Information
-
Fire door Standards Being Assessed
-
GENERAL STANDARDS BEING ASSESSED ( These may not be to the certified standards of the door if the manufacturer can not be identified)
FIRE DOOR: is designed to hold back fire.
FIRE AND SMOKE DOOR: is designed to hold back fire and smoke.
DOOR LEAF: The door leaf should be certificated and in good condition with no damage. If no certification is in place an assessment of the door will be made to identify if the door is to the required standard (Notional fire door) or not a fire door.
Some old doors may still be suitable if in good condition.
The door leaf should make full contact with the door stops.
Any glass within the door leaf should be fire rated with standard marks displayed or Georgian wired glass.
DOOR FRAME AND DOOR STOPS: The frame should be in good condition and fixed secure to the wall.
The doorstops should be a minimum of 12mm, in good condition and fixed secure to the frame lining.
Soft wood: 30-minute fire rating
Hard wood: 60-minutes fire rating
GAPS BETWEEN THE DOOR LEAF AND FRAME: Gaps should be a minimum of 2mm to allow the intumescent strips to work effectively and a maximum of 4mm for a standard cold smoke seal to cover the gap and prevent smoke from breaching the door set.
Key Requirements of BS 8214:
The primary requirement of BS 8214 is the specification for gaps around the perimeter of the door leaf. Fire doors must have a 2-4mm gap around the perimeter of the door leaf to allow for the expansion of materials such as sealant, intumescent strips, and the surrounding frame when exposed to high temperatures during a fire. This gap is critical in ensuring that the door can effectively prevent the spread of fire and smoke without compromising its ability to close securely.
BS 8214 also recommends the use of linear gap seals to fill the gap between the door leaf and the frame or wall. These seals must be made of fire-resistant materials that can withstand high temperatures and prevent the spread of smoke and flames through the gap.
INTUMESCENT STRIPS AND COLD SMOKE SEALS: Preferably fitted into the door frame but can be fitted into the door leaf. In good condition and full continuous coverage of the door leaf and frame.
Smoke seals should fully cover the gap between the door leaf and frame lining.
Bottom gap: Fire door maximum 8mm, Fire & Smoke door maximum 3mm
HINGES: Hinges should be fire rated to BS EN 1935:2002 Minimum Grade 11
There should be 3 hinges on each door, in good condition free from leaks and any combustible packing.
All screws should be the correct size and all the same with no missing screws supporting the door.
Intumescent hinge pads should be fitted to prevent heat transfer from the hinge to the frame and door leaf.
LOCK AND LATCH: Should be fitted securely and holding the door closed without rattling. The door should be able to be opened without the use of a key from the inside.
Any open locks should have covered to restrict smoke and fire to travelling.
SELF CLOSING DEVICE: Various self-closers are suitable as long as they fully close the door to the door stops and hold in place. OVERHEAD, PERKO AND SELF CLOSING HINGES are the most common.
The device should be in good condition with no damage, fixed securely to the door and frame and free from any leaks.
DOOR FURNITURE: Handles should be well fitted, in good condition and suitable for use.
Letterboxes need to withstand the effects of fire.
SIGNAGE: Signage needs to be displayed on the fire doors:
Communal doors (FIRE DOOR KEEP SHUT)
Service cupboard doors (FIRE DOOR KEEP LOCKED) -
LOCATION/S:
-
Date:
-
SUMMARY OF AREAS THAT REQUIRE ATTENTION:
- 2: DOOR LEAF
- 3: FRAME AND DOORSTOPS
- 5: FIRE STOPPING TO LINEAR GAPS
- 6: HINGES
- 7: INTUMESCENT STRIPS AND COLD SMOKE SEALS
- 8: GAPS BETWEEN DOOR AND FRAME
- 9: THRESHOLD GAP
- 10 DOOR CLOSER
- 10.1 OPENING FORCE
- 11: LATCH
- 12: LOCK
- 13: LETTERBOX
- 14: HARDWARE / IRONMONGERY
- 15: HOLD OPEN DEVICE
- 16: SIGNAGE
- 17: AIR TRANSFER GRILLS
- OTHER: SEE NOTES
DOOR SURVEY
-
LOCATION:
-
DOOR CONFIGURATION:
- SINGLE LEAF
- DOUBLE LEAF
- SINGLE ACTING
- DOUBLE ACTING
- OTHER
-
LABEL NUMBER:
-
Photographs of door
-
Door Requirement
-
DOOR MATERIAL:
-
Frame approximate size: Height mm
-
Frame approximate size: Width mm
-
COMPOSITE DOOR
- CERTIFIED FIRE DOOR
- UNSURE IF THE DOOR FIRE RATED
- DOOR NOT FIRE RATED
- MANUFACTURERS DETAILS ON DOOR
- NO MANUFACTURERS DETAILS ON THE DOOR
- OTHER
-
USAGE / TRAFFIC
-
Annual service checks required (Observation when used to advised standards on report and fire door information in common parts. Report any defects)
-
Quarterly service checks require (Observation at all times and report any defects)
-
DETAIL CERTIFICATION REQUIREMENTS:
-
CERTIFICATION No:
-
MANUFACTURER:
-
DOOR ASSEMBLY REQUIREMENTS:
- SINGLE ACTION
- DOUBLE ACTION
- SINGLE LEAF
- DOUBLE LEAF
- LATCHED
- UNLATCHED
- DOOR ASSEMBLED IN LINE WITH REQUIREMENTS
- DOOR NOT ASSEMBLED IN LINE WITH REQUIREMENTS
- OTHER
-
MAXIMUM DIMENSIONS:
- HEIGHT 2040 mm X WIDTH 926 mm
- OTHER
- OTHER
- OTHER
- OTHER
- DIMENSIONS IN LINE WITH CERTIFICATION
- DIMENSIONS NOT IN LINE WITH CERTIFICATION
- OTHER
-
Under no circumstances must either the maximum height or maximum width be exceeded without separate CERTIFIRE approval.
-
DOOR FRAME:
- SOFTWOOD
- HARDWOOD
- MDF
- DENSITY: 440 KG/M3 MINIMUM
- DENSITY: 700 KG/M3 MINIMUM
- DIMENSIONS: 70 mm X 28 mm MINIMUM
- DIMENSIONS: 70 mm X 18 mm MINIMUM
- DIMENSIONS: 77 mm X 25 mm MINIMUM
- DIMENSIONS: 70 mm X 25mm MINIMUM
- DIMENSIONS
- DIMENSIONS
- DIMENSIONS
- DIMENSIONS
- CF160: DOOR STOP: 12x25 mm- pinned (Steel 40mm long), screwed or rebated from solid (min stop density 450kg/m3)
- DOOR STOP: Any size- pinned, screwed or rebated from solid (min stop density 440kg/m3)
- DOOR STOP: Any size- pinned, screwed or rebated from solid (min stop density 700kg/m3)
- DOOR STOP
- DOOR STOP
- JOINTING: Butt joints, mortice and tenon, mitred or half lapped joints with the head screw fixed to the jams using two steel screws
- JOINTING:
- JOINTING
- OTHER
- SEE NOTES
-
SUPPORTING STRUCTURE:
- BRICK
- BLOCK
- MASONRY
- TIMBER STUD MINIMUM THICKNESS: 70mm AT LEAST 30 MINUTES FIRE RESISTANCE.
- TIMBER STUD MINIMUM THICKNESS: 85mm AT LEAST 30 MINUTES FIRE RESISTANCE.
- STEEL STUD PARTITION SEE CERTIFICATION
- SEE NOTES:
-
CF380 STEEL STUD
-
INSTALLATION:
- DOOR LINING: SOFTWOOD OR HARDWOOD
- CONTINUOUS MIN WIDTH 85mm
- CONTINUOUS MIN WIDTH 85mm
- CONTINUOUS MIN WIDTH 85mm
- CONTINUOUS MIN WIDTH: SEE NOTES
- EACH DOOR JAM: FIXED AT 4 POINTS- STEEL OR NYLON FIXINGS- MAX 600 mm CENTRES- PENETRATING AT LEAST 50 mm.
- EACH DOOR JAM: FIXED AT 4 POINTS- STEEL OR NYLON FIXINGS- MAX 600 mm CENTRES- PENETRATING AT LEAST 50 mm.
- ARCHITRAVE: OPTIONAL
- ARCHITRAVE:
- ARCHITRAVE:
- SEE NOTES
-
INSTALLATION: TRIMMING
- SIDE STILES: 10 mm
- SIDE STILES: 3 mm
- SIDE STILES: 4 mm
- TOP: 3 mm
- TOP: 10 mm
- TOP: No limit providing lips are not fitted, 3 mm if lips fitted
- TOP: SEE NOTES
- BOTTOM: 10 mm
- BOTTOM: 5 mm
- BOTTOM: 6 mm
- BOTTOM: No limit providing lips are not fitted, 3 mm if lips fitted
- LABELLED AS INCREASED TRIM: 40 mm STILES, TOP & BOTTOM
- SEE NOTES
- STILES: SEE NOTES
-
DOOR TO FRAME GAPS:
- PERIMETER <4 mm
- PERIMETER <3 mm
- THRESHOLD <10 mm
- THRESHOLD <8 mm
- MEETING EDGE: 3.5 mm DOUBLE LEAF
- MEETING EDGE: 3 mm DOUBLE LEAF
- SEE NOTES
-
INTUMESCENT SEALS: CERTIFIED SEALS
- SINGLE ACTION- SINGLE LEAF: HEAD: 15 mm X 4 mm
- SINGLE ACTION- SINGLE LEAF: VERTICAL: 15 mm X 4 mm
- SINGLE ACTION- DOUBLE LEAF: HEAD: 20 mm or 15 mm X 4 mm
- SINGLE ACTION- DOUBLE LEAF: VERTICAL: 15 mm X 4 mm
- SINGLE ACTION- DOUBLE LEAF: MEETING EDGE: 10 mm X 4 mm (NOT OPPOSING)
- SINGLE ACTION- DOUBLE LEAF: HEAD AND VERTICAL EDGE: 10 mm X 4 mm + 10 mm X 4 mm FITTED INTO HEAD OF LEAF
- SINGLE ACTION- DOUBLE LEAF: MEETING EDGE: 2 X 10 mm X 4 mm or 1 X 20 mm IN ONE LEAF ONLY. ( For rebated edges one strip in rebate to each leaf edge)
- SINGLE ACTION- SINGLE LEAF: HEAD: 10 mm X 4 mm
- SINGLE ACTION- SINGLE LEAF: VERTICAL: 10 mm X 4 mm
- SEE NOTES:
-
HINGES: CE MARKED EN 1935: SIZE: HEIGHT 90-120 mm- WIDTH 27-33 mm- THICK 3 mm. MIN 8 Screws 32 mm long
- MINIMUM X 2
- MINIMUM X 3
- TOP POSITION: MAX 250 mm from top of door to top of hinge
- TOP POSITION: MAX 200 mm from top of door to top of hinge
- TOP POSITION: MAX 200 mm (+50 mm) from top of door to top hinge
- MIDDLE POSITION: Any position from MID height to MIN 200 mm from top hinge.
- MIDDLE POSITION: MID height
- BOTTOM POSITION: MAX 275 mm from bottom of door to bottom hinge
- BOTTOM POSITION: MAX 200 mm (-50/+75 mm) from bottom of door to hinge
- OTHER
- INTUMESCENT PROTECTION (NOT REQUIRED)
- INTUMESCENT PROTECTION (REQUIRED)
- MIN 4
- TOP POSITION: MAX 300 mm from top of door to top of hinge
- BOTTOM POSITION: MAX 300 mm from bottom of door to bottom hinge
- MIDDLE POSITION: Centrally between top/bottom +/- 20 mm. Min 200 mm below top hinge
- SEE NOTES
-
LOCKS & LATCHES: CE Marked for use on 30 minute timber fire doors
- MAX CASE: UP TO 164 mm X 80 mm DEEP X 14 mm WIDE
- MAX FOREND: 235 mm X 25 mm
- MAX KEEP: 185 mm X 25 mm
- STEEL OR BRASS
- POSITION: MAX 1100 mm FROM BOTTOM TO CENTRELINE OF LOCK CASE.
- MAX CASE: UP TO 100 mm X 75 mm DEEP X 19 mm WIDE
- MAX FOREND: 160 mm X 25 mm
- STEEL OR BRASS
- MAX CASE: UP TO 165 mm X 98 mm DEEP X 19 mm WIDE
- MAX FOREND: 235 mm X 25 mm
- STEEL OR BRASS
- INTUMESCENT PROTECTION: None required
- INTUMESCENT PROTECTION: Forend / Keeps bedded on intumescent mastic
- INTUMESCENT PROTECTION: 1 mm intumescent sheet material required FULL COVERAGE
- INTUMESCENT PROTECTION: 2 mm intumescent sheet material required FULL COVERAGE
- OTHER
- CF160 MAX CASE: 120 mm X 19 mm FOREND 165 mm X 26 mm
- SEE NOTES:
-
SELF-CLOSING DEVICES: CERTIFIED
- PERKO: Only internal door (Not flat entrance doors)
- OVERHEAD CLOSER: Fire Rated
- NO HOLD OPEN DEVICE
- MIN SIZE 2 CLOSING FORCE
- MIN SIZE 3 CLOSING FORCE
- MIN SIZE 4 CLOSING FORCE
-
LETTER PLATES:
- INTUMESCENT LETTER PLATES: Fitted to manufacturers instructions
- CAN BE FITTED ON SITE: By non certified approved staff
- NOT FITTED ON SITE:
- OTHER
-
DROP SEALS:
- MORTISED INTO BOTTOM/ LOWER EDGE
- NO DETAIL ON CERTIFICATION
- CONTACT MANUFACTURER
- INTUMESCENT LINING
- OTHER
-
PULL HANDLES:
- PERMITTED
- NOT PERMITTED
- Screw fixed, bolt fixed from back to back (Steel or Brass)
- Aluminium and nylon, permitted with steel through bolt fixings
- NO DETAIL ON CERTIFICATION
-
DOOR VIEWERS:
- METAL SLEEVE & OPTICAL GLASS LENS
- MAX HEIGHT: 1500 mm FROM THRESHOLD
- DIAMETER: Max 15 mm
- APERTURE: Lined with intumescent mastic
- APERTURE: Lined with intumescent sleeve
- OTHER
-
PROTECTION PLATE & SIGNAGE: Surface mounted: plastic, laminated, steel or brass
- < 2 mm THICK
- NO MORE THAN 20% of the door leaf, kick plates < 500mm, < 300 mm mid-plates
- KICK / TROLLEY PLATES UP TO 1000 mm HIGH
- PUSH PLATES: Not to exceed 200 mm wide x door height
- MID PLATES: Up to 300 mm high
-
COAT HOOKS and other surface mounted hardware
-
AIR TRANSFER GRILLS:
- FACTORY PREPARED
- APERTURE LINED WITH MIN 6 mm HARDWOOD
- APERTURE LINED WITH MIN 10 mm HARDWOOD
- APERTURE LINED: Intumescent mastic/paste
- FIXED: min 35 mm long screws min 200 centres
- FACTORY PRE-CUT BY MANUFACTURER OR CERTIFIED LICENSED DOOR PROCESSOR
- INTUMESCENT: Air transfer grille (Certified FD30) fitted on site by NON-CERTIFIED approved staff in line with CERTIFICATION
- OTHER
-
1: Certification ID in place (Label or Plug)
- YES: FD30 ID
- YES: FD60 ID
- NO CERTIFICATION ID
- NO: CONSIDERED A NOTIONAL FIRE DOOR (FITTED TO STANDARD AT TIME OF INSTALLATION)
- NO: CONSIDERED A NOMINAL FIRE DOOR
- 44/45MM
- 54MM
- NOT A SUITABLE FIRE DOOR
- SUITABLE STRUCTURE
- NO CERTIFIED ID BUT OTHER DOORS THE SAME WITH IN BUILDING ARE
- CERTIFICATION ID (UNREADABLE)
- NO ACCESS
- CERT LABEL EXAMPLE
-
2: DOOR LEAF: Good condition no damage
- GOOD CONDITION
- SLIGHT DAMAGED (REPAIRABLE)
- EXTENSIVE DAMAGE (NON REPAIRABLE)
- NOT A SUITABLE FIRE RATING
-
If the depth of the damage reveals the core of the door then the fire door leaf should be replaced. Unless the door leaf can be replaced with one of the exact same type by the same manufacturer, a complete replacement fire door-set or fire door assembly should be recommended instead
-
If the door is suspected to have been trimmed beyond its allowed tolerance, the door needs to be replaced
-
This is often due to impact damage to the faces and the edges of the door. There are tested impact protection products for fire doors and these may be used for repairs to the faces and edges, subject to the requirements of the door leaf manufacturer. If the door has been over-morticed at fixing points for hardware such as seals, grille or spy-viewer apertures, hinges and locks? The door leaf should be repaired.
Damage to the top edge, bottom edge or vertical edges of the door? Depending on the extent of the damage, a repair by using hardwood lipping may be possible. The lipping material should be a suitable hardwood of the correct size and density, and fixed using a suitable adhesive to the requirements of the door manufacturer. (minimum density 640kg/m³. The new timber should be tightly butt jointed and glued in position using urea-formaldehyde adhesive). If the door has been trimmed beyond its allowed tolerance, the door needs to be replaced. -
IS THE GLAZING APERTURE LABEL PRESENT (USUALLY ON THE TOP OF THE DOOR)
- YES
- NO
- UNKNOWN
- SUSPECTED RETROFITTED
- ETCHING IN PLACE
- ASSUMED ORIGINAL GLAZING SYSTEM
- BEEDING FIXINGS @ 150MM CENTRES
- BEEDING FIXINGS NON COMPLIANT
- BEEDING IS DAMAGED
- LABEL EXAMPLE
-
CHECK FIRE DOOR CERTIFICATION FOR CORRECT GLAZING SYSTEM
-
a complete replacement fire door-set or fire door assembly should be installed by a competent person.
-
GLAZING:
- GLASS WITHIN THE DOOR
- GLASS ABOVE THE DOOR
- GEORGIAN WIRED GLASS
- FIRE RATED GLASS
- GLASS NOT FIRE RATED
- GLASS FIRE RATED BUT DAMAGED
- GLASS SUSPECTED NOT BE FITTED CORRECTLY (SEE DIAGRAM)
- OTHER
-
See the labelled schematic of a glazing system below
-
IS THE GLAZING APERTURE LABEL PRESENT (USUALLY ON THE TOP OF THE DOOR)
- YES
- NO
- UNKNOWN
- SUSPECTED RETROFITTED
- ETCHING IN PLACE
- ASSUMED ORIGINAL GLAZING SYSTEM
- BEEDING FIXINGS @ 150MM CENTRES
- BEEDING FIXINGS NON COMPLIANT
- BEEDING IS DAMAGED
- LABEL EXAMPLE
-
This particular door leaf is not suitable for a glazed panel, the panel appears to be retro-fitted. I suggest replacing the door leaf
-
The glazing bead fixing centres are too far apart. Install more fixings at 150mm centres.
-
The glazing bead is damaged. Repair/replace the glazing bead. Install fixings at 150mm centres.
- YES
- NO
- IN PART
- GOOD PRACTICE / RECOMMENDATION
- SECURE INFORMATION BOX
- FLOOR AND BUILDING PLAN
- WAYFINDING SIGNAGE
- OTHER
-
GLAZING APERTURE LABEL
-
The glass needs to be replaced with suitable fire rated glass, fitted in line with the door certification by a competent person
-
Replace the glazing on a like-for-like basis.
-
2.1: DOOR LEAF: Fit to doorstop.
- CLOSING TO DOOR STOP (TOLERANCE 1MM TOP 3MM BOTTOM)
- NOT FITTING TO DOORSTOP WITHIN TOLLERANCE (TOLERANCE 1MM TOP 3MM BOTTOM)
- OTHER
-
RECOMMENDED ACTION REQUIRED: Door is either twisted or frame is out of line. Further investigation required.
-
OBSERVATION:
-
3: FRAME AND DOORSTOPS: Good condition, fixed well
- GOOD CONDITION
- SLIGHT DAMAGED (REPAIRABLE)
- EXTENSIVE DAMAGE (NON REPAIRABLE)
- NOT A SUITABLE FIRE RATING
-
RECOMMENDED ACTION REQUIRED: Have the door frame or stops repaired by a competent person in accordance with BM Trada repair technique
-
RECOMMENDED ACTION REQUIRED: The door frame or stops are thought to be non repairable. Install a replacement door frame , stops or both .
-
FRAME SIZE:
- 70MM >WIDE
- <70MM WIDE
- 30MM> THICK
- <30MM THICK
- OTHER
-
FRAME JOINTED
- YES
- NO
- SEE NOTES
- UNKNOWN
- SUSPECTED NO (SEE NOTES)
- JOINT SEPERATED / DAMAGED
-
POSITION OF FRAME TO WALL FIXINGS: Normally 150mm from corners at 450mm centres
- FIXINGS VISIBLE
- FIXINGS NOT VISBLE
- 150mm from corners at 450mm centres
- Not 150mm from corners at 450mm centres
- In line with manufacturers Installation instructions
- Not in line with manufacturers Installation Instructions
- Unknown if in line with manufacturers Installation Instructions
- No Certification instructions available
- OTHER
-
IN LINE WITH: Manufacturers Installation Instructions
-
IS THE FRAME FIRMLY FIXED TO THE SUPPORTING STRUCTURE:
- YES
- NO
- SEE NOTES
- UNKNOWN
- SUSPECTED NO (SEE NOTES)
- JOINT SEPERATED / DAMAGED
-
If the frame is loose then repairs will be necessary, by fixing the frame to the manufacturers installation instructions or 150mm from corners and 450mm centres if not available. The fixings should achieve minimum 50mm penetration into the wall construction.
-
ADDITIONAL ACTION:
-
MATERIAL OF DOOR FRAME / SURROUNDING STRUCTURE
- SOFTWOOD
- ASSUMPTION SOFTWOOD
- HARDWOOD
- MDF
- METAL
- OTHER
- PAINTED
- VARNISHED
- OTHER
- SURROUNDING STRUCTURE: BRICK
- SURROUNDING STRUCTURE: WOOD STUD WALL
- ASSUMPTION 60 MINUTES FIRE RATING
- ASSUMPTION 30 MINUTES FIRE RATING
- OLD STRUCTURE (NOTIONAL 30 MINUTES FIRE RATING)
- UNKOWN
- OTHER
-
IN LINE WITH: Manufacturers Installation Instructions
-
4: SIZE OF DOORSTOPS: Minimum 12 x 25mm
- 12 x 25mm
- 12 x 32mm
- 25 x 32mm
- 20 x 45mm
- OTHER
- IN LINE WITH CERTIFICATION
- UNKNOWN IF IN LINE WITH CERTIFICATION
- NOT IN LINE WITH CERTIFICATION
- OTHER
-
RECOMMENDED ACTION: Replace doorstops with correct size for the required fire rating and certification of the door
-
IN LINE WITH: Manufacturers Installation Instructions
-
LINEAR GAP SEAL TO BS8214:2016
-
BS8214:2016
-
5: FIRE STOPPING TO THE LINEAR GAP SEAL (INLINE WITH BS8214:2016) SERVICE CUPBOARDS CHECK THE INNER EDGE
- UNKNOWN (NON INTRUSIVE ASSESSMENT)
- RP TO CONFIRM WITH INSTALLER
- YES
- NO
- GAP EXPOSED
-
HEAD GAP
- 1-5MM
- 6-10MM
- 11-15MM
- 15MM-20MM
- FILLED
- ROCK FIBRE
- EXPANDING FIRE RATED FOAM
- EXPANDING FOAM
- INTUMESCENT STRIP
- CAPPED WITH MASTIC
- FILLER UNKNOWN
- NOT FILLED
- GAP >20MM (EXCESSIVE)
-
CLOSING EDGE GAP:
- 1-5MM
- 6-10MM
- 11-15MM
- 15MM-20MM
- FILLED
- ROCK FIBRE
- EXPANDING FIRE RATED FOAM
- EXPANDING FOAM
- INTUMESCENT STRIP
- CAPPED WITH MASTIC
- FILLER UNKNOWN
- NOT FILLED
- GAP >20MM (EXCESSIVE)
-
HINGE EDGE GAP:
- 1-5MM
- 6-10MM
- 11-15MM
- 15MM-20MM
- FILLED
- ROCK FIBRE
- EXPANDING FIRE RATED FOAM
- EXPANDING FOAM
- INTUMESCENT STRIP
- CAPPED WITH MASTIC
- FILLER UNKNOWN
- NOT FILLED
- GAP >20MM (EXCESSIVE)
-
Are the gaps filled in line with BS 8214:2016 standards
- YES
- NO
- UNSUITABLE
- ASSUMED YES (NON INTRUSIVE ASSESSMENT)
-
There is an architrave fitted to both sides of the door. Therefore, I was unable to verify that the linear gap seal is compliant to BS 8214
-
6: HINGES:
- FIRE RATED GRADE 11 HINGES BS EN1935
- FIRE RATED GRADE 13 HINGES BS EN1935
- FIRE RATED HINGES BS EN1935
- ORIGINAL STEEL / BRASS HINGES (NOTIONAL FIRE RATED)
- HINGES NOT FIRE RATED/CORRECT GRADE (Grade 11 minimum)
- 3 HINGES IN PLACE
- 2 HINGES IN PLACE
- HINGES FITTED WITH THE MAIN LEAF ON THE FRAME (MAY RESULT IN HINGE WRITING BEING UPSIDE DOWN)
- MAIN HINGE BODY NOT FIXED TO THE FRAME
- GOOD CONDITION
- POOR CONDITION
- NEED CLEANING AND MONITORING
- PAINTED OVER
- SCREWS MISSING / UNSUITABLE
- LEAKING OIL
- HINGES NOT SUITABLE AND NEED REPLACING
- OTHER
-
RECOMMENDED ACTION REQUIRED: Hinges are likely to be notional fire rated but this can not be confirmed. Recommend they are replaced with marked fire rated hinges minimum Grade11 fire rating for FD30 doors
-
RECOMMENDED ACTION REQUIRED: Replace the hinges with 3X suitable fire rated hinges: Minimum Grade 11 FD30, Minimum Grade 13 FD60. Recommend intumescent pads are fitted between the metal and wood surfaces to eliminate heat transfer between the surfaces.
-
Screws are missing or suspected unsuitable, which may result in early failure of the door set. Replace the missing screws with like for like items or other steel screw fixings. Screws should be no less than 38mm long and a diameter of not less than 3.8mm. If screws are not uniformed replace them all.
-
When excessive black oil is leaking from the hinges this is a sign that there is excessive wear on the components and that the hinges should be replaced. The black in the oil is metal fragments
- YES
- NO
- IN PART
- GOOD PRACTICE / RECOMMENDATION
- SECURE INFORMATION BOX
- FLOOR AND BUILDING PLAN
- WAYFINDING SIGNAGE
- OTHER
-
Replace hinges with fire rated hinges in line with the certification instructions, or minimum Grade11 for FD30 door if not available.
-
RECOMMENDED ACTION: Upgrade to fire rated hinges minimum Grade11 hinges
-
POSITION OF HINGES: TOP HINGE (Notional Range 120-180mm from door head):
- TOP HINGE: 120-200 mm
- TOP HINGE: 200-250 mm
- TOP HINGE: <120 mm
- TOP HINGE > 250 mm
- TOP HINGE SEE NOTES
- MID HINGE: MID HEIGHT
- MID HINGE: MID TO 200 mm FROM TOP HINGE
- MID HINGE: < 200 mm FROM TOP HINGE
- MID HINGE: LOWER THAN EQUAL DISTANCE
- MID HINGE SEE NOTES
- BOTTOM HINGE: 200-250 mm FROM FOOT OF DOOR (NOTIONAL)
- BOTTOM HINGE: 150-275 mm FROM FOOT OF DOOR
- BOTTOM HINGE: < 150 mm FROM DOOR FOOT
- BOTTOM HINGE: SEE NOTES
- OTHER
-
HINGES LOCATED IN LINE WITH CERTIFICATION /NOTIONAL REQUIREMENTS:
- COMPLIANT
- NON COMPLIANT
- SUPSECTED NON COMPLIANT
- UNKNOWN (NO CERTIFICATION AVAILABLE)
- IN LINE WITH GENERAL / NOTIONAL REQUIREMENTS
-
Move hinges to the correct position and repair any damage
-
Identify the correct hinge location if possible, or move hinges to a general hinge location
-
MAINTENANCE REQUIRED:
-
7: INTUMESCENT STRIPS (HOT SEAL) AND COLD SMOKE SEALS IN PLACE
- INTUMESCENT STRIPS AND COLD SMOKE SEALS IN PLACE
- INTUMESCENT STRIPS ONLY (FIRE DOOR/ 25 mm DOORSTOP)
- INTUMESCENT STRIPS ONLY (COLD SMOKE SEAL REQUIRED AS WELL)
- GOOD CONDITION
- POOR CONDITION REDUCING THE PERFORMANCE OF THE DOOR SET
- NONE IN PLACE, BUT REQUIRED TO CONTAIN FIRE AND SMOKE
- 1INCH DOORSTOPS (NOTIONAL SMOKE CONTROL)
- STRIPS SET INTO THE FRAME
- STRIPS SET INTO THE DOOR LEAF
- COVERAGE COMPLETE (ALLOWING FOR HINGES/LOCKS/KEEPS)
- COVERAGE INTERRUPTED (ALLOWING FOR HINGES/LOCKS/KEEPS)
- REPLACEMENT/ INSTALLATION REQUIRED
-
SIZE
-
IN LINE WITH: Manufacturers Installation Instructions
-
MAINTENANCE REQUIRED:
-
REPLACEMENT SIZE
-
8: GAPS: Between door leaf and frame: DOOR HEAD from hinge side:
- <2mm
- 2-4mm
- >4mm
- UNEVEN GAP
- SUSPECTED EXCESSIVE TRIMMING BEYOND THE ALLOWED TOLERANCE
-
GAP SIZE: mm
-
FROM CLOSING SIDE: mm
-
CLOSING SIDE:
- <2mm
- 2-4mm
- >4mm
- UNEVEN GAP
- SUSPECTED EXCESSIVE TRIMMING BEYOND THE ALLOWED TOLERANCE
-
GAP SIZE: mm
-
FROM HEAD TO THRESHOLD: mm
-
HINGE SIDE
- <2mm
- 2-4mm
- >4mm
- UNEVEN GAP
- SUSPECTED EXCESSIVE TRIMMING BEYOND THE ALLOWED TOLERANCE
-
GAP SIZE: mm
-
IN LINE WITH: Manufacturers Installation Instructions
-
FROM HEAD TO THRESHOLD: mm
-
MAINTENANCE REQUIRED
- YES
- NO
- IN PART
- EXCESSIVE TRIMMIMG OF THE DOOR LEAF
-
RECOMMENDED ACTION REQUIRED: Excessive gaps over 4mm between the door leaf and frame will make the cold smoke seals ineffective. If the door cannot be adjusted / eased to reduce the gaps to within 2-4mm other maintenance may be possible if the door is in good condition: Examples are: Having the door re-lipped by a competent person in line with BM Trada accepted repair techniques is a suitable solution. For minor deviations tested products may be available to mitigate the risk. https://www.londonfiresolutions.co.uk/wp-content/uploads/2016/09/BM-Trada-FireDoor-Maintenance-Scheme.pdf
-
If this is the case then you need to install a new door leaf.
-
9: THRESHOLD GAP: Fire and smoke door < 3mm Fire door < 8mm. (The gap should be as small as practicable ensuring the door is unlikely to snag on the floor even if the door drops slightly on the hinges)
- FIRE AND SMOKE DOOR <3MM
- FIRE DOOR <8MM
- DROP DOWN SMOKE (INTERNAL)
- EXTERNAL SMOKE SEAL FITTED
- NON COMPLIANT
- NON COMPLIANT: UNEVEN GAP
- DAMAGED FLOOR
- OTHER
-
THRESHOLD GAP: mm
-
RECOMMENDED ACTION REQUIRED: If the gap is under 8mm fitting a cold smoke barrier may be acceptable or install a hardwood threshold (Part M compliant) to reduce the gap. Over 8mm install a hardwood threshold (Part M compliant) or replace the door leaf. Any action taken must not restrict the door from fully closing and engaging the lock on the self-closer.
-
Is the smoke seal working and reducing the gap sufficiently
- YES
- NO
- IN PART
- GOOD PRACTICE / RECOMMENDATION
- SECURE INFORMATION BOX
- FLOOR AND BUILDING PLAN
- WAYFINDING SIGNAGE
- OTHER
-
Complete repairs to the floor to give a suitable surface for the door or seals to meet and reduce the risk of smoke and fire passing under the door
-
GAP FROM CLOSING SIDE TO HINGE SIDE:
-
HAS THERE BEEN ANY MITIGATING MAINTENANCE TO REDUCE THE RISK?
- YES VISIBLE EVIDENCE
- NO VISIBLE EVIDENCE
- EXTERNAL SMOKE BRUSH
- EXTERNAL DROP DOWN SMOKE SEAL
- INTERNAL DROP DOWN SMOKE SEAL
- GAP <8mm
- GAP >8mm
-
10: DOOR CLOSER
- OVERHEAD CONTROLLED CLOSER (FIRE RATED)
- CONCEALED JAM CLOSER:
- DOUBLE CONCEALED CLOSER (CONTROLLED ACTION)
- SELF-CLOSING HINGES
- NO SELF-CLOSER
- FULLY CLOSING TO DOORSTOPS
- NOT FULLY CLOSING TO DOORSTOPS / LATCH
- ASSUMPTION: DOOR POSSIBLY BOWED
- ASSUMPTION: DOOR FRAME OR STOPS NOT SQUARE
- ISSUE WITH CLOSER
- CE MARKED
- NO CE MARK VISIBLE
- MINIMUM POWER SIZE 3
- UNKOWN POWER SIZE
-
RECOMMENDED ACTION REQUIRED: DHF (DOOR AND HARDWARE FEDERATION): These uncontrolled closers do not meet the requirements in Approved Document B 2006 edition for self-closing devices.
-
RECOMMENDED ACTION REQUIRED: Concealed closers are acceptable as long as they close the door from any angle. If they fail, they should be replaced with overhead closers.
-
RECOMMENDED ACTION REQUIRED: If closer in place if may require adjustment to the latching speed if not install an overhead self-closer and set to fully close the door to the doorstops and engage the latch securely.
-
MODEL AND MANUFACTURER DETAILS
-
CONFIRM IF THE SELF CLOSER IS SUITABLE
- YES SUITABLE
- NOT SUITABLE
- UNKOWN: FURTHER INVESTIGATION REQUIRED
-
FITTED LOCATION:
- FITTED ON THE PULL SIDE
- FITTED ON THE PUSH SIDE
- FITTED TO THE FRAME
- FITTED TO THE ARCHITRAVE
- ARCHITRAVE DAMAGED
- MONITOR ARCHITRAVE
-
Fix the closer to the frame if damaged
-
10.1 EQUALITY ACT OPENING FORCES: Approved Document M
-
IS THE OPENING FORCE SUITABLE
- NO MORE THAN 30N (6.7 POUNDS, 3.05KG) FROM CLOSED POSITION TO 30 DEGRESS
- NO MORE THAN 22.5N (5 POUNDS/2.24KG) FROM 30 DEGRESS TO 60 DEGRESS
- MORE THAN 30N (6.7 POUNDS/3.05KG) FROM CLOSED POSITION TO 30 DEGRESS
- MORE THAN 22.5N (5 POUNDS/2.24KG) FROM 30 DEGRESS TO 60 DEGRESS
- OTHER
-
DOOR THRESHOLDS – To achieve Part M compliance, for ease of wheelchair access, door thresholds should be a maximum of 15mm. The threshold should be chamfered or ramped
- COMPLIANT
- NON COMPLIANT
- SUPSECTED NON COMPLIANT
- UNKNOWN (NO CERTIFICATION AVAILABLE)
- IN LINE WITH GENERAL / NOTIONAL REQUIREMENTS
-
MAINTENANCE REQUIRED:
-
11: LATCH: LOCKING INTO KEEP, KEYLESS EGRESS
- CYLINDER RIM NIGHTLATCH
- ROLLER BOLT CYLINDER RIM NIGHTLATCH (Allowing keyless re-entry)
- TUBULAR MORTICE LATCH
- LOCKING INTO KEEP OVERCOMING ANY FRICTION
- OPERATING SMOOTHLY
- NOT LOCKING INTO KEEP
- NOT OPERATING SMOOTHLY
- LATCH/KEEP NOT SUITABLE
- OTHER
-
RECOMMENDED ACTION REQUIRED: The lock may need adjustment to hold into keep or replacement with a suitable lock for fire doors
-
RECOMMENDED ACTION REQUIRED: Replace with a suitable lock for fire doors
-
12: MORTICE DEADLOCK: Covered to limit smoke travel, considering keyless egress
- LOCK COVERED
- LOCK OPEN ALLOWING SMOKE TRAVEL
- KEYLESS EGRESS
- NO KEYLESS EGRESS (Consideration for fire safety)
- OTHER
-
RECOMMENDED ACTION REQUIRED: Install covers onto the lock as a minimum to restrict smoke travel.
-
RECOMMENDED ACTION REQUIRED: If there is a chance of people being locked in the dwellings, consider changing the lock to a thumb turn lock offering keyless egress.
-
DEADLOCK POSITION, PROTECTION AND MARKINGS
- 800-1200 mm FROM DOOR FOOT
- <800mm FROM DOOR FOOT
- >1200mm FROM DOOR FOOT
- CE / UKCA MARKINGS
- NO: CE / UKCA VISIBLE
- INTUMESCENT PROTECTION AROUND THE LOCK SET
- NO INTUMESCENT PROTECTION AROUND THE LOCK SET VISIBLE
- INTUMESCENT PROTECTION: UNKNOWN
-
DETAILS OF MARKINGS
-
RECOMMENDED ACTION: This is likely to be too high or too low on the door leaf and not permitted within the door leaf certification. I recommend moving the lock/latch to a lower position on the door leaf in line with the certification. The mortice work left at the existing height should be suitably repaired using timber of the same density and a urea-formaldehyde-based adhesive. A competent fire door maintenance technician should be used to carry out this work.
-
IN LINE WITH: Manufacturers Installation Instructions
- YES
- NO
- UNKOWN NOMINAL FIRE DOOR (NO CERTIFICATION AVAILABLE)
- LOCKS THOUGHT TO BE UNSUITABLE
-
RECOMMENDED ACTION: Locks are replaced with fire rated locks in line with certification if available
-
RECOMMENDATION: Locks are removed and intumescent protection installed
-
13: LETTERBOX
- FIRE RATED LETTERBOX
- BRASS OR STEEL LETTERBOX COVERED BOTH SIDES AND STRING LOADED (NOTIONAL MONITOR CONDITION)
- LETTERBOX NOT SUITABLE / DAMAGED
- SEE NOTES
-
RECOMMENDED ACTION REQUIRED: Replace the letter box with a fire rated intumescent letter box.
-
14: HARDWARE: IRONMONGERY: Intumescent pads used to mitigate heat transfer between metal and timber (FD60 Requirement FD30 good practice)
- SPY HOLE IN PLACE
- HANDLES IN PLACE
- STEEL SCREWS
- COMPLETE THROUGH BOLT (STEEL)
- BOLT NOT A COMPLETE THROUGH BOLT
- INTUMESCENT PROTECTION
- INTUMESCENT PROTECTION: UNKNOWN
- NO INTUMESCENT PROTECTION
-
NON INTRUSIVE INSPECTION: It was not possible to remove door hardware to verify that the correct intumescent gaskets had been installed between the hardware components and the door / door frame. FURTHER INVESTIGATION REQUIRED
-
Replace the handle with a complete through bolt handle
-
15: HOLD OPEN DEVICES
- DEVICE SUITABLE
- DEVICE UNSUITABLE / DEFECTIVE
- OTHER
- MOUNTED HOOKS IN PLACE
- DOOR WEDGES (EVIDENCE IN THE AREA)
- DOOR NOT SUITABLE FOR HOLD OPEN DEVICES
-
RECOMMENDED ACTION REQUIRED: Replace the hold open device with a suitable device for the needs of access. Take advise from a competent person.
-
RECOMMENDED ACTION: Remove hold open devices so the door can not let fixed in position: THIS WILL BOW THE DOOR AND REPLACEMENT WILL BE REQUIRED
-
16: DOOR SIGNAGE CORRECT: KEEP LOCKED (Door with no self closer), KEEP SHUT (Door with self closer), HOLD OPEN DEVICE SIGNAGE
- SIGNAGE CORRECT
- SIGNAGE INCORRECT
- KEEP LOCKED
- KEEP SHUT
- AUTOMATIC FIRE DOOR KEEP CLEAR
- SET AT THE OPTIMAL HEIGHT 150Omm
- NOT SET AT 15OOmm OPTIMAL HEIGHT
- GOOD CONDITION
- POOR CONDITION
- KEEP LOCKED (REQUIRED)
- KEEP SHUT (REQUIRED)
- AUTOMATIC FIRE DOOR KEEP CLEAR (REQUIRED)
- <2 mm THICK
- >2 mm THICK
-
RECOMMENDED ACTION REQUIRED: Install the correct signage for the door use at the optimal height of 1500mm
-
17: AIR TRANSFER GRILLS:
- GOOD CONDITION
- POOR CONDITION
- EVIDENCE: THAT FITTED TO MANUFACTURERS SPECIFICATION
- NO EVIDENCE: THAT FITTED TO MANUFACTURERS SPECIFICATION
- SUSPECTED NOT TO BE FITTED TO MANUFACTURERS SPECIFICATION
-
RECOMMENDED ACTION REQUIRED: Replace in line with manufacturers instructions
-
RECOMMENDED ACTION: Replace door if vent required this should be fitted in line with manufacturers instruction (minimum Aperture cut by certified installer)
-
RECOMMENDED ACTION: The responsible person need to confirm certified installation or replace the door
-
OVERVIEW / GENERAL NOTES:
-
Details of the manufacturer
-
The certificate of approval will detail everything you can and cannot do with the door. There is information denoting the position of hinges, locks, glazing, the types of seals allowed and where they can be installed.
It is important that the certificate of approval is followed to the absolute letter. Failure to do so will invalidate the certification. -
An explanation of notional fire doors
According to advice by UK government, a notional fire door is a fire door that satisfied the standards applicable to fire door resistance at the time of construction. These types of doors are therefore not the most up-to-date with the latest codes, regulations and tests, and may not have been fitted with intumescent strips and smoke seals, and may not even be constructed correctly. -
The certificate of approval will detail everything you can and cannot do with the door. There is information denoting the position of hinges, locks, glazing, the types of seals allowed and where they can be installed.
It is important that the certificate of approval is followed to the absolute letter. Failure to do so will invalidate the certification.
As there is no certification details, the door will be assessed to general fire door standards, but may not be in line with the certified standards of the door manufacturer. -
Note: Where there is no certification label / marker present the door will be checked against GENERAL fire door standards. It can not be guaranteed that these were the standards that the door was tested to.
-
What are nominal fire doors?
The term 'nominal fire door' is used where an existing fire door's fire separation performance cannot be proven but it is assumed that the door will be of a suitable build to act as a fire door. -
The certificate of approval will detail everything you can and cannot do with the door. There is information denoting the position of hinges, locks, glazing, the types of seals allowed and where they can be installed.
It is important that the certificate of approval is followed to the absolute letter. Failure to do so will invalidate the certification.
As there is no certification details, the door will be assessed to general fire door standards, but may not be in line with the certified standards of the door manufacturer. -
CERTIFICATION LABEL EXAMPLE
Signed
-
Completed on behalf of
- CEAS & FIREGUARD / BAUER fire & Security Unit 95 Maple Leaf Business Park, Ramsgate CT12 5GD (01843 295241)
- CANTIUM SAFETY MANAGEMENT LTD, 22 CHURCH STREET BROADSTAIRS CT10 2TT. Tel: 07824 632474
- PASSIVE FIRE SOLUTIONS KENT LTD, 9 Coniston Avenue, Ramsgate, Kent CT11 0PW
-
Completed by:
- Steven Rigden (TechIOSH, AIFSM, Nebosh FIRE)
- Darren Fox (Certified UK FIRE DOOR TRAINING)
- (Certified UK FIRE DOOR TRAINING Fire door inspections)
- (Certified UK FIRE DOOR TRAINING Fire Door Maintenance)
- (FPA UNDERSTANDING FIRE DOORS W17c)
-
Signed:
-
Date:
-
Note: It is the freeholder and / or his agents responsibility, to inform individuals employee's, contractors, occupiers,
leaseholders and tenants of any Fire Hazards and Fire Safety measures provided and / or recommended for their protection. -
DISCLAIMER
When the sample assessment was completed (see date above) it does not reflect the business units that have been added to Business affairs since that time.
Also understand that the risks identified at that time may or may not be the same risks that would be identified today should that department repeat this process. This is a process that should be repeated periodically, depending on the level of risk.