through the use of hose streams or flow meter within the past 12 months?
-
What type of inspection has the Owner been performing on the fire suppression systems?
- Weekly
- Monthly
- Quaterly
- Semi-Annual
- Annual
- Third Year
- Fifth Year
- Special
- None
-
Are these inspection performed at normal intervals?
General Inspection
General Inspection Questions
City Connection
-
City Connection
Connection
-
What type of water supply
-
Other Type
Test Pipe
-
What is the test pipe connection?
-
What is the size of the test pipe? (inches)
-
Static pressure before (psi)
-
Flow Pressure (psi)
-
Static pressure after (psi)
Backflow
-
Title of Backflow
-
What type are the valves?
-
Are valves "Easily Accessible"?
-
Are signs visible and legible?
-
Are the valves open?
-
Are the valves secured?
-
Is the tamper operational?
-
Photo of Backflow
Select Type of Inspection
-
Any "No" answer, test failures or other problems found with the sprinkler system must be explained in each comment section provide with the question
-
Weekly Inspection
Weekly
-
Are the control valves supervised with seals in correct (open or closed) position
-
Are Backflow preventers valves in correct (open or closed) position?
-
Are Backflow preventers sealed, locked or supervised and accessible
-
If sprinklers have been replaced, were proper replacement used?
-
Monthly Inspection (in addition to previous inspection section)
Monthly
-
Are control valves with locks or electrical supervision in correct (open or closed) position?
-
Sprinkler wrench with spare sprinklers?
-
Gauges in good condition?
-
Are alarm valves: gauges show normal supply water pressure, free from physical damage, valves in correct (open or closed) position and no leakage from retarding chamber or drains?
-
Quarterly Inspection (in addition to previous inspection section)
Quarterly
-
Pressure reducing valves: in open position, not leaking, maintaining downstream pressure per design criteria and in good condition with handwheels not broken?
-
Are the hydraulic nameplates securely attached to risers and legible?
-
Fire Department connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and undamaged, gaskets in place and in good condition, identification sign(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly?
-
If plugs or caps are not in place on the Fire Department Connection, inspect interior for obstructions.
-
Alarm devices free from physical damage?
Testing
-
Mechanical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
-
Did post indicting valves open until spring or torsion is felt in the rod? (then closed back one quarter turn)
-
Semi-Annual Inspection (in addition to previous inspection section)
Semi-Annual
-
Valve supervisory switches indicate movement?
-
Electrical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
-
Annual Inspection (in addition to previous inspection section)
Annual
-
Proper number and type of spare sprinklers?
Visible sprinklers:
-
Free of corrosion and physical damage?
-
Free of obstructions to spray patterns?
-
Free of foreign materials including paint?
-
Liquid in all glass bulb sprinklers?
Visible pipe:
-
In good condition/no external corrosion?
-
No mechanical damage and no leaks?
-
Properly aligned and no external loads?
-
Are visible pipe hangers and seismic braces damaged or loose?
-
Does VISIBLE wet pipe have adequate heat?
-
Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branchline within the last five (5) years? (If not, conduct an internal inspection) Take Pictures
Testing
-
Are all sprinkler dated 1920 or later?
-
Fast response sprinkler 20 or more years old replaced or successfully sample tested within last 10 years?
-
Standard response sprinkler 50 or more years old replaced or successfully sample tested within last 10 years?
-
Standard response sprinkler 70 or more years old replaced or successfully sample tested within last 5 years?
-
Dry-type sprinklers replaced or successfully sample tested within last 10 years?
-
All control valves operated through full range and returned to normal position?
-
Backflow devices pass backflow test?
-
Backflow devices pass full flow test?
-
Pressure reducing valves passed partial flow test?
-
Fifth year inspection (in addition to previous inspection section)
Fifth year
-
Check valves internally inspected and all parts operate properly move freely and are in good condition?
Testing
-
Sprinkler rated above High temperature tested?
-
Gauges checked by calibrated gauge or replaced?
-
Pressure reducing valves passed full flow test?
-
Additional Photos
-
Additional Comments
Wet Pipe
Wet Pipe
-
Total Number of Wet Pipe Systems?
-
Wet Systems
Wet System
-
Title of System Riser
-
Photo of System Riser
-
Size of System Riser
-
System Riser Valve Information (Make/Model/Year)
-
Is the valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open? (if no, is it supposed to be closed?)
-
Is the valve secured?
-
Is the tamper operational?
-
What color tag was placed on riser after inspection? (If a Yellow or Red tag is select) What is the deficiency?
-
Does system use antifreeze solution?
-
Test Results?
-
Were the antifreeze test results satisfactory?
-
Type of valve (Make/Model/Year)
-
Valve size (inches)
-
Photo of Anti-Freeze Valve
-
1. Defective intake screen on pump with suction from open source.
2. Obstructive material discharged during waterflow tests.
3. Foreign materials found in dry-pipe valves, check valves or pumps.
4. Foreign material in water during drain test or plugging of inspector's test connection.
5. Plugging of pipe of sprinklers found during activation or alteration.
6. Failure to flush yard piping or surrounding public mains following new installation or repair.
7. Record of broken mains in the vicinity.
8. Abnormally frequent false-tripping of dry-pipe valve.
9. System is returned to service after extended period out of service (greater than 1 year).
10. There is reason to believe the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe systems. -
If any of the above items were discovered, was an obstruction investigation conducted?
-
If conditions were found that required flushing, was flushing of system conducted?
Alarms
-
Did the water motor gong operate during testing?
-
Did the electrical alarms operate during testing?
-
Did the supervisory alarms operate during testing?
-
Was the water flow alarm indicator and retard test satifactory?
-
What was the time (seconds)
General Wet-Pipe Inspection
-
Gauges of wet-pipe system showing normal water supply?
-
Alarm Valves: gauges show normal supply water pressure, free from physical damage, valves in correct (open or closed) position and no leakage from retarding chamber or drains?
-
Is this any Annual Inspection or Quarterly Inspection?
Main drain test
-
Record Static Pressure (psi)
-
Record Residual Pressure (psi)
-
Are results comparable to previous test?
-
Was flow observed?
Dry System
6. Dry System
-
Total number of Dry systems
-
Add Dry System
Dry System
-
Title of system riser
-
Photos of system riser
-
System Riser Valve Information (Make/Model/Year)
-
System Riser Size
-
Is the valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open? (if no, is it supposed to be closed?)
-
Is the valve secured?
-
Is the tamper operational?
-
What color tag was placed on the riser after inspection? (If a Yellow or Red tag is select) What is the deficiency?
Alarms
-
Did the water motor gong operate during testing?
-
Did the electrical alarms operate during testing?
-
Did the supervisory alarms operate during testing?
-
Was the water flow alarm indicator and retard test satisfactory?
-
What was the time (seconds)
General Dry System Inspection
-
Any "No" answer, test failures or other problems found with the sprinkler system must be explained in each comment section provide with the question
-
Dry-Pipe Valve: enclosure around valves maintaining a minimum of 40F and gauge in good condition showing normal air and water pressure?
-
For freezer systems, is the gage near the compressor reading the same as the gage near the dry-pipe valve?
-
Dry Pipe Valve: free from physical damage, trim valves in appropriate (open or closed) position and no leakage from intermediate chamber?
-
Dry-pipe valves passed internal inspection?
-
Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of a branchline within the last 5 years? If the answer is "No" conduct an internal inspection
-
Low temperature alarms passed test?
-
Automatic air maintenance device passed test?
-
Strainers, filters, restricted orifices and diaphragm chambers on dry-pipe valve passed internal inspection?
-
Air leaks in dry-pipe system resulting in air pressure lost more than 10psi/week repaired?
-
Dry pipe systems maintained in dry condition?
-
Have low point drains been emptied?
-
Interior of dry-pipe valve cleaned?
-
If any of the following were discovered, was an obstruction investigation conducted?
-
If conditions were found that required flushing, was flushing of system conducted?
-
1. Defective intake screen on pump with suction from open source
2. Obstructive material discharged during waterflow tests
3. Foreign materials found in dry-pipe valves, check valves or pumps
4. Foreign material in water during drain test or plugging of inspector's test connection
5. Plugging of pipe of sprinklers found during activation or alteration
6. Failure to flush yard piping or surrounding public mains following new installation or repair
7. Record of broken mains in the vicinity
8. Abnormally frequent false-tripping of dry-pipe valve
9. System is returned to service after extended period out of service (greater than 1 year)
10. There is reason to believe the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe systems
Testing
-
Is the priming level correct and has the low air pressure signal passed its test?
-
Quick opening devices passed test?
Main Drain Test
-
Record Static Pressure (psi)
-
Record Residual Pressure (psi)
-
Was flow observed?
-
Are results comparable to previous test?
Dry-Pipe Valve Partial Flow Trip Test:
-
Record initial air pressure (psi)
-
Record initial water pressure (psi)
-
Record tripping air pressure (psi)
-
Record tripping time (seconds)
-
Above results comparable to previous tests?
Dry-Pipe Full Flow Trip Test:
-
Record initial air pressure (psi)
-
Record initial water pressure (psi)
-
Record tripping air pressure (psi)
-
Record tripping time (seconds)
-
Record water delivery time (minutes:seconds)
-
Water delivery time not required to be 60 seconds per NFPA 25
-
Above results comparable to previous tests?
-
Additional Photos
-
Additional Notes
Pre-Action/Deluge
Pre-Action Systems
-
Note: Before any Dry pipe, Deluge, or Pre-action valve is trip tested. the water supply lines should be throughly flushed. The two-inch drain below the valve should be opened wide and water at full pressure should be discharged long enough to clear pipe of any accumulation of scale or foreign material. the drip valve on the dry pipe valve should be checked before tripping the dry pipe valve to see that it is in operating condition.
-
Total Number of Pre-Action Systems?
-
Pre-Action System
Pre-Action
-
Title of Pre-Action System
-
What area is the Pre-action system protecting?
-
Approximate number of sprinkler heads on system?
-
Pre-Action Valve Photos
-
Pre-Action Valve Information (Make/Model/Year)
-
Pre-Action Valve Size (inches)
-
Is the Pre-action valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open? (if no, is it supposed to be closed?)
-
Is the valve secured?
-
Is the tamper operational?
-
What color tag was placed on the riser after inspection? (If a Yellow or Red tag is select) What is the deficiency?
Alarms
-
Did the water motor gong operate during testing?
-
Did the electrical alarms operate during testing?
-
Did the supervisory alarms operate during testing?
-
Was the water flow alarm indicator and retard test satisfactory?
-
What was the time? (seconds)
General Pre-Action Inspection
-
Any "No" answer, test failures or other problems found with the sprinkler system must be explained in each comment section provide with the question
-
Gauges in good condition and showing normal air and water pressure?
-
Valve enclosure maintaining at least 40F?
-
For freezer systems, is the gauge near the compressor reading the same as the gauge near the pre-action valve?
-
Valves free from physical damage, trim valve in appropriate (open or closed) position, no leak from valve seat, and all electrical components in sevice?
-
Is the priming level correct and has the low air pressure signal passed it's test?
-
Pre-Action valve that need to be opened to be reset passed internal inspections?
-
Low temperature alarms passed test?
-
Pipe through freezers free of ice blockage?
-
Has an internal inspection or the pipe been performed by removing the flushing connection and one sprinkler near the end of a branchline within the last five (5) years?(If the answer is "No," conduct an internal inspection)
-
Automatic air maintenance devices on preaction systems passed test?
-
Strainers, filters, restricted orifices and diaphragm chambers passed internal inspection?
-
Pre-action valve that can externally reset passed internal inspection?
-
Have low point drains been emptied?
-
If any of the following were discovered, was an obstruction investigation conducted?
-
If the conditions were found that required flushing, was flushing of system conducted?
-
1. Defective intake screen on pump with suction from open source
2. Obstructive material discharged during waterflow tests
3. Foreign materials found in dry-pipe valves, check valves or pumps
4. Foreign material in water during drain test or plugging of inspector's test connection
5. Plugging of pipe of sprinklers found during activation or alteration
6. Failure to flush yard piping or surrounding public mains following new installation
7. Record of broken mains in the vicinity
8. Abnormally frequent false-tripping of dry-pipe valve
9. System is returned to service after extended period out of service (greater than 1 year)
10. There is reason to believe the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe systems
Testing
Main Drain Test:
-
Record Static Pressure (psi)
-
Recored Residual Pressure (psi)
-
Was flow observed?
-
Are the results comparable to previous?
Full Flow Trip Test: (not required where water can't be discharged. Test all systems together that will operate simultaneously.)
-
Discharge from all nozzles unimpeded?
-
Pressure reading at hydraulically most remote nozzle? (psi)
-
Residual pressure reading at valve? (psi)
-
Above readings comparable to design valves?
-
Manual activation devices passed test?
-
Additional Notes
-
Additional Photos
Deluge Systems
-
Total Number of Deluge Systems?
-
Deluge System
Deluge
-
Title of Deluge System
-
What area is the Deluge system protecting?
-
Approximate number of sprinkler heads on system?
-
Deluge Valve Photos
-
Deluge Valve Information (Make/Model/Year)
-
Deluge Valve Size (inches)
-
Is the Deluge valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open? (if no, is it supposed to be closed?)
-
Is the valve secured?
-
Is the tamper operational?
-
What color tag was placed on the riser after inspection? (If a Yellow or Red tag is select) What is the deficiency?
Alarms
-
Did the water motor gong operate during testing?
-
Did the electrical alarms operate during testing?
-
Did the supervisory alarms operate during testing?
-
Was the water flow alarm indicator and retard test satisfactory?
-
What was the time (seconds)
General Deluge Inspection
-
Any "No" answer, test failures or other problems found with the sprinkler system must be explained in each comment section provide with the question
-
Gauges in good condition and showing normal air and water pressure?
-
Valve enclosure maintaining at least 40F?
-
For freezer systems, is the gauge near the compressor reading the same as the gauge near the pre-action valve?
-
Valves free from physical damage, trim valve in appropriate (open or closed) position, no leak from valve seat, and all electrical components in sevice?
-
Is the priming level correct and has the low air pressure signal passed it's test?
-
Deluge valve that need to be opened to be reset passed internal inspections?
-
Low temperature alarms passed test?
-
Pipe through freezers free of ice blockage?
-
Has an internal inspection or the pipe been performed by removing the flushing connection and one sprinkler near the end of a branchline within the last five (5) years?(If the answer is "No," conduct an internal inspection)
-
Automatic air maintenance devices on dry-pipe and preaction systems passed test?
-
Strainers, filters, restricted orifices and diaphragm chambers passed internal inspection?
-
Deluge valve that can externally reset passed internal inspection?
-
Have low point drains been emptied?
-
If any of the following were discovered, was an obstruction investigation conducted?
-
If the conditions were found that required flushing, was flushing of system conducted?
-
1. Defective intake screen on pump with suction from open source
2. Obstructive material discharged during waterflow tests
3. Foreign materials found in dry-pipe valves, check valves or pumps
4. Foreign material in water during drain test or plugging of inspector's test connection
5. Plugging of pipe of sprinklers found during activation or alteration
6. Failure to flush yard piping or surrounding public mains following new installation
7. Record of broken mains in the vicinity
8. Abnormally frequent false-tripping of dry-pipe valve
9. System is returned to service after extended period out of service (greater than 1 year)
10. There is reason to believe the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe systems
Testing
Main Drain Test:
-
Record Static Pressure (psi)
-
Recored Residual Pressure (psi)
-
Was flow observed?
-
Are the results comparable to previous?
Full Flow Trip Test: (not required where water can't be discharged. Test all systems together that will operate simultaneously.)
-
Discharge from all nozzles unimpeded?
-
Pressure reading at hydraulically most remote nozzle? (psi)
-
Residual pressure reading at valve? (psi)
-
Above readings comparable to design valves?
-
Manual activation devices passed test?
-
Additional Notes
-
Additional Photos
Fire Pump Assembly Information
Fire Pump Assembly Information
-
Fire pump assembly
fire pump assembly
-
Title of fire pump
-
Photos of Fire Pump
-
Inlet valve
inlet valve
-
Type of valve
-
Is valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open?
-
Is the valve secured?
-
How is it secured?
-
Is the tamper operational
-
Flow Meter bypass valve
Flow Meter bypass
-
Type of valve
-
Is valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open?
-
Is the valve secured?
-
How is it secured?
-
Is the tamper operational?
-
Test Header
Test Header
-
Type of valve
-
Is valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open?
-
Is the valve secured?
-
How is it secured?
-
Is the tamper operational?
Discharge valve
-
Type of valve
-
Is valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open?
-
Is the valve secured?
-
How is it secured?
-
Is the tamper operational?
Bypass valve
-
Type of valve
-
Is valve "Easily Accessible"?
-
Are signs visible and legible?
-
Is the valve open?
-
Is the valve secured?
-
How is it secured?
-
Is the tamper operational?
Special Systems
Special Systems
-
Were Fire Extinguisher tags currents?
-
Were Alarm panel tags currents?
-
Where vent hood tags currents?
-
Where there any other speciality systems?
Other
-
What type of system?
-
Where tags current?
Fire pump
Fire Pump
-
Fire Pump
Fire pump
-
Title of Fire pump
-
Photos of Fire Pump
-
Manufacture of Fire pump
-
Size of pump
-
Inlet size
-
Discharge size
-
Weekly Inspection
Weekly
-
Pump House/Room proper temperature (at least 70F for diesels without engine heater or 40F for other)?
-
Ventilating louvers free to operate?
-
Piping free from leaks?
-
Suction and system pressure gauges normal?
-
Suction Reservoir, if provide, full?
-
Circulation relief valve flowing water while pump churns?
-
Pressure relief valves operating with proper pressure downstream while pump is operational?
Electric Motor Driven Pumps
-
Controller indicting power on, transfer switch indicting normal situation and isolation?
-
Reverse phase alarm indicator off or normal phase rotation indicator on?
-
Oil level in vertical motor sight normal?
Testing
-
Pump started automatically?
-
Record starting pressure (psi)
-
Pump run for at least 10 minutes?
-
Record suction pressure while running (psi)
-
Record discharge pressure while running (psi)
-
Pump packing gland showing slight discharge? (adjust if necessary)
-
Packing boxes, bearings and pump casing free from overheating?
-
Record time for motor to accelerate to full speed (seconds)
-
For reduced voltage or reduced current starting, record time controller is on first step (seconds)
-
For automatic stop controllers, record time pump runs after starting (seconds)
-
All times and pressure are acceptable?
Diesel Engine Driven Pump
-
Fuel tanks at least two thirds full?
-
Controller selector switch in Auto position?
-
Battery voltage and charger readings normal?
-
Battery indicators on or failure indicators off?
-
All alarm indicators off?
-
Record engine running time meter reading
-
Is the engine running time meter appropriately higher than previous reading?
-
Oil level in right angle gear drive normal?
-
Crankcase oil level normal?
-
Cooling water level normal?
-
Electrolyte level in batteries normal?
-
Battery terminals free from corrosion?
-
Water-jacket heater operating?
Testing
-
Pump start automatically?
-
Record starting pressure (psi)
-
Did pump run for at least 30 minutes?
-
Record suction pressure while running (psi)
-
Record discharge pressure while running (psi)
-
Pump packing gland showing slight discharge? (adjust if necessary)
-
Free from unusual noises or vibrations?
-
Packing boxes, bearings and pump casing free from overheating?
-
Record time for engine to crank (seconds)
-
Record time for engine to reach running speed (seconds)
-
Engine oil pressure gauge, speed indicator, water and oil temperature indicators all reading normal?
-
Cooling water flowing from heat exchanger?
-
All times and pressures are acceptable?
Maintenance
-
Fuel tank level, tank flow switch, and solenoid valve operation acceptable?
-
Diesel fuel system free of water?
-
Flexible hoses and connectors in fuel and coolant systems acceptable?
-
Oil level and lube oil heater acceptable?
-
Is coolant level acceptable?
-
Water pump for coolant system operating?
-
Is jacket water heater for coolant system acceptable?
-
Exhaust system free of leakage?
-
Drain condensate trap on exhaust system operational?
-
Electrolyte level in batteries acceptable?
-
Connections to electrical system acceptable?
Steam Turbine Driven Pumps
-
Steam pressure gauge reading normal?
Testing
-
Record pump starting pressure(psi)
-
Record suction pressure (psi)
-
Record discharge pressure (psi)
-
Pump packing gland showing slight discharge? (adjust if necessary)
-
Free from unusual noise or vibrations?
-
Packing boxes, bearings and pump casing free from overheating?
-
Record steam pressure gauge reading (psi)
-
Record time for turbine to reach running speed (seconds)
-
All times and pressure are acceptable?
-
Monthly Inspection
Monthly
Maintenance
-
Isolation switch and circuit breaker exercised?
-
Battery case clean, dry and free of corrosion and battery's specific gravity or state of charge passed test?
-
Charger and charge rate passed visual inspection and batter charge being equalized?
-
Circuit breakers appear clean?
-
Quarterly Inspection
Quarterly
Maintenance
-
Clean strainer, filter or dirt leg in diesel fuel system?
-
Cleaned or replaced crank case breather in lubrication system?
-
Cleaned water strainer in coolant system?
-
Battery terminals clean and tight?
-
Electric system free of wire chafing?
-
Semi-Annual Inspection
Semi-Annual
Maintenance
-
Manual starting means on electrical systems operated and boxes panels and cabinets cleaned?
-
Antifreeze tested in coolant system?
-
Flexible exhaust section acceptable?
-
Alarms operated on electrical portions of diesel engine systems?
-
Annual Inspection
Annual
-
Method A: Discharge of flow through hose streams. Flow readings taken at each hose stream.
Method B: Discharge through by-pass flow meter to drain or suction reservoir. Flow readings taken by flow meter.
Method C: Discharge through by-pass flow meeter directly returned to pump suction. Flow readings taken by flow meter. -
Select Method Type
No Flow Results:
-
Suction Pressure (psi)
-
Discharge Pressure (psi)
-
Pump Speed (RPM)
Rated Flow Results:
-
Suction Pressure (psi)
-
Discharge Pressure (psi)
-
Flow (GPM)
-
Electric Voltage and Current
-
Pump Speed (RPM)
Peak Flow Results:
-
Suction Pressure (psi)
-
Discharge Pressure (psi)
-
Flow (GPM)
-
Electric Voltage and Current
-
Pump Speed (RPM)
-
Are the results above acceptable?
-
No-flow (churn) test run for 30 min?
-
Circulation relief valve and pressure relief valve operated properly during all flow test?
-
No alarm indicators or other visible abnormalities observed during the no flow test?
-
Suction screen cleaned after flow?
Low Suction Throttling Device Test:
-
Low suction pressure simulated?
-
Free from abnormalities in throttling action?
-
Free from abnormalities in return to full flow?
Automatice Transfer Switch Test:
-
Power failure simulated during peak flow?
-
Connection made alternate power source?
-
After termination of simulated power failure did motor reconnect to the normal power source?
-
All alarm conditions simulated?
-
All alarms operated?
Maintenance
-
Changed pump bearing lubrication?
-
Shaft end play acceptable?
-
Transmission coupling right angle gear drive and mechanical moving parts lubricated?
-
Circuit breakers passed trip test?
-
Emergency manual starting means operated without power?
-
Electrical connections secure?
-
Pressure switch settings calibrated?
-
Are motor bearings greased?
-
Fuel tank free of water and foreign material tank vents and overflow pipes free of obstructions, fuel piping acceptable, and oil and filters changed in diesel systems?
-
Has antifreeze been changed in coolant system?
-
Is heater exchanger clean and free of debris?
-
Are duct work and louvers (combustion air) acceptable?
-
Exhaust system free of back pressure?
-
Are exhaust system hangers and supports acceptable?
-
Is control and power wiring tight?
-
Suction, Discharge and Bypass valves open?
Standpipe and Hose System
Standpipe and Hose Systems
-
Total number of standpipe systems
-
Total number of hose systems
-
Standpipe Systems
Standpipe
-
Title of Standpipe System
-
Photos of Standpipe
-
Valve Information (Make/Model/Year)
-
Riser Size
Select Type of Inspection:
-
Daily/Weekly Inspection
Weekly
-
Enclosures around dry-pipe valves (without low temperature alarms) maintaining a minimum of 40F?
-
Relief port on reduced pressure backflow prevention assemblies not continuously discharging?
-
Gauges on dry system (no low pressure alarm) in good condintion showing normal air and water pressure?
-
Sealed control valves and valves on backflow assemblies in normal (open or closed) position, accessible, with seals in place, free from external leaks, and provided with appropritate identification?
Maintenance
-
Items found missing or in disrepair during inspection or testing?
-
Air leaks in dry-pipe systems resulting in air pressure loss more than 10psi/week repaired?
-
Dry system being maintained in dry condition?
-
If any of the following were discovered, was an obstruction investigation conducted?
-
If conditions were found that required flushing, was flushing of system conducted?
-
1. Defective intake screen for pump taking suction from open sources.
2. Obstructive material discharged during water flow.
3. Foreign materials found in dry-pipe valves, check valves or pumps.
4. Heavy discoloration of water during drain test or plugging of inspector's test connection.
5.Plugging found in piping dismantled during alterations.
6.Failure to flush yard piping or surroundings public mains following new installation or repairs.
7.Record of broken mains in the vicinity.
8.Abnormally frequent false tripping of dry-pipe valves.
9.System is returned to service after an extend period out of service (greater than a year).
10.There is reason to believe the system contains sodium silicate or it's derivativesIF con -
Monthly Inspection
Monthly
-
Dry-pipe valve: enclosures around valves (with low temperature alarms) maintaining a minimum of 40F, free from physical damage, trim valves in appropriate (open or closed) position, and no leakage from intermediate chamber?
Pressure Reducing Valves (Hose Connection)
-
Handwheels in place and in good condition?
-
Hose threads in good condition?
-
Valves not leaking?
-
Reducers and caps in place and in good condition?
Pressure Reducing Valves (Hose Rack)
-
Handwheels in place and in good condition ?
-
Valves not leaking?
-
Gauges (on dry system with low pressure alarm or on wet systems) in good condition and showing normal air and water pressure?
-
Control valves and valves on backflow assemblies (with locks or electric supervision) in normal (open or closed) position with locks or supervision in place, accessible, free from external leaks, provided with appropriate wrenches and provide with appropriate identification?
-
Alarm devices free from physical damage?
-
Alarm valves free from physical damage, valves in correct (open or closed) position, no leakage from retard chamber or drains, gauges indicating normal water pressure?
-
Quarterly Inspection
Quarterly
-
Hose Valve Outlets: Valves not leaking and no visible obstructions with caps, hose connections, valve handle, cap gasket, restricting devices in place, undamaged and in good condition?
-
Visible pipe and supports in good condition?
-
Alarm devices free from physical damage?
Testing
-
Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
-
Post indicator valves opened until spring or torsion is felt in the rod? (then closed back one quarter turn)
-
Priming water level (dry-pipe) passed test?
-
Low air pressure signal (dry-pipe) passed test?
-
Quick opening device passed test?
Main Drain Test for system downstream of backflow or pressure reducing valve (automatic water supply)
-
Record static pressure (psi)
-
Record residual pressure (psi)
-
Was flow observed?
-
Are the results comparable to previous test?
-
Semi-Annual Inspection
Semi-Annual
Testing
-
Electrical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection?
-
Valve supervisory devices indicate movement?
-
Annual Inspection
Annual
-
Hose free from mildew, cuts and deterioration, couplings of compatible threads and undamaged, gaskets in place and in good condition, hose connected?
Hose Nozzles:
-
Nozzles and gaskets in place and good condition?
-
No visible obstructions?
-
Nozzles operate smoothly?
Hose Storage Devices
-
Hose properly racked or rolled?
-
Nozzle clips in place and nozzles contained?
-
Undamaged, unobstructed and operable?
-
Will racks swing out of cabinet at least 90 degrees?
Storage Cabinets:
-
Cabinets have no corroded or damaged parts, are easy to fully, and are accessible and identified?
-
Door glazings in good condition?
-
Locks functioning in break-glass type cabinets?
-
All parts, valves, hoses and fire extinguishers accessible?
-
Adequate heat available to areas where visible wet pipe is located?
-
Interior of dry-pipe valves (which must be open to be reset) passed internal inspection?
Testing:
System Main Drain Test: (automatic water supply)
-
Record static pressure (psi)
-
Record residual pressure (psi)
-
Was flow observed?
-
Are results comparable to previous test?
-
Specific gravity of antifreeze correct?
-
All control valves operated through full range and returned to normal position?
-
Low temperature alarms in dry pipe enclosures passed test?
Dry-Pipe Valve Partial Flow Trip Test:
-
Record initial air pressure (psi)
-
Record initial water pressure (psi)
-
Record tripping air pressure (psi)
-
Record tripping time (seconds)
-
Are the above results comparable to previous test?
-
Automatic air maintenance devices on dry-pipe system passed test?
-
Backflow device passed backflow test?
-
Backflow devices pass full flow test?
-
Pressure reducing valves passed partial flow test?
Third Year Test
Dry-Pipe Valve Full Flow Trip Test:
-
Record initial air pressure (psi)
-
Record initial water pressure (psi)
-
Record tripping air pressure (psi)
-
Record tripping time (seconds)
-
Was water delivered to inspector test connection?
-
Are the above results comparable to previous test?
-
Is hose less than five years old?
-
If "No" has the hose been tested within three years?
-
If "No" test hose now and every three years.
Maintenance
-
Operating stem of all OS&Y Valves lubricated, completely closed, and reopened?
-
Hose reracked or rerolled so folds do not occur in same position?
-
Interior of dry-pipe valves cleaned?
-
Low points drained in dry systems prior to onset of freezing weather?
-
Fifth Year Inspection
Fifth Year
-
Interior of dry-pipe valve (which can be reset without opening) passed internal inspection?
-
Alarm valves and their associated strainers, filters and restriction orifices passed internal inspection?
-
Check valves internally inspected and all parts operate properly, move freely and are in good condition?
-
Strainers, filters, restricted orifices and diaphragm chambers on dry-pipe valves passed internal inspection?
Test
-
Gauges tested against calibrated one or replaced?
Automatic Standpipe Systems Tested and Required Flows:
-
Record Static Pressure (psi)
-
Record Residual Pressure (psi)
-
Record Total Flow (gpm)
-
Above flow and pressures acceptable?
-
Manual systems not a part of a sprinkler/standpipe system passed hydrostatic test
-
All hose connection and hose rack assembly pressure reducing and valves passed full flow test?
-
Add Stairwell
Stairwell
-
Add Floor
Floor
-
Which level
Tamper
-
Photo of Tamper
-
What color tag?
-
(If a Yellow or Red tag is select) What is the deficiency?
Conclusion
Conclusion
-
Although these comments are not the result of and engineering review, the following improvements are recommended for code compliance
-
Deficiencies and Recommendations
-
Additional Photos
-
Additional Notes
-
Inspector Signature
-
Do any the fire suppression inspected today need a "Fifth Year Obstruction Investigation"
-
Did the owner decline the investigation?
-
I the under signed have declined to have a fifth year obstruction investigation. I am completely aware and understand the risks associated with not having a fifth year obstruction investigation done. I do not hold GFS Texas responsible for anything that causes damage to personnel or property by an obstruction in the fire suppression system. (Type name and Title)
-
Disclaimer:
The fire inspector believes the information contained within this "Fire Inspection" report to be correct at the time of printing. The fire inspector/GFS Texas does not accept responsibility for any consequences arising from the use of the information herein. The report is based on matters which were observed or came to the attention of the inspector during the day of the assessment and should not be relied upon as an exhaustive record of all possible risks or hazards that may exist or potential improvements that can be made.
Fire suppression systems that are not properly maintained and serviced can present a risk to life safety and property. This inspection is to assist in maintaining the fire suppression system and should not be relied upon as the sole basis for maintaining the system inspected.
As Per NFPA 25 14.2.1 "An inspection of piping and branch line condition shall be conducted every five (5) years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one main and by removing a sprinkler toward the end of one branch line for the purpose of inspecting for the presence of foreign organic and inorganic material." This investigation is to insure that the fire suppression systems do not show any evidences of an obstruction that could impair the system.
GFS Texas is not responsible for any damage, to life (or/and) property due to neglect of properly heating area with wet pipe fire suppression system or dry pipe/pre-action fire suppression system that contain water due to tripped valves and system not being completely drain afterwards.
Confindetiality Statement:
In order to maintain the integrity and credibility of the fire inspection processes and to protect the parties involved, it is understood that the fire inspector will not divulge to unauthorized persons any information obtained during this inpseciton unless legally obligated to do so. -
Owner's or Owner's Representative Signature (I have read the above disclaimer and understand its content)
Witness
-
Name - Title and Signature