  • WTG # and Exhibit:

  • Conducted on

  • Prepared by

  • Project Name: Baffin Wind Project

  • Project Number: 13140009

  • WTG #:

  • Date:

  • Ground Grid Engineer and Drawing: Barr, E-01 R1 & E-02 R1

  • Interior Ring Ground Wire Size: #4/0

  • Exterior Ring Ground Wire Size: #4/0

  • Pedestal Conduit Ground Tail Size: #4/0

  • Legs Connecting Rings Size: #4/0

  • Cable Tails to Ground Rod Size: #4/0

  • Ground Rod Length is 10' and 5/8" Diameter

  • Depth Rod is Driven to: 9.5'<br>Enter Actual Depth ('):

  • See folder K:\Energy\Shared\Quality\Electrical for exothermic weld inspection guide

  • All Connections Inspected & Pass:<br>17 Welds between rings, tails, & legs<br>4 Clamps to foundation reinforcement

  • Exothermic Weld Connections Properly Bonded

  • Crimps & Welds are Secure

  • No Damage to Cables

  • Notes & Observations

  • Photos:

  • Grounding Complete with no NCN's

  • If no, are they closed

  • Installation Foreman:

  • Mortenson QA/QC Representative:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.