Information

  • Maintenance PLI Plantrooms

  • Wollongong Central GPT

  • Conducted on

  • Prepared by

Maintenance Checks

1- Building 1

Plant Rooms Building 1 (Level 3)

  • Boilers (Level 3 North West Plant Room)<br>Check operational if required

  • Cooling Towers (Level 3 North Plant Room)<br>Check operational including Dosing Pumps & Chemical levels

  • Distribution Panel (North West next to Maintenance Workshop)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

  • Kitchen Extracts (Level 3 Central Plant Room).<br>-Check all VSD set in Auto<br>- Check room free of Waste & Equipment

  • Radio Repeater Building 1 (Electrical Riser outside Guest Lift Lobby Lv3)<br>- Check power to cabinet<br>- Check UPS in place and working

  • Air Handling Units & Car Park Extracts (Level 3 North, South West & South East Plant Rooms)<br>-Please check operational & VSD units set in auto.<br>- Check rooms are free of waste & Equipment.

  • Distribution Panel (North West next to Boiler House)<br>- Check door locked<br>- checked for tripped Circuits

Plant Rooms (Level 2)

  • Kitchen Extracts (Level 2 South Plant room)

  • Distribution Panel (North Western Corner outside Maintenance Workshop)<br>- Check Panel secure and door locking<br>- Checked for tripped Circuits including Dynalights.

  • Chillers (Level 2 North plant Room).

  • Air Handling Units & Car Park Extracts (Level 2 North, North East ,South East & South West Plant Rooms)<br>- Please check operational & VSD units set in auto.<br>- Check room free of waste or Equipment

Plant Rooms (Level 1)

  • Main Switch Room (North West)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

  • Distribution Panel (North West within Main Switch Room)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

  • Rainwater harvesting Tank Room (West)<br>- Check valves open & water passing through UV filter<br>- Check Life of UV filter<br>- check level of tank (weekly)

  • Air Handling Units West & South<br>- Check operational & VSD is in Auto<br>- Check room free free of Waste & Equipment

  • Fire Control Room (Outside South West Exit).<br>- check for Isolations<br>- Check for Alarms

  • EWIS Panel<br>- Check for faul

  • Mains Water Meter Room (Outside North West Exit)<br>- Check area clean and free of Waste & Equipment.<br>-

Plant Rooms (Ground Level).

  • Tenant Metering Room including Distribution Panel & IDF<br>- Check meters are functional <br>- check DB for tripped circuits including Dynalight Relays<br>- Check IDF board is secure with no loose or pulled lines.

  • Air Handling Unit (South)<br>- Check operational & VSD in auto<br>- Check room free of waste & Equipment

  • Gas isolation (Gas Safe) Switch & Intake/ meter room (South)<br>- check system is functional & not tripped<br>- Check room free of waste & Equipment

  • Communication & MDF Room (east of Gas Room end of Corridor)

Plant Rooms ( Lower Ground)

  • Distribution Panel (South west of corridor)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

  • Car Park Extracts (south-west of corridor)<br>- Check VSD operational & in Auto<br>- Check room free of waste & equipment<br>

  • Air Handling Unit (adjoining Distribution Room)<br>- Check VSD operational & in Auto<br>- Check room free of waste & equipment<br>

Plant Rooms (Basement)

  • Grease Arrestor Room (West)<br>- Check for flooding

  • Air Pelhams North & South<br>- check nothing stored within these areas.

  • Distribution Panel (North)<br>- Check panel door locked<br>- checked for tripped Circuits including Dynalight Relays<br>- Check integrity of Server

  • Air Handling Units & Car Park Extracts (North East)<br>- Please check operational & VSD units set in auto.<br>- Check room free of waste or Equipment

  • DAF Room (East)<br>- Check room not flooded<br>- check operational including Air Compressor<br>- Check stored level of both solids & fluid tank.

  • Sump Pumps (East & West) <br>- Check for high level alarms<br>- Test pumps in Manual

  • Sprinkler Tank Storage Room (South West)<br>- Check for leaks<br>-Confirm level full ( Tank level indicator)<br>- Check filler valve open

  • Sprinkler valve room including diesel pumps (South West)<br>- Check pumps on stand by<br>- check all pumps are up to pressure required

  • Valves strapped open?

2 - Building 2

Plant rooms (Level 4)

  • Cooling Towers <br>- Check operational including Dosing Pumps & Chemical levels

Plant Rooms Level 3

  • Are the Chillers and Pneumatics in Buildings 2

  • Boilers (Level 3 North West Plant Room)<br>Check operational if required

  • Gas intake including Metering

Plant Rooms (Level 2) Sprinkler Valve Room/ Fire Indication Panels

  • Fire panel checked and functioning?

  • Isolations noted?

  • Alarm panel checked and functioning?

  • Valves strapped open?

Plant Room (Level 2) Main Switch Room/ Fire Control Room / MDF

  • Main Switch Room (Left Door P2 Entry)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

  • EWIS checked and functional (Middle Room P2 Entry)

  • MDF (Right Door P2 Entry)<br>- Check no wiring exposed or disconnected

Plant Rooms (Level 1 a)

  • Air Handling Unit / Kitchen Extracts / Toilet Extracts (East,Central & West)<br>- Check operational and VSD is in Auto (if fitted) or control panels without faults/alarms<br>- check room is free of Waste & Equipment

Tower Centre Management Office Weekly Tone testing for EWIS (Thursday's between 0700 & 0730)

  • Please note areas Tested this day

Tower Plant rooms (Levels 8-12)

  • Air Handling Unit & Toilet Extracts (Level 8 Terrace entry & Levels 9-12 West corridor access)<br>- Check operational and VSD is in Auto (if fitted) or control panels without faults/alarms<br>- check room is free of Waste & Equipment

  • Roof plant room Tank , Diesel Booster Pump<br>- Check for leaks<br>- Check fuel for Pump full and Gerry Can full.

Plant room (Level Ground A)

  • Sprinkler Tank Storage Room (behind staff toilets)<br>- Check for leaks<br>-Confirm level full ( Tank level indicator)<br>- Check filler valve open

  • Sprinkler Tank Room (Check Weekly and report level)<br>

  • Auxiliary Diesel Pump<br>- Check Fuel level in tank and Gerry Cans <br>- ump showing as on duty<br>

Plant Room (Ground)

  • Grease Arrestor Room (off lift lobby BOH near CML storage )<br>- Check level of tank<br>- Check high level alarm<br>- Check pump in Manual are working<br>- Check room free of waste & Equipment

  • Water Meter (Behind Pandora stairwell to Keira St)<br>- Check for leaks

3- Building 3

Plant Room Level 5 (roof via plant room)

  • Cooling Towers <br>- Check operational including Dosing Pumps & Chemical levels

Plant Room Level 4

  • Air Handling Units / Toilet Extracts

  • Compressors

  • Boilers

Plant rooms Dock Level

  • Main Switch Room ( 2 x Doors opposite Cardboard Compactor)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

  • Gas intake Room

  • Sprinkler Valve Room including F.I.P<br>- Check all valves are strapped open<br>- Check Fire Indicator Panel is functional <br>- Check for alarms and note isolations

  • Grease Arrestor Room (opposite Wet compactor)<br>- Check level of tank<br>- Check high level alarm<br>- Check pump in Manual are working<br>- Check room free of waste & Equipment

  • MDF

  • Mains Water Meter<br>- Check valve are locked open<br>- Check no leaks

CCTV in Security

  • - Check and note any faults or Camera not working

Casual Leasing

  • Is the test and tagging up to date?

  • Are the tables and chairs in good working order?

  • Is the area surrouding all casual leases clear of hazards?

Remedial Action

  • Remedial Action Required

  • Task
  • Job Details

  • Add location

Fire Control Room Inspections

Building 1 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

Building 2 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

Building 3 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.