Title Page

  • Site conducted

  • Prepared by

  • Conducted on

  • Location

CAUSE

  • Gas Meter Room - Manual Call Point Activation (ZONE 139)

EFFECT ON SOUNDERS / INDICATIONS

Sounders / Indications

  • Building D Sounders / Beacons (Ground, 1st Floor & Roof)

  • Car Park Sounders / Beacons<br>

  • FM Hub Room Sounders / Beacons

  • "FIRE" Indication On all Landlord Fire Alarm Panels

EFFECT ON PLANT

Plant

  • Gas Solenoid Valve Shuts Off

EFFECT ON MSFD

Damper Control Panel (D Locker Room)

  • Ref 8 Block E Cleaner Store - Closes

  • Ref 12 Block F Cleaner Store - Closes

  • Ref 5 Block A Cleaner Store - Closes

  • Ref 13 Block B Cleaner Store - Closes

  • Ref 4 Block C Cleaner Store - Closes<br>

  • Ref 1 Block C Retail Refuse Store - Closes

  • Ref 2 Block C Residential Refuse - Closes

  • Ref 16 Block D Wet Riser Tank Room - Closes

  • Ref 14 Block D Lockers Room - Closes

OBSERVATIONS

  • Observations

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.