Title Page
-
Site conducted
-
Prepared by
-
Conducted on
-
Location
CAUSE
-
BLOCK F - Ground Floor - Manual Call Point Activation
EFFECT ON SOUNDERS / INDICATIONS
Sounders / Indications
-
Building D Sounders / Beacons (Ground, 1st Floor & Roof)
-
Car Park Sounders / Beacons<br>
-
FM Hub Room Sounders / Beacons
-
"FIRE" Indication On all Landlord Fire Alarm Panels
EFFECT ON PLANT
Plant
-
Building C District Heating Plant Room BMS Panel
-
Gas Solenoid Valve Shuts Off
-
Building A Ground Floor Extract Fans Shut Off<br>
-
Building B Ground Floor Extract Fans Shut Off<br>
-
Building C Ground Floor Extract Fans Shut Off<br>
-
Building D Ground Floor Extract Fans Shut Off<br>
-
Building E Ground Floor Extract Fans Shut Off<br>
-
Building F Ground Floor Extract Fans Shut Off
EFFECT ON DOORS
Doors
-
Building A Door A.SY.01 Access Control Locks Released
-
Building A Door A.SY.02 Access Control Locks Released<br>
-
Building B Door B.SY.01 Access Control Locks Released<br>
-
Building B Door B.PD.01 Access Control Locks Released
-
Building C Door C.SY.01 Access Control Locks Released
-
Building C Door C.SY.02 Access Control Locks Released
-
Building E Door E.SY.01 Access Control Locks Released<br>
-
Building E Door E.SY.02 Access Control Locks Released<br>
-
Building E Door E.SY.03 Access Control Locks Released<br>
-
Building F Door F.SY.01 Access Control Locks Released<br>
-
Building F Door F.PG.01 Access Control Locks Released<br>
-
Building F Door F.VG.01 Access Control Locks Released<br>
EFFECT ON DAMPER CONTROL PANEL / MSFD <br> <br>
Damper Control Panel (D Locker Room)
-
Building E Ground Floor MSFD Closes
-
Building F Ground Floor MSFD Closes
-
Ref 8 Block E Cleaner Store - Closes
-
Ref 12 Block F Cleaner Store - Closes
-
Ref 5 Block A Cleaner Store - Closes
-
Ref 13 Block B Cleaner Store - Closes
-
Ref 4 Block C Cleaner Store - Closes<br>
-
Ref 1 Block C Retail Refuse Store - Closes
-
Ref 2 Block C Residential Refuse - Closes
-
Ref 16 Block D Wet Riser Tank Room - Closes
-
Ref 14 Block D Lockers Room - Closes
EFFECT ON AOV / JET FANS
AOV / JET FANS
-
Car Park Smoke Extract System "ON"
OBSERVATIONS
-
Observations