Title Page
-
Site conducted
-
Prepared by
-
Conducted on
-
Location
CAUSE
-
BLOCK E - Ground Floor - Manual Call Point Activation
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Building E Sounders / Beacons (Ground Floor & Roof)
-
Car Park Sounders / Beacons<br>
-
FM Hub Room Sounders / Beacons
-
"FIRE" Indication On all Landlord Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Building C District Heating Plant Room BMS Panel
-
Gas Solenoid Valve Shuts Off
-
Building E Ground Floor Extract Fans Shut Off
EFFECT ON DOORS
Doors
-
Building E Door E.ME.01 Access Control Locks Released
-
Building A Door A.PD.01 Access Control Locks Released
-
Building B Door B.PD.01 Access Control Locks Released
-
Building C Door C.PD.01 Access Control Locks Released
-
Building E Door E.PD.01 Access Control Locks Released
-
Building F Door F.PD.01 Access Control Locks Released
EFFECT ON MSFD
Damper Control Panel (D Locker Room)
-
Ref 8 Block E Cleaner Store - Closes
-
Ref 12 Block F Cleaner Store - Closes
-
Ref 5 Block A Cleaner Store - Closes
-
Ref 13 Block B Cleaner Store - Closes
-
Ref 4 Block C Cleaner Store - Closes<br>
-
Ref 1 Block C Retail Refuse Store - Closes
-
Ref 2 Block C Residential Refuse - Closes
-
Ref 16 Block D Wet Riser Tank Room - Closes
-
Ref 14 Block D Lockers Room - Closes
EFFECT ON AOV
AOV
-
Building E Head of Stair Extract Vent Opens
EFFECT ON LIFTS
Lifts
-
Lift E1 Secondary Floor
-
Lift E2 Secondary Floor
OBSERVATIONS
-
Observations